Single Ended Fault Location Method for Lines Connected with Inverter Based Renewable Resources

被引:0
|
作者
Naidu, O. D. [1 ]
Aarthi, V [1 ]
Likhitha, Kukkala [1 ]
机构
[1] Hitachi Energy, Grid Automat R&D, Bangalore, India
关键词
Fault location; single ended; transmission line; inverter based renewable resource;
D O I
10.1109/APPEEC57400.2023.10562020
中图分类号
TE [石油、天然气工业]; TK [能源与动力工程];
学科分类号
0807 ; 0820 ;
摘要
The integration of renewable energy sources based on inverters has a negative impact on the accuracy of impedance-based single-ended fault locators due to the phase angle shift introduced by inverter controls and grid codes. In this paper, we proposed two practical approaches to mitigate these challenges. The first approach uses remote current measurement in addition to local measurements when a reliable communication system is available, and the second approach uses local measurements alone to estimate in the absence of communication channel and compensate for the phase angle deviation. Without making any additional infrastructure changes, the proposed method can be used in existing protection relays. The accuracy of the developed method is validated by laboratory experimental and field data.
引用
收藏
页数:6
相关论文
共 50 条
  • [21] Frequency domain double-ended method of fault location for transmission lines
    Faybisovich, V.
    Khoroshev, M. I.
    [J]. 2008 IEEE/PES TRANSMISSION & DISTRIBUTION CONFERENCE & EXPOSITION, VOLS 1-3, 2008, : 941 - +
  • [22] A Single-Terminal Fault Location Method for Transmission Lines Integrated by Inverter-Type Source
    Chang, Peng
    Song, Guobing
    Hou, Junjie
    Xu, Ruidong
    [J]. IEEE TRANSACTIONS ON POWER DELIVERY, 2022, 37 (03) : 1704 - 1713
  • [23] A novel noniterative single-ended fault location method with distributed parameter model for AC transmission lines
    Duan, Mengzhao
    Liu, Yu
    Lu, Dian
    Pan, Ruiyu
    [J]. INTERNATIONAL JOURNAL OF ELECTRICAL POWER & ENERGY SYSTEMS, 2023, 153
  • [24] Single-ended Fault Location Method Based on Traveling Wave Panoramic Fault Characteristics Deep Mining
    Deng, Feng
    Zeng, Zhe
    Zu, Yarui
    Huang, Yifei
    Feng, Sixu
    Zhang, Zhen
    Zeng, Xiangjun
    [J]. Zhongguo Dianji Gongcheng Xuebao/Proceedings of the Chinese Society of Electrical Engineering, 2024, 44 (04): : 1310 - 1321
  • [25] RESEARCH ON HVDC SINGLE-ENDED FAULT TRAVELING WAVE LOCATION METHOD BASED ON FASTICA
    Yue, Liu
    [J]. PROCEEDINGS OF 2016 INTERNATIONAL CONFERENCE ON AUDIO, LANGUAGE AND IMAGE PROCESSING (ICALIP), 2016, : 509 - 514
  • [26] Six-sequence Component Based Single Ended Fault Location Method of Transmission Line
    Tian, Bin
    Li, Zhen-xing
    Yao, Yuan
    Wang, Lu
    Wang, Xin
    [J]. 2016 INTERNATIONAL CONFERENCE ON ELECTRICAL ENGINEERING AND AUTOMATION (ICEEA 2016), 2016,
  • [27] A novel principle of single-ended fault location technique for EHV transmission lines
    Ha, HX
    Zhang, BH
    Lv, ZL
    [J]. IEEE TRANSACTIONS ON POWER DELIVERY, 2003, 18 (04) : 1147 - 1151
  • [28] A novel principle of single-ended fault location technique for EHV transmission lines
    Ha, HX
    Zhang, BH
    Lu, ZL
    [J]. POWERCON 2002: INTERNATIONAL CONFERENCE ON POWER SYSTEM TECHNOLOGY, VOLS 1-4, PROCEEDINGS, 2002, : 2106 - 2110
  • [29] New Principle of Single-Ended Fault Location Base on Verification for Transmission lines
    Yu Jiangtao
    Jiao Yanjun
    Wang Zengping
    [J]. 2010 ASIA-PACIFIC POWER AND ENERGY ENGINEERING CONFERENCE (APPEEC), 2010,
  • [30] Modern single-ended fault location in HVDC systems based on fault transients
    Burek, Arkadiusz
    Balcerek, Przemyslaw
    Smolana, Michal
    Dawidowski, Pawel
    Sipowicz, Jakub
    [J]. 2019 MODERN ELECTRIC POWER SYSTEMS (MEPS), 2019,