摘要
Due to the impacts of unconspicuous fault characteristics, noise interference, imbalanced operation condition of distribution network and so on, there are insufficiencies in reliability and universality in existing fault line detection methods for single-phase earth fault occurred in small current grounding system. A new fault line detection method for single-phase earth fault occurred in small current grounding system is proposed. Based on frequency characteristics of fault transient quantity the proposed method filters interference factors by finite impulse response (FIR) filter and extracts available fault characteristics; utilizing hierarchical clustering and based on the filtered waveform, the variation trend of transient zero-sequence capacitive current component at the beginning end of the faulty feeder is different from variation trends other healthy feeders, so the faulty feeder can be detected. Simulation results show that using the proposed method the data decomposition step by step can be avoided, and the faulty feeder under various fault conditions can be reliably detected, besides, the demand on the sampling frequency is decreased, thus the system resource can be saved and the proposed method is easy to implement. ©, 2014, Chinese Society of Astronautics. All right reserved.
引用
收藏
页码:143 / 149
相关论文
共 50 条
  • [21] Detection Method for Tree-contact Single-phase-to-ground Fault of 10 kV Overhead Line
    Liang D.
    Xu B.
    Wang P.
    Dianli Xitong Zidonghua/Automation of Electric Power Systems, 2021, 45 (14): : 149 - 157
  • [22] A Single-Phase-to-Ground Fault Detection Method Based on the Ratio Fluctuation Coefficient of the Zero-Sequence Current and Voltage Differential in a Distribution Network
    Liang, Huamin
    Li, Haifeng
    Wang, Gang
    IEEE ACCESS, 2023, 11 : 7297 - 7308
  • [23] Fault Line Selection Principle of Single-phase-to-ground Fault Based on Improved Zero-sequence Admittance
    Luan X.
    Wu S.
    Jia C.
    Yang Y.
    Zhang Z.
    Luo X.
    Dianwang Jishu/Power System Technology, 2022, 46 (01): : 353 - 360
  • [24] Single-phase-to-ground Fault Arc-extinguishing Method for Distribution Network Based on SVG Two-phase Current Injection
    Zhou X.
    Lu S.
    Chen Y.
    Liang S.
    Wu S.
    Dianli Xitong Zidonghua/Automation of Electric Power Systems, 2019, 43 (10): : 142 - 149
  • [25] Single-phase-to-ground fault line selection based on additional low-frequency-signal injection
    Zhengzhou Railway Vocational and Technical College, Zhengzhou 450052, China
    Dianli Zidonghua Shebei Electr. Power Autom. Equip., 2008, 4 (23-27):
  • [26] A Novel Single-Phase-to-Ground Fault Location Method Based on Phase Current Differences in Power Distribution Systems
    Chang, Yongle
    Tang, Jinrui
    Li, Yang
    Xiong, Binyu
    Lu, Xiaotian
    Liu, Jianchao
    2022 4TH INTERNATIONAL CONFERENCE ON SMART POWER & INTERNET ENERGY SYSTEMS, SPIES, 2022, : 1196 - 1201
  • [27] Study on Single-phase Ground Fault Location of Distribution Network Based on MDS and DBSCAN Clustering
    Mu, Zhijun
    Wu, Yuguang
    Yin, Hongxu
    Liu, Zhigang
    Liu, Chunxiu
    PROCEEDINGS OF THE 39TH CHINESE CONTROL CONFERENCE, 2020, : 6146 - 6150
  • [28] Electrical Characteristics of Medium-voltage Distribution Network with Single-phase-to-ground Fault After Arc Extinction
    Yang F.
    Li G.
    Shen Y.
    Xue Y.
    Peng H.
    Xu B.
    Dianli Xitong Zidonghua/Automation of Electric Power Systems, 2019, 43 (10): : 134 - 141
  • [29] AN INTEGRATE METHOD OF LOCATING FAULT LINE UNDER SINGLE PHASE TO GROUND FAULT IN DISTRIBUTION NETWORK
    Yang, Yao-Quan
    Jia, Li-Li
    Dang, Li-Ye
    PROCEEDINGS OF 2009 INTERNATIONAL CONFERENCE ON MACHINE LEARNING AND CYBERNETICS, VOLS 1-6, 2009, : 3701 - +
  • [30] Review of Flexible Arc Suppression Technology for Single-phase-to-ground Fault in Distribution Networks
    Guo M.
    You J.
    Zheng Z.
    Gaodianya Jishu/High Voltage Engineering, 2023, 49 (10): : 4232 - 4246