Crossflow microsand filtration in cooling tower systems to control fouling in heat exchanger devices

被引:1
|
作者
Ashok, Vaishali [1 ]
Absalan, Faezeh [1 ]
Silverwood, Alain [2 ]
Robert, Etienne [3 ]
Claveau-Mallet, Dominique [1 ]
Bedard, Emilie [1 ]
机构
[1] Polytech Montreal, Civil Geol & Min Engn Dept, Montreal, PQ, Canada
[2] Xylem Water Solut & Water Technol, Washington, DC USA
[3] Polytech Montreal, Mech Engn Dept, Montreal, PQ, Canada
来源
JOURNAL OF BUILDING ENGINEERING | 2024年 / 95卷
关键词
Side stream filtration; Building energy; HVAC; Clogging; BIOFILTRATION; CORROSION;
D O I
10.1016/j.jobe.2024.110167
中图分类号
TU [建筑科学];
学科分类号
0813 ;
摘要
In the context of global warming, there is a growing need for high-performance heat, ventilation and air conditioning systems. Fouling is a challenge, affecting heat exchanger operational and energetic performance. Side stream filtration can be used to improve water quality by reducing particle concentration in the system. The aim of this study was to assess a crossflow microsand filtration unit's efficacy in reducing fouling within an 81-plate heat exchanger, in an in-situ cooling tower circuit. A pilot heat exchanger without filtration was operated under similar conditions. After 3 years of continuous operation, visual inspection of the full-scale heat exchanger plates operating with filtration showed minimal accumulation. Pairs of facing plates (7) were scraped and rinsed to collect total solids accumulated on surfaces. Samples were resuspended and analyzed for solids and metal concentration measurements. Low average values of total volatile solids (45 mu g/cm2) and total solids (93 mu g/cm2) were indicative of a low biofilm formation. X-ray diffraction revealed the presence of calcite associated to water hardness. Low levels of iron and copper were detected despite slightly corrosive water. In contrast, the pilot heat exchanger exhibited higher deposit accumulation of total volatile solids (90 mu g/cm2) and total solids (110 mu g/cm2) after only 12 weeks of operation. These findings underscore the role of side stream filtration in reducing particle deposition and biofouling potential in full-scale cooling tower systems. Crossflow microsand filtration is a promising avenue to control fouling in building cooling tower systems, which could contribute in improving the building's energetic performance.
引用
收藏
页数:11
相关论文
共 50 条
  • [31] Aircraft heat exchanger fouling detection based on valve control command
    Shang, L.
    Liu, G.
    PROCEEDINGS OF THE INSTITUTION OF MECHANICAL ENGINEERS PART G-JOURNAL OF AEROSPACE ENGINEERING, 2012, 226 (G7) : 740 - 750
  • [32] Effects of pressure loss coefficients of heat exchanger on thermal performance of the dry cooling tower
    Ma, Huan
    Si, Fengqi
    Li, Xuebo
    Wang, Junshan
    4TH INTERNATIONAL CONFERENCE ON ENERGY AND ENVIRONMENT RESEARCH, ICEER 2017, 2017, 136 : 169 - 175
  • [33] CONTROL OF FOULING WITHIN COOLING WATER-SYSTEMS
    BIRCHALL, GA
    EFFLUENT & WATER TREATMENT JOURNAL, 1979, 19 (11): : 571 - &
  • [34] On-line control of the heat exchanger network under fouling constraints
    Markowski, Mariusz
    Trzcinski, Przemyslaw
    ENERGY, 2019, 185 (521-526) : 521 - 526
  • [35] Semi-theoretical modeling oscillatory fouling in enhanced tubes in cooling tower systems
    Li, Wei
    PROCEEDINGS OF THE ASME/JSME THERMAL ENGINEERING SUMMER HEAT TRANSFER CONFERENCE 2007, VOL 1, 2007, : 705 - 711
  • [36] Fouling control of PVC film-type cooling tower fills at power plants
    Sinha, Ashwini
    MATERIALS PERFORMANCE, 2008, 47 (02) : 50 - 54
  • [37] Modelling, simulation, and experimental evaluation of a crossflow heat exchanger for an aircraft environmental control system
    Shah, S.
    Liu, G.
    Greatrix, D. R.
    PROCEEDINGS OF THE INSTITUTION OF MECHANICAL ENGINEERS PART G-JOURNAL OF AEROSPACE ENGINEERING, 2010, 224 (G5) : 613 - 623
  • [38] Thermal performance analysis of heat exchanger for closed wet cooling tower using heat and mass transfer analogy
    Yoo, Seong-Yeon
    Kim, Jin-Hyuck
    Han, Kyu-Hyun
    JOURNAL OF MECHANICAL SCIENCE AND TECHNOLOGY, 2010, 24 (04) : 893 - 898
  • [39] Experimental Study on the Heat Release Operational Characteristics of a Soil Coupled Ground Heat Exchanger with Assisted Cooling Tower
    Yang, Weibo
    Yang, Binbin
    Xu, Rui
    ENERGIES, 2018, 11 (01):
  • [40] Thermal performance analysis of heat exchanger for closed wet cooling tower using heat and mass transfer analogy
    Seong-Yeon Yoo
    Jin-Hyuck Kim
    Kyu-Hyun Han
    Journal of Mechanical Science and Technology, 2010, 24 : 893 - 898