Detection of partial discharge patterns in hybrid high voltage power transmission lines based on parallel recognition method

被引:0
|
作者
Yang Y. [1 ]
Wu Y. [2 ]
Gao Y. [3 ]
Huang Y. [4 ]
Liu S. [5 ]
Wang Y. [6 ]
机构
[1] Xihua University, Chengdu
[2] Chengdu Power Supply Company, State Grid Sichuan Electric Power Company, Chengdu
[3] Chongqing University of Posts and Telecommunications, Chongqing
[4] Queen Mary University of London, London
[5] Nanyang Technological University, Nanyang
[6] University of Sheffield, Sheffield
关键词
BPNN; Dung beetle optimization algorithm; Hybrid high-voltage power transmission lines; Orthogonal contrastive learning; Partial discharge;
D O I
10.7717/PEERJ-CS.2045
中图分类号
学科分类号
摘要
Due to their specially designed structures, the partial discharge detection of hybrid highvoltage power transmission lines (HHVPTL) composed of overhead lines and power cables has made it difficult to monitor the conditions of power transmission lines. A parallel recognition method for partial discharge patterns of HHVPTLs is proposed by implementing wavelet analysis and improved backpropagation neural network (BPNN) to address the shortcomings of low efficiency, poor accuracy, and inability to parallel analysis of current partial discharge (PD) detection algorithms for HHVPTLs. Firstly, considering the non-smoothness of the partial discharge of the HHVPTLs, the wavelet packet decomposition algorithm is implemented to decompose the PD of the HHVPTL and resolve the relevant signal indicators to form the attribute vectors. Then, BPNN is implemented as a classification model. A beetle optimization (DBO) algorithm based on orthogonal contrastive learning improvement is introduced to optimize the BPNN parameters since BPNN has a slow convergence problem and fails easily into a local optimum. The proposed IDBO-BPNN is employed as the model that recognizes and analyzes the parallel partial discharge patterns of HHVPTLs. Finally, the suggested model is implemented to investigate the local discharge data of an HHVPTL in the Kaggle Featured Prediction Competition and is compared with other algorithms. The experimental results indicate that the proposed model can more accurately identify whether PDs occur in an HHVPTL and detect phases where PDs occur, with higher overall accuracy and efficiency. An excellent practical performance is achieved. The proposed model can achieve the recognition accuracy of 95.5%, which is 5.3333% higher than that of the DBO-BPNN and far more than other recognition algorithms. © (2024), Yang et al.
引用
收藏
相关论文
共 50 条
  • [31] Unit Transient Based Protection for High Voltage Wind Power Transmission Lines
    Xia, Mingchao
    Lin, Yong
    Lo, Edward W. C.
    INSTRUMENTATION, MEASUREMENT, CIRCUITS AND SYSTEMS, 2012, 127 : 205 - +
  • [32] Partial Discharge Monitoring Method for High Voltage Equipment Based on Ultrasound Technology
    Jiang Yijun
    Wang Liqun
    Ren Xinzhuo
    Wu Feifei
    Song Jiajia
    Zhang Jinbo
    PROCEEDINGS OF 2019 IEEE 2ND INTERNATIONAL CONFERENCE ON ELECTRONIC INFORMATION AND COMMUNICATION TECHNOLOGY (ICEICT 2019), 2019, : 853 - 856
  • [33] Detection, recognition and location of partial discharge sources in power transformer
    Sikorski, Wojciech
    Moranda, Hubert
    Brodka, Boleslaw
    Neumann, Roman
    PRZEGLAD ELEKTROTECHNICZNY, 2010, 86 (11B): : 142 - 145
  • [34] A New Detection Method for Corona Discharge in High Voltage Power Modules Based on Decomposition Gas Analysis
    Li Kang
    Wan Liujie
    Zhang Guoqiang
    2018 INTERNATIONAL CONFERENCE ON POWER SYSTEM TECHNOLOGY (POWERCON), 2018, : 3123 - 3128
  • [35] Monitoring of high voltage power transformer using direct optical partial discharge detection technique
    Karmakar, S.
    Roy, N. K.
    Kumbhakar, P.
    JOURNAL OF OPTICS-INDIA, 2009, 38 (04): : 207 - 215
  • [36] Partial Discharge Detection Using Acoustic and Optical Methods in High Voltage Power Equipments: A Review
    Al Saedi, Malik Abdul Razzaq
    Yaacob, Mohd Muhridza
    MATERIALS, INDUSTRIAL, AND MANUFACTURING ENGINEERING RESEARCH ADVANCES 1.1, 2014, 845 : 283 - 286
  • [37] Simultaneous radial deformation and partial discharge detection of high-voltage winding of power transformer
    Karami, Hossein
    Gharehpetian, Gevork B.
    Norouzi, Yaser
    Akhavan-Hejazi, Maryam
    IET ELECTRIC POWER APPLICATIONS, 2020, 14 (03) : 383 - 390
  • [38] Application of optical fibre sensor for partial discharge detection in high-voltage power equipment
    Zargari, A
    Blackburn, TR
    IEEE 1996 ANNUAL REPORT - CONFERENCE ON ELECTRICAL INSULATION AND DIELECTRIC PHENOMENA, VOLS I & II, 1996, : 541 - 544
  • [39] ELECTROSTATIC ANALYSIS OF TRANSMISSION LINES TO SIMULATE CORONA DISCHARGE AT HIGH VOLTAGE
    Serteller, N. F. Oyman
    PROGRESS IN ELECTROMAGNETICS RESEARCH M, 2011, 20 : 107 - 113
  • [40] Design and optimization of Hilbert fractal antenna for corona discharge detection of high-voltage transmission lines
    Xiao, Xiaoming
    Wang, Qin
    Hu, Weinan
    Ran, Jun
    OPTOELECTRONIC MATERIALS AND DEVICES (ICOMD 2020), 2021, 11767