Comparative study of heat exchanger tubes failure analysis using ECT and IRIS

被引:0
|
作者
Saffiudeen, Mohamed Fayas [1 ]
Syed, Abdullah [1 ]
Mohammed, Fasil T. [1 ]
Mughal, Mohammad Asghar [1 ]
Alamri, Yassir A. [2 ]
Alanazi, Mubarak A. [3 ]
机构
[1] Department of Mechanical Skills, Jubail Technical Institute, Royal Commission for Jubail and Yanbu, Jubail, Saudi Arabia
[2] Mechanical Engineering Department, Jubail Industrial College, Royal Commission for Jubail and Yanbu, Jubail, Saudi Arabia
[3] Electrical Engineering Department, Jubail Industrial College, Royal Commission for Jubail and Yanbu, Jubail, Saudi Arabia
关键词
Chemical industry - Concrete construction - Cooling towers - Eddy current testing - Fracture mechanics - Mineral oils - Tubing;
D O I
10.1007/s10751-024-02131-5
中图分类号
学科分类号
摘要
This article describes the comparative study of selected advanced tubing inspection nondestructive testing (NDT) methods of eddy current testing(ECT) & internal rotating inspection system (IRIS)for heat Exchanger equipment in the petrochemical industry. In this research tube material was SB 163 800 H (UNS 8810) and tubesheet material SB 564 800H (N08810). By utilizing two advanced tubing inspection methods of reporting, we can make adjustments to the process and extend the life of the heat exchanger by plugging tubes or retubing individual tubes or partial retubing or full retubing. The following data compares the suitability of ECT and IRIS for inspecting heat exchanger tubes. The capabilities of the considered NDT methods for tube inspections are presented in the study. Because of their high detectability and quick examination, nonferromagnetic materials like inconel should be tested by ECT. IRIS is ineffective on non-ferromagnetic materials like inconel based on experimentation and testing. © The Author(s), under exclusive licence to Springer Nature Switzerland AG 2024.
引用
收藏
相关论文
共 50 条
  • [11] Failure Analysis of Ethanol Vaporizer Heat Exchanger Tubes
    Sanders, S. A.
    Iwand, H. C.
    JOURNAL OF FAILURE ANALYSIS AND PREVENTION, 2013, 13 (03) : 328 - 332
  • [12] Failure analysis of AISI 321 tubes of heat exchanger
    Corte, J. S.
    Rebello, J. M. A.
    Areiza, M. C. L.
    Tavares, S. S. M.
    Araujo, M. D.
    ENGINEERING FAILURE ANALYSIS, 2015, 56 : 170 - 176
  • [13] Failure analysis of titanium heat exchanger condenser tubes
    Chen, K.M. (t113@mail.csc.com.tw), 2013, Corrosion Engineering Assocoation of the Republic of China (27):
  • [14] Failure analysis of heat exchanger tubes of four gas coolers
    Allahkaram, S. R.
    Zakersafaee, P.
    Haghgoo, S. A. M.
    ENGINEERING FAILURE ANALYSIS, 2011, 18 (03) : 1108 - 1114
  • [15] Failure Analysis of CO Shift Gas Heat Exchanger Tubes
    Cao, Huaixiang
    Zhang, Hao
    Song, Mingda
    Shen, Xiaomin
    ASME PRESSURE VESSELS AND PIPING CONFERENCE - 2014, VOL 6A, 2014,
  • [16] Corrosion Failure of Aluminum Heat Exchanger Tubes
    Ifezue D.
    Tobins F.H.
    Journal of Failure Analysis and Prevention, 2015, 15 (4) : 541 - 547
  • [17] A corrosion failure analysis of heat exchanger tubes operating in petrochemical refinery
    Rezaei, Milad
    Mahidashti, Zeynab
    Eftekhari, Sajad
    Abdi, Ehsan
    ENGINEERING FAILURE ANALYSIS, 2021, 119
  • [18] Failure analysis of 70/30 cupronickel tubes serving in a heat exchanger
    Tong, Hongtao
    Liu, Xuehui
    Sui, Yongqiang
    Liu, Feng
    Liu, Yapeng
    Li, Xiangbo
    Hou, Jian
    ENGINEERING FAILURE ANALYSIS, 2023, 152
  • [19] Failure Analysis of Stainless Steel Heat Exchanger Tubes in a Petrochemical Plant
    Adnyana, D. N.
    JOURNAL OF FAILURE ANALYSIS AND PREVENTION, 2018, 18 (02) : 413 - 422
  • [20] A Study on the Remaining Life Evaluation of Heat Exchanger Tubes Using Extreme Value Analysis
    Yoo, Eui Jong
    TRANSACTIONS OF THE KOREAN SOCIETY OF MECHANICAL ENGINEERS A, 2021, 45 (06) : 523 - 529