Electrical Characteristics of Medium-voltage Distribution Network with Single-phase-to-ground Fault After Arc Extinction

被引:0
|
作者
Yang F. [1 ]
Li G. [2 ]
Shen Y. [1 ]
Xue Y. [2 ]
Peng H. [3 ]
Xu B. [4 ]
机构
[1] Electric Power Research Institute of State Grid Hubei Electric Power Co. Ltd., Wuhan
[2] College of Information and Control Engineering, China University of Petroleum (East China), Qingdao
[3] State Gird Hubei Energy Comprehensive Service Co. Ltd., Wuhan
[4] Shandong Kehui Power Automation Co. Ltd., Zibo
基金
中国国家自然科学基金;
关键词
Arc extinction; Distribution network; Electrical characteristics; Single-phase-to-ground fault; System recovery;
D O I
10.7500/AEPS20180911007
中图分类号
学科分类号
摘要
The electrical variation law of the single-phase-to-ground fault in distribution network after arc extinction do not only determines the over-voltage level whether the arc is re-ignited or the re-ignition electrical characteristics, but also affects the adaptability and reliability of the fault diagnosis method. The system fault recovery process is analyzed based on the single-phase-to-ground fault equivalent circuit of distribution network. It is found that the zero-sequence network in different grounding systems have an attenuated oscillation process after arc extinction. For ungrounded system, the zero-sequence voltage amplitude is large. The oscillation frequency is much lower than the power frequency and the oscillation time is long. The phase overvoltage will last for a long time. For arc suppression coil grounding system, the zero sequence voltage amplitude is large. The oscillation frequency is slightly larger than the power frequency, and the duration is generally above 5 cycles. The beat frequency phenomenon will cause overvoltage whose amplitude is within 1.1 times of the normal level on the fault phase. For low resistance grounding system, the oscillation frequency is much higher than the power frequency. Its amplitude is small and the attenuation speed is fast. The correctness of the recovery process of single-phase-to-ground fault after are extinction in three types of grounding systems is verified by ATP-EMTP. © 2019 Automation of Electric Power Systems Press.
引用
收藏
页码:134 / 141
页数:7
相关论文
共 22 条
  • [1] Chen Y., Power System Analysis, (2005)
  • [2] Johns A.T., Aggarwal R.K., Song Y.H., Improved techniques for modelling fault arcs on faulted EHV transmission systems, IET Generation, Transmission & Distribution, 141, 2, pp. 148-154, (1994)
  • [3] Khakpour A., Franke S., Gortschakow S., Et al., An improved arc model based on the arc diameter, IEEE Transactions on Power Delivery, 31, 3, pp. 1335-1341, (2016)
  • [4] Chen B., Qu W., Yang H., Et al., Research on single phase grounding arc model and line selection for neutral ineffectively grounding system, Power System Protection and Control, 44, 16, pp. 1-7, (2016)
  • [5] Shu H., Zhu M., Huang W., Et al., Faulty line selection based on time-frequency characteristics of transient zero-sequence current, Electric Power Automation Equipment, 33, 9, pp. 1-6, (2013)
  • [6] Feng S., Cai Y., Liu M., Et al., Adaptive reclosure feeder automation method considering processing of single phase grounding fault, Automation of Electric Power Systems, 42, 3, pp. 92-97, (2018)
  • [7] Yang F., Jin X., Shen Y., Et al., Multilevel classification and identification model for earth faults in non-solidly earthed network, Automation of Electric Power Systems, 42, 15, pp. 186-191, (2018)
  • [8] Qi Z., Zheng Y., Hang T., Et al., Transient process based fault phase identification method for non-effectively grounded system, Automation of Electric Power Systems, 42, 16, pp. 155-160, (2018)
  • [9] Xing Y., Wang H., Lu Y., Faulty line selection in non-solid earthed network based on zero sequence frequency characteristic of transmission lines, Electric Power Automation Equipment, 26, 4, pp. 59-62, (2006)
  • [10] Guo L., Xue Y., Zhang L., Et al., Analysis of single-phase earth fault in low resistance grounded distribution network containing DG, Automation of Electric Power Systems, 39, 20, pp. 116-123, (2015)