High impedance fault detection in distribution networks using randomness of zero-sequence current signal: A detrended fluctuation analysis approach

被引:2
|
作者
Gadanayak, Debadatta Amaresh [1 ]
Mishra, Manohar [1 ]
Bansal, Ramesh C. [2 ,3 ]
机构
[1] SOA Deemed Be Univ, Dept Elect & Elect Engn, Bhubaneswar, Odisha, India
[2] Univ Sharjah, Dept Elect Engn, Sharjah, U Arab Emirates
[3] Univ Pretoria, Dept Elect Elect & Comp Engn, Pretoria, South Africa
关键词
Detrended fluctuation analysis; High impedance fault; Zero-sequence current; Fault recognition; Distributed network protection; WAVELET TRANSFORM; METHODOLOGY;
D O I
10.1016/j.apenergy.2024.123452
中图分类号
TE [石油、天然气工业]; TK [能源与动力工程];
学科分类号
0807 ; 0820 ;
摘要
Detection of high impedance faults (HIFs) in low and medium voltage distribution networks has always been challenging due to their lower magnitude and random current characteristics. Conventional overcurrent relays are ineffective in detecting HIFs because of the low fault current associated with them. Consequently, existing HIF detection schemes predominantly rely on features extracted from the frequency, time-frequency, or symmetrical component domains. However, these methods are often limited in their effectiveness under specific conditions, such as particular voltage levels, conductor types, or environmental factors, due to the multifaceted nature of HIF currents, which depend upon a variety of factors such as type of materials, voltage level, wetness of the surface, shape of the conductor, and even the weather conditions. On the other hand, due to the intrinsic presence of arcing in the HIF phenomenon, the resultant fault current consistently assumes a random character, and this inherent randomness can be leveraged as a potential feature for fault detection. This paper proposes a new HIF detection method by analyzing the randomness or unpredictability of the fault current signals. The Detrended fluctuation analysis (DFA) is innovatively employed to assess the unpredictability of the lower frequency component of the zero -sequence current by examining its instantaneous amplitude envelope. The accuracy of the proposed approach is verified with extensive simulation data of fault events under diverse operative conditions. The security of the proposed scheme is also verified under several no-fault transient circumstances, such as capacitor switching and load perturbation. The computational efficiency of the method has been verified through the process -in -loop (PIL) simulation using cost-effective hardware.
引用
收藏
页数:14
相关论文
共 50 条
  • [1] Detection of High Impedance Grounding Fault in Distribution Network Based on Interval Slope Curves of Zero-sequence Current
    Wei M.
    Shi F.
    Zhang H.
    Xu B.
    Wang P.
    Dianli Xitong Zidonghua/Automation of Electric Power Systems, 2020, 44 (14): : 164 - 171
  • [2] High Impedance Grounding Fault Detection in Resonance Grounding System Based on Nonlinear Distortion of Zero-sequence Current
    Zhu, Jiran
    Haiguo, Tang
    Leng, Hua
    Sun, Jiao
    Huang, Chun
    2020 5TH INTERNATIONAL CONFERENCE ON SMART GRID AND ELECTRICAL AUTOMATION (ICSGEA 2020), 2020, : 74 - 78
  • [3] Zero Sequence Current Detection Method of High Impedance Faults Using Distortion Waveform in Distribution Networks
    Manmoh, Jiraphat
    Srirattanawichaikul, Watcharin
    2023 IEEE PES 15TH ASIA-PACIFIC POWER AND ENERGY ENGINEERING CONFERENCE, APPEEC, 2023,
  • [4] Fault detection method for unbalanced distribution networks based on flexible regulation of zero-sequence voltage
    Zhang W.
    Wang L.
    Xue Y.
    Xu B.
    Wang C.
    Dianli Xitong Baohu yu Kongzhi/Power System Protection and Control, 2024, 52 (11): : 159 - 169
  • [5] Impedance fault location technology for a distribution network based on a zero-sequence component
    Qi Z.
    Huang Z.
    Chen Y.
    Dianli Xitong Baohu yu Kongzhi/Power System Protection and Control, 2023, 51 (06): : 54 - 62
  • [6] A Single-Phase-to-Ground Fault Detection Method Based on the Ratio Fluctuation Coefficient of the Zero-Sequence Current and Voltage Differential in a Distribution Network
    Liang, Huamin
    Li, Haifeng
    Wang, Gang
    IEEE ACCESS, 2023, 11 : 7297 - 7308
  • [7] Estimating Zero-Sequence Line Impedance and Fault Resistance Using Relay Data
    Das, Swagata
    Ananthan, Sundaravaradan Navalpakkam
    Santoso, Surya
    IEEE TRANSACTIONS ON SMART GRID, 2019, 10 (02) : 1637 - 1645
  • [8] Induction Motor Fault Diagnosis Based on Zero-Sequence Current Analysis
    Duda, Arkadiusz
    Drozdowski, Piotr
    ENERGIES, 2020, 13 (24)
  • [9] Detection of High Impedance Fault in Distribution Networks
    Kavaskar, Sekar
    Mohanty, Nalin Kant
    AIN SHAMS ENGINEERING JOURNAL, 2019, 10 (01) : 5 - 13
  • [10] Detection method of high impedance grounding fault based on differential current of zero-sequence current projection and neutral point current in low-resistance grounding system
    Sheng Y.
    Cong W.
    Bu X.
    Li X.
    Dianli Zidonghua Shebei/Electric Power Automation Equipment, 2019, 39 (03): : 17 - 22and29