Failure Analysis of Once-Through Steam Generator (OTSG) Tube

被引:1
|
作者
Tina, Wahida [1 ]
Donaldson, Elizabeth [1 ]
Dickinson, Thomas E. [2 ]
Schmidt, William Hal [3 ]
机构
[1] Department of Asset Management, Lansing Board of Water and Light, 830 E. Hazel, Lansing,MI,48912, United States
[2] REO Town Plant, Peffley Chiller Plant, Lansing Board of Water and Light, 1201 S Washington Ave, Lansing,MI,48910, United States
[3] Department of Project Engineering, Lansing Board of Water and Light, 1201 S Washington Ave, Lansing,MI,48910, United States
来源
关键词
Descaling - Energy dispersive X ray analysis - Failure (mechanical) - Flow of gases - Heat exchangers - Heat transfer - Heat treatment - Nickel compounds - Optical emission spectroscopy - Scanning electron microscopy - Steam - Steam generators - Stress corrosion cracking - Thermoelectric power plants - Tubing - X ray diffraction analysis;
D O I
10.1115/1.4062769
中图分类号
学科分类号
摘要
The once-through steam generator (OTSG) produces superheated steam using purified feed water. The plant-specific water quality, steam quality, high temperature, and pressure operations lead to the leakage of the OTSG tubes with economic, safety, and environmental consequences. Tube leakage is one of the most frequent causes of OTSG tube failure. A leaking tube was discovered within the OTSG unit of the 110 MW cogeneration plant. The failed section of the tube was removed from the steam generator. Several metallurgical examinations of this tube segment were performed to identify the failure mode and cause. A portion of the tube was analyzed using optical emission spectroscopy (OES) to determine the alloy composition. The results confirmed that the tubing was fabricated from a material consistent with chemical specifications for ASME Specification SB 407 Inconel Alloy 800 (UNS N08800). Glass bead blasting was used to determine the deposit-weight-density (DWD). The DWD value was a maximum of 5.1 g/ft2. The maximum internal deposit thickness was 0.002 in. No evidence of overheating was observed. Scanning electron microscopeenergy-dispersive x-ray analysis (SEM-EDXA) was used to determine the elemental composition of the internal deposits. The results indicated that the internal gray deposits primarily comprised iron, chromium, and nickel compounds. There were also fewer amounts of sodium, silicon, aluminum, potassium, and calcium species. The subject tube failure involved a through-wall crack that occurred as stress corrosion cracking (SCC). Additions of caustic solution used in OTSG water treatment practices potentially induced corrosive substances into the tube. Copyright © 2023 by ASME.
引用
收藏
相关论文
共 50 条
  • [31] Research on Modeling and Simulation of Once-Through Steam Generator
    Xu Y.
    Huangfu Z.
    Xu J.
    Tian P.
    Li C.
    Cheng X.
    Yan S.
    Liao X.
    Xu, Jianqun (qlj1062@163.com), 1600, Atomic Energy Press (42): : 154 - 160
  • [32] Numerical Study of Liquid Metal Helical Coil Once-through Tube Steam Generator
    Yang Y.
    Wang C.
    Zhang D.
    Su G.
    Tian W.
    Qiu S.
    Yuanzineng Kexue Jishu/Atomic Energy Science and Technology, 2021, 55 (07): : 1288 - 1295
  • [33] EXPERIMENTAL INVESTIGATION OF A ONCE-THROUGH COAXIAL STEAM GENERATOR
    KARIG, HE
    JACKLEY, DN
    HIDDE, LG
    JOURNAL OF SPACECRAFT AND ROCKETS, 1965, 2 (03) : 405 - &
  • [34] Primary fluid optimization in once-through steam generator
    Wei, Xinyu
    Dai, Chunhui
    Tai, Yun
    Zhao, Fuyu
    APPLIED THERMAL ENGINEERING, 2011, 31 (17-18) : 3979 - 3988
  • [35] GAS PATH DIAGNOSTICS FOR ONCE-THROUGH STEAM GENERATOR
    Chen, Yu-Zhi
    Li, Yi-Guang
    Newby, Mike A.
    PROCEEDINGS OF THE ASME TURBO EXPO: TURBOMACHINERY TECHNICAL CONFERENCE AND EXPOSITION, 2019, VOL 3, 2019,
  • [36] THERMAL HYDRAULICS ANALYSIS OF A HIGH-PERFORMANCE ONCE-THROUGH STEAM GENERATOR WITH ANNULAR NARROW SLOT TUBE
    Han, Jinyu
    He, Wen
    Guan, Shunran
    Zhao, Chenru
    Bo, Hanliang
    PROCEEDINGS OF 2021 28TH INTERNATIONAL CONFERENCE ON NUCLEAR ENGINEERING (ICONE28), VOL 1, 2021,
  • [37] Numerical study on annular tube once-through steam generator using compressible flow model
    Wang, Z. L.
    Tian, W. X.
    Wu, Y. W.
    Qiu, S. Z.
    Su, G. H.
    ANNALS OF NUCLEAR ENERGY, 2012, 39 (01) : 49 - 55
  • [38] Sizing of a tube inlet orifice of a once-through steam generator to suppress the parallel channel instability
    Yoon, Juhyeon
    NUCLEAR ENGINEERING AND TECHNOLOGY, 2021, 53 (11) : 3643 - 3652
  • [39] Load following dynamic characteristic analysis of casing once-through steam generator
    Liu, Jian-Ge
    Peng, Min-Jun
    Zhang, Zhi-Jian
    Xu, Wen-Qi
    Cheng, Shou-Yu
    Yuanzineng Kexue Jishu/Atomic Energy Science and Technology, 2010, 44 (02): : 175 - 182
  • [40] Analysis of steady-state characteristics of casing once-through steam generator
    Liu, Jian-Ge
    Peng, Min-Jun
    Zhang, Zhi-Jian
    Li, Hua
    Harbin Gongcheng Daxue Xuebao/Journal of Harbin Engineering University, 2009, 30 (07): : 757 - 762