Settings determination for numerical transformer differential protection via its detailed mathematical model

被引:7
|
作者
Andreev, Mikhail [1 ]
Suvorov, Alexey [1 ]
Ruban, Nikolay [1 ]
Ufa, Ruslan [1 ]
Gusev, Alexander [1 ]
Askarov, Alisher [1 ]
Kievets, Anton [1 ]
Bhalja, Bhavesh R. [2 ]
机构
[1] Natl Res Tomsk Polytech Univ, Sch Energy & Power Engn, Lenina Ave 30, Tomsk, Russia
[2] Indian Inst Technol Roorkee, Dept Elect Engn, Roorkee, Uttarakhand, India
基金
俄罗斯科学基金会;
关键词
relay protection; instrument transformers; power system simulation; power transformer protection; power system transients; hybrid power systems; real-time systems; power system faults; numerical transformer differential protection; electric power systems; fault existence; RP settings calculation; RP settings determination; instrumental transformers; large-scale EPS mathematical model; hybrid power system; real-time power system; analogue-digital solution; hybrid power system simulator; dual-slope tripping characteristic;
D O I
10.1049/iet-gtd.2019.0932
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
Currently, an issue of relay protection (RP) settings determination that ensures its correct operation in electric power systems (EPSs) has not been resolved completely. The main reason for this is the lack of methods and tools for adequate consideration of transients during a fault existence for RP settings calculation. In this study, a novel approach for RP settings determination is presented. Its main feature is the application of detailed mathematical models reproducing simultaneously processes in the entire set of elements in the RP scheme, including instrumental transformers, and in large-scale EPS mathematical model as a whole. This key feature can be achieved via the hybrid power system simulator - hybrid real-time power system simulator - implementing a methodically accurate analogue-digital solution of the EPS mathematical model. The numerical transformer differential protection (NTDP) based on this approach was set up via the standard dual-slope tripping characteristic. Also, a novel approach to the formation of the tripping characteristic is proposed. The key feature of this approach is applying a flexible curve that enveloping all fault characteristics I-diff = f(I-rest) of those modes in which the NTDP should not trip.
引用
收藏
页码:1962 / 1972
页数:11
相关论文
共 50 条
  • [1] Novel Method For Numerical Transformer Differential Protection Setting Up Using Its Detailed Mathematical Model
    Andreev, Mikhail
    Suvorov, Aleksey
    Ruban, Nikolay
    Ufa, Ruslan
    Gusev, Alexander
    Razzhivin, Igor
    Bay, Yuly
    Kievets, Anton
    Askarov, Alisher
    Rudnik, Vladimir
    [J]. PROCEEDINGS OF 2019 IEEE PES INNOVATIVE SMART GRID TECHNOLOGIES EUROPE (ISGT-EUROPE), 2019,
  • [2] A Detailed Testing Procedure of Numerical Differential Protection Relay for EHV Auto Transformer
    Ehsan, Umer
    Jawad, Muhammad
    Javed, Umar
    Shabih Zaidi, Khurram
    Ur Rehman, Ateeq
    Rassolkin, Anton
    Althobaiti, Maha M.
    Hamam, Habib
    Shafiq, Muhammad
    [J]. ENERGIES, 2021, 14 (24)
  • [3] Relay Protection Settings Determination Using Its Mathematical Models
    Andreev, Mikhail
    Suvorov, Aleksey
    Ufa, Ruslan
    Razzhivin, Igor
    [J]. PRZEGLAD ELEKTROTECHNICZNY, 2021, 97 (06): : 140 - 143
  • [4] Detailed mathematical and numerical analysis of a dynamo model
    Sood, Aditi
    Kim, Eun-jin
    [J]. ASTRONOMY & ASTROPHYSICS, 2014, 563
  • [5] Mathematical Model of a Transformer with Differential Electromagnetic Parameters
    Stakhiv, Petro
    Hamola, Orest
    Horyachko, Vsevolod
    Grzywacz, Tomasz
    [J]. PROCEEDINGS OF 19TH INTERNATIONAL CONFERENCE COMPUTATIONAL PROBLEMS OF ELECTRICAL ENGINEERING, 2018,
  • [6] Beyond the Nameplate - Selecting Transformer Compensation Settings for Secure Differential Protection
    Edwards, Barker
    Williams, David G.
    Hargrave, Ariana
    Watkins, Matthew
    Yedidi, Vinod K.
    [J]. 2017 70TH ANNUAL CONFERENCE FOR PROTECTIVE RELAY ENGINEERS (CPRE), 2017,
  • [7] Testing Microprocessor-based Numerical Transformer Differential Protection
    Verzosa , Quintin, Jr.
    Lee , Wah A.
    [J]. 2015 51ST IEEE INDUSTRY APPLICATIONS SOCIETY ANNUAL MEETING, 2015,
  • [8] Testing Microprocessor-Based Numerical Transformer Differential Protection
    Verzosa, Quintin, Jr.
    Lee, Wah A.
    [J]. IEEE TRANSACTIONS ON INDUSTRY APPLICATIONS, 2017, 53 (01) : 56 - 64
  • [9] Mathematical Model of a Nonlinear Power Transformer for Needs of Relay Protection
    Kolesnikov, Evgeniy
    Novozhilov, Aleksandr
    Rakhimberdinova, Dilara
    Kislov, Aleksandr
    Novozhilov, Timofey
    [J]. ENERGIES, 2024, 17 (07)
  • [10] MATHEMATICAL SIMULATION OF THE TRANSFORMER DIFFERENTIAL PROTECTION, BASED ON THE TIME-IMPULSE PRINCIPLE
    Andreev, Mikhail V.
    Borovikov, Yuri S.
    Ruban, Nikolay Yu.
    Khlebov, Aleksey V.
    [J]. FOURTH INTERNATIONAL YOUTH FORUM SMART GRIDS 2016, 2017, 91