Pressure drop simulation and pipe size optimization in ammonia pump feeding refrigeration system

被引:0
|
作者
Research Institute of Energy Source and Motivity, Jimei University, Xiamen 361021, China [1 ]
机构
来源
Huagong Xuebao | 2008年 / SUPPL.卷 / 148-153期
关键词
Annual energy savings - Compressor suction - Performance parameters - Pressure drop model - Refrigeration compressors - Refrigeration system - Size optimization - Thermal parameters;
D O I
暂无
中图分类号
学科分类号
摘要
Mathematical models for pressure drop through both the compressor suction pipe and the evaporator returning pipe in ammonia pump feeding refrigeration system are developed. The system cycle's performance parameters are simulated by a computer program, which are developed based on both the pressure drop models and the thermal parameters models of the ammonia refrigerant. The program was used to simulate an ice making refrigeration loop with a capacity of 100 kW, a 102 m long compressor suction pipe and a 152 m long evaporator returning pipe. The simulation results show that, comparing to the traditional pipe selecting method, the pipe size optimized by the program is capable of increasing the system COP by 7.6% which corresponds to an annual energy saving of 9092 kWh. The further analysis shows the cost caused by the optimization can be recalled within two years. The life period of refrigeration compressor can be extended because its discharged temperature reduced evidently after pipe size optimization.
引用
收藏
页码:148 / 153
相关论文
共 50 条
  • [41] Effect of Helium Purification System Intake Pipe on Pressure Drop of HTGR Steam Generator
    Kadarno, P.
    Riyandwita, B. W.
    Sriyono
    Irianto, I. D.
    3RD INTERNATIONAL CONFERENCE ON NUCLEAR ENERGY TECHNOLOGIES AND SCIENCES (ICONETS) 2019, 2019, 2180
  • [42] Study on current simulation method of ammonia water absorption heat pump system
    Beijing University of Aero and Astro, Beijing 100083, China
    不详
    Taiyangneng Xuebao, 2008, 4 (454-458):
  • [43] NUMERICAL SIMULATION AND OPTIMIZATION OF CONVECTIVE HEAT TRANSFER AND PRESSURE DROP IN CORRUGATED TUBES
    Wu, Feng
    Zhou, Wenjing
    HEAT TRANSFER RESEARCH, 2012, 43 (06) : 527 - 544
  • [44] Experimental study of the relative effect of pressure drop and flow rate on the droplet size downstream of a pipe restriction
    Fossen, Martin
    Schuemann, Heiner
    JOURNAL OF DISPERSION SCIENCE AND TECHNOLOGY, 2017, 38 (06) : 826 - 831
  • [45] NUMERICAL OPTIMIZATION OF MULTI-STAGE CASCADED REFRIGERATION-HEAT PUMP SYSTEM.
    Gupta, V.K.
    1600, (05):
  • [46] Influences of make-up water pump flow and expansion pipe size upon operating pressure of the hot water heating system
    Qu, Qian
    Nuantong Kongtiao/HV & AC, 2000, 30 (05): : 50 - 51
  • [47] SIMULATION RESEARCH ON HEAT RECOVERY SYSTEM OF HEAT PUMP COMPOSITE PUMP-DRIVEN LOOP HEAT PIPE
    Liu, Shuailing
    Ma, Guoyuan
    Jia, Xiaoya
    Xu, Shuxue
    Wu, Guoqiang
    THERMAL SCIENCE, 2022, 26 (05): : 4301 - 4313
  • [48] Performance characteristics of carry-over and pressure drop through mist eliminators in absorption refrigeration system
    Hong, Sung Joo
    Kim, Byung Ryeon
    Lee, Chang Hyun
    Woo, Sung Min
    Park, Chan Woo
    INTERNATIONAL JOURNAL OF REFRIGERATION-REVUE INTERNATIONALE DU FROID, 2019, 104 : 213 - 220
  • [49] PRESSURE PULSATION IN A CENTRIFUGAL PUMP-PIPING SYSTEM (2ND REPORT, PRESSURE DISTRIBUTION IN A PIPE AND EFFECTS OF PUMP CONFIGURATION ON PRESSURE PULSATION).
    Goto, Masanori
    Nippon Kikai Gakkai Ronbunshu, B Hen/Transactions of the Japan Society of Mechanical Engineers, Part B, 1988, 54 (502): : 1371 - 1377
  • [50] A microcellular foaming simulation system with a high pressure-drop rate
    Guo, Qingping
    Wang, Jin
    Park, Chul B.
    Ohshima, Masahiro
    INDUSTRIAL & ENGINEERING CHEMISTRY RESEARCH, 2006, 45 (18) : 6153 - 6161