High impedance fault detection in distribution networks using randomness of zero-sequence current signal: A detrended fluctuation analysis approach

被引:2
|
作者
Gadanayak, Debadatta Amaresh [1 ]
Mishra, Manohar [1 ]
Bansal, Ramesh C. [2 ,3 ]
机构
[1] SOA Deemed Be Univ, Dept Elect & Elect Engn, Bhubaneswar, Odisha, India
[2] Univ Sharjah, Dept Elect Engn, Sharjah, U Arab Emirates
[3] Univ Pretoria, Dept Elect Elect & Comp Engn, Pretoria, South Africa
关键词
Detrended fluctuation analysis; High impedance fault; Zero-sequence current; Fault recognition; Distributed network protection; WAVELET TRANSFORM; METHODOLOGY;
D O I
10.1016/j.apenergy.2024.123452
中图分类号
TE [石油、天然气工业]; TK [能源与动力工程];
学科分类号
0807 ; 0820 ;
摘要
Detection of high impedance faults (HIFs) in low and medium voltage distribution networks has always been challenging due to their lower magnitude and random current characteristics. Conventional overcurrent relays are ineffective in detecting HIFs because of the low fault current associated with them. Consequently, existing HIF detection schemes predominantly rely on features extracted from the frequency, time-frequency, or symmetrical component domains. However, these methods are often limited in their effectiveness under specific conditions, such as particular voltage levels, conductor types, or environmental factors, due to the multifaceted nature of HIF currents, which depend upon a variety of factors such as type of materials, voltage level, wetness of the surface, shape of the conductor, and even the weather conditions. On the other hand, due to the intrinsic presence of arcing in the HIF phenomenon, the resultant fault current consistently assumes a random character, and this inherent randomness can be leveraged as a potential feature for fault detection. This paper proposes a new HIF detection method by analyzing the randomness or unpredictability of the fault current signals. The Detrended fluctuation analysis (DFA) is innovatively employed to assess the unpredictability of the lower frequency component of the zero -sequence current by examining its instantaneous amplitude envelope. The accuracy of the proposed approach is verified with extensive simulation data of fault events under diverse operative conditions. The security of the proposed scheme is also verified under several no-fault transient circumstances, such as capacitor switching and load perturbation. The computational efficiency of the method has been verified through the process -in -loop (PIL) simulation using cost-effective hardware.
引用
收藏
页数:14
相关论文
共 50 条
  • [41] A method for preventing mal-operation of zero-sequence direction component using current fault component
    Song G.
    Xu H.
    Fan Z.
    Wang C.
    Xu, Haiyang (xuhaiyang.2009@stu.xjtu.edu.cn), 1600, Automation of Electric Power Systems Press (40): : 114 - 120
  • [42] High Impedance Arc Fault Detection Based on the Harmonic Randomness and Waveform Distortion in the Distribution System
    Wei, Mingjie
    Shi, Fang
    Zhang, Hengxu
    Jin, Zongshuai
    Terzija, Vladimir
    Zhou, Jian
    Bao, Hailong
    IEEE TRANSACTIONS ON POWER DELIVERY, 2020, 35 (02) : 837 - 850
  • [43] Fault line selection method of grounding fault with high resistance in resonant grounding system based on intensive zero-sequence impedance characteristics
    Shao W.
    Liu Y.
    Cheng Y.
    Zhang Z.
    Cheng C.
    Dianli Zidonghua Shebei/Electric Power Automation Equipment, 2021, 41 (11): : 120 - 126
  • [44] A Visual Fault Detection Method for Induction Motors Based on a Zero-Sequence Current and an Improved Symmetrized Dot Pattern
    Huang, Liangyuan
    Wen, Jihong
    Yang, Yi
    Chen, Ling
    Shen, Guoji
    ENTROPY, 2022, 24 (05)
  • [45] Analysis on Zero-sequence Current Variation Characteristic for Feeders of Distribution Network at Different Residual Current Compensation Factors
    Tang J.
    Yang C.
    Cheng L.
    Tang, Jinrui (tangjinrui001@126.com), 1600, Automation of Electric Power Systems Press (41): : 125 - 132
  • [46] Monitoring, Detection and Locating of Transient Earth Fault Using Zero-Sequence Current and Cable Screen Earthing Current in Medium Voltage Cable and Mixed Feeders
    Lowczowski, Krzysztof
    Olejnik, Bartosz
    ENERGIES, 2022, 15 (03)
  • [47] A new approach to high impedance fault detection using Wavelet Packet Analysis
    Lazkano, A
    Ruiz, J
    Aramendi, E
    Leturiondo, LA
    NINTH INTERNATIONAL CONFERENCE ON HARMONICS AND QUALITY OF POWER PROCEEDINGS, VOLS I - III, 2000, : 1005 - 1010
  • [48] Inter-turn faults detection in Induction Motor drives using zero-sequence signal injection
    Otero, M.
    Bossio, G. R.
    de la Barrera, P. M.
    Tyshakin, O.
    Leidhold, R.
    2018 INTERNATIONAL SYMPOSIUM ON POWER ELECTRONICS, ELECTRICAL DRIVES, AUTOMATION AND MOTION (SPEEDAM), 2018, : 202 - 207
  • [49] A novel approach for cardiac pathology detection using phonocardiogram signal multifractal detrended fluctuation analysis and support vector machine classification
    Hakkoum K.N.
    Cherif L.H.
    Research on Biomedical Engineering, 2024, 40 (02) : 331 - 346