nonlinear transformer; mathematical model; electrical circuit; magnetic circuit; inductance; mutual inductance; winding current harmonic components; SIMULATION;
D O I
10.3390/en17071710
中图分类号
TE [石油、天然气工业]; TK [能源与动力工程];
学科分类号
0807 ; 0820 ;
摘要
In this work, a mathematical model of a three-phase nonlinear transformer is suggested. The model enables simulating the transformer operation with allowance for its nonlinearity and covers needs of the relay protection. Our model has been developed on the basis of a mathematical model with phase coordinates, where differential equations are composed by the Kirchhoff's phase-voltage law. Based on this model, we first compose a mathematical model for simulating steady-state operation modes of a transformer, taking into account the asymmetry and nonlinearity of its ferromagnetic core. In this model, the initial values of inductances and mutual inductances of loops are determined from the main phase inductance calculated by the experimentally found no-load current, and their current values are determined from the currents in windings and the magnetic fluxes in legs of the transformer core. The magnetic fluxes are calculated by the nodal-pair method. This improved mathematical model is verified through a comparison between the calculated harmonic components of the phase currents and the experimental results. The harmonic components are calculated with the use of Fourier expansion of the calculated phase currents. Their experimental values are determined with a spectrum analyzer. The calculated and experimental harmonic components of the currents of phase A during no-load and rated-load operation of the transformer are tabulated. The comparison of these results shows that the mathematical model of a three-phase transformer we suggest makes it possible to simulate currents in transformer windings under steady-state operation modes with accuracy acceptable for relay protection.
引用
收藏
页数:15
相关论文
共 50 条
  • [31] A Dynamic Cascading Failure Model Integrating Relay Protection in Power Grid
    Yang, Yujie
    Zhou, Yadong
    Wu, Jiang
    Xu, Zhanbo
    Guan, Xiaohong
    Chen, Wei
    Liu, Ting
    2020 IEEE 16TH INTERNATIONAL CONFERENCE ON AUTOMATION SCIENCE AND ENGINEERING (CASE), 2020, : 1331 - 1336
  • [32] Development of Algorithm for the Protection Coordination Operation of Ratio Difference Relay for Transformer Protection
    Park Y.-K.
    Eo I.-S.
    Transactions of the Korean Institute of Electrical Engineers, 2022, 71 (08): : 1182 - 1192
  • [33] Establishment of Transformer Turn-to-turn Fault Model Based on Relay Protection Management System
    Yong, To
    Su Shenghao
    Chen Qingfang
    Tang Luqing
    Shuang, Yang
    Chen Dinghui
    Deng, Xiangli
    Li Qingbo
    Meng, Nan
    2015 IEEE ADVANCED INFORMATION TECHNOLOGY, ELECTRONIC AND AUTOMATION CONTROL CONFERENCE (IAEAC), 2015, : 763 - 767
  • [34] MATLAB-SIMULINK-based simulation for digital differential relay protection of power transformer for educational purpose
    Vahidi, B.
    Esmaeeli, E.
    COMPUTER APPLICATIONS IN ENGINEERING EDUCATION, 2013, 21 (03) : 475 - 483
  • [35] Efficiency of Relay Protection of Power System
    Shalin, A. I.
    Trofimov, A. S.
    IFOST: 2007 INTERNATIONAL FORUM ON STRATEGIC TECHNOLOGY, 2007, : 371 - 375
  • [36] Radial basis function neural network model for protection of power transformer
    Moravej, Z
    Vishwakarma, DN
    Singh, SP
    ELECTRIC POWER COMPONENTS AND SYSTEMS, 2001, 29 (04) : 307 - 320
  • [37] Settings determination for numerical transformer differential protection via its detailed mathematical model
    Andreev, Mikhail
    Suvorov, Alexey
    Ruban, Nikolay
    Ufa, Ruslan
    Gusev, Alexander
    Askarov, Alisher
    Kievets, Anton
    Bhalja, Bhavesh R.
    IET GENERATION TRANSMISSION & DISTRIBUTION, 2020, 14 (10) : 1962 - 1972
  • [38] Modeling and implementing of a proposed electronic differential relay for transformer protection
    Ashour, HA
    ICEEC'04: 2004 INTERNATIONAL CONFERENCE ON ELECTRICAL, ELECTRONIC AND COMPUTER ENGINEERING, PROCEEDINGS, 2004, : 795 - 799
  • [39] Adaptive digital differential relay of parabolic characteristic for transformer protection
    Maheshwari, RP
    Verma, HK
    ELECTRIC MACHINES AND POWER SYSTEMS, 1997, 25 (05): : 459 - 473
  • [40] The Impact Analysis of Current Transformer's Saturation to Relay Protection
    Xu, Ningting
    Dong, Jun
    Zheng, Siyuan
    2014 CHINA INTERNATIONAL CONFERENCE ON ELECTRICITY DISTRIBUTION (CICED), 2014,