Research on Ultraviolet Characteristic Parameters of DC-Positive Polarity Corona Discharge on Conductors

被引:0
|
作者
Dai, Youquan [1 ]
Zhang, Zhanlong [1 ]
Dong, Zijian [1 ]
Wu, Yongye [1 ,2 ]
Jun, Deng [1 ]
机构
[1] Chongqing Univ, Sch Elect Engn, Chongqing 400044, Peoples R China
[2] Chengdu Power Supply Co, Chengdu 610002, Peoples R China
来源
APPLIED SCIENCES-BASEL | 2024年 / 14卷 / 08期
基金
中国国家自然科学基金;
关键词
corona discharge; UV imaging; photon number; gain; observation distance; AIR-PRESSURE; PERFORMANCE; VOLTAGES;
D O I
10.3390/app14083258
中图分类号
O6 [化学];
学科分类号
0703 ;
摘要
The detection of corona-related defects in transmission lines has been included in the work of transmission line defect detection. Ultraviolet detection technology has gradually been widely applied in the field of corona discharge detection. However, the current research on the application of ultraviolet detection technology in transmission lines is relatively simple and mainly limited to using changes in the photon count to determine whether corona discharge has occurred. To address this, this study used a mini corona cage to simulate transmission lines and measured the changes in the photon count, spot area, and corona current in the corona inception process of different types of smooth, stainless-steel conductors. This study also investigated the variations in the photon count and spot area depending on conductor corona intensity, ultraviolet imager gain, and observation distance. The results show that the photon count and spot area can, to some extent, reflect the intensity of corona discharge. Both the photon count and spot area exhibited quadratic relationships with the voltage. As the observation distance increased, both the photon count and spot area showed exponential decay. The photon count exhibited a trend of initially increasing, then decreasing, and finally increasing again with the increase of gain, while the spot area showed exponential growth with increasing gain. The photon count and spot area can complement each other to identify and characterize the intensity of corona discharge.
引用
收藏
页数:16
相关论文
共 50 条
  • [21] Ozone production in the positive DC corona discharge: Model and comparison to experiments
    Chen, JH
    Davidson, JH
    PLASMA CHEMISTRY AND PLASMA PROCESSING, 2002, 22 (04) : 495 - 522
  • [22] TECHNOLOGICAL PARAMETERS THAT INFLUENCE THE PRODUCTION OF OZONE IN A dc CORONA DISCHARGE.
    Peyrous, R.
    Lacaze, C.
    Ozone: Science and Engineering, 1986, 8 (02): : 107 - 127
  • [23] Research on mechanism and ultraviolet imaging of corona discharge of electric device faults
    Zang Chunyan
    Zhao Xinjie
    He Shuang
    Lei Hongcai
    Jiang Zhenglong
    Ye Huisheng
    Jiang Zhiwen
    CONFERENCE RECORD OF THE 2008 IEEE INTERNATIONAL SYMPOSIUM ON ELECTRICAL INSULATION, VOLS 1 AND 2, 2008, : 690 - +
  • [24] Research on the Simulation Method for HVDC Continuous Positive Corona Discharge
    Liu, Yingyi
    Li, Zhuqing
    Qin Zhimin
    Li Xiaoguang
    Liu Yuanqing
    Huang Hui
    Huang Feng
    IEEE TRANSACTIONS ON PLASMA SCIENCE, 2022, 50 (09) : 2805 - 2814
  • [25] Comparison of Different Characteristic Parameters Acquired by UV Imager in Detecting Corona Discharge
    Zhang, Zhijin
    Zhang, Wei
    Zhang, Dongdong
    Xiao, Yao
    Deng, Jun
    Xia, Gulin
    IEEE TRANSACTIONS ON DIELECTRICS AND ELECTRICAL INSULATION, 2016, 23 (03) : 1597 - 1604
  • [26] Simulation of a Positive dc Corona Discharge in a Needle-Plane Electrode Configuration
    Amiour, Nesrine
    Ziari, Zehira
    Sahli, Salah
    PROCEEDINGS 2018 3RD INTERNATIONAL CONFERENCE ON ELECTRICAL SCIENCES AND TECHNOLOGIES IN MAGHREB (CISTEM), 2018, : 383 - 386
  • [27] Comparison of laser induced streamers to regular streamers in the positive DC corona discharge
    Kocik, M
    Mizeraczyk, J
    Ohkubo, T
    Kanazawa, S
    13th International School on Quantum Electronics: Laser Physics and Applications, 2005, 5830 : 130 - 134
  • [28] Comparison of the AC barrier corona with DC positive and negative coronas and barrier discharge
    Akishev, YS
    Dem'yanov, AV
    Karal'nik, VB
    Monich, AE
    Trushkin, NI
    PLASMA PHYSICS REPORTS, 2003, 29 (01) : 82 - 91
  • [29] Properties of corona discharge under positive DC voltage at low atmospheric pressure
    Yu, D.
    Farzaneh, M.
    Zhang, J.
    Shu, L.
    Sima, W.
    Sun, C.
    2006 ANNUAL REPORT CONFERENCE ON ELECTRICAL INSULATION AND DIELECTRIC PHENOMENA, 2006, : 393 - 396
  • [30] Comparison of the AC barrier corona with DC positive and negative coronas and barrier discharge
    Yu. S. Akishev
    A. V. Dem’yanov
    V. B. Karal’nik
    A. E. Monich
    N. I. Trushkin
    Plasma Physics Reports, 2003, 29 : 82 - 91