Partial Discharge Detection of High Voltage Switchgear Using a Ultra High Frequency Sensor

被引:5
|
作者
Shin, Jong-Yeol [1 ]
Lee, Young-Sang [2 ]
Hong, Jin-Woong [2 ]
机构
[1] Sahmyook Univ, Dept Car Mechatron, Seoul 139742, South Korea
[2] Kwangwoon Univ, Dept Elect Engn, Seoul 139701, South Korea
关键词
Ultra high frequency; High voltage switchgear; Gas insulated switchgear; Partial discharge; Insulation; Diagnosis techniques;
D O I
10.4313/TEEM.2013.14.4.211
中图分类号
T [工业技术];
学科分类号
08 ;
摘要
Partial discharge diagnosis techniques using ultra high frequencies do not affect load movement, because there is no interruption of power. Consequently, these techniques are popular among the prevention diagnosis methods. For the first time, this measurement technique has been applied to the GIS, and has been tested by applying an extra high voltage switchboard. This particular technique makes it easy to measure in the live state, and is not affected by the noise generated by analyzing the causes of faults ? thereby making risk analysis possible. It is reported that the analysis data and the evaluation of the risk level are improved, especially for poor location, and that the measurement of Ultra high frequency (UHF) partial discharge of the real live wire in industrial switchgear is spectacular. Partial discharge diagnosis techniques by using the Ultra High Frequency sensor have been recently highlighted, and it is verified by applying them to the GIS. This has become one of the new and various power equipment techniques. Diagnosis using a UHF sensor is easy to measure, and waveform analysis is already standardized, due to numerous past case experiments. This technique is currently active in research and development, and commercialization is becoming a reality. Another aspect of this technique is that it can determine the occurrences and types of partial discharge, by the application diagnosis for live wire of ultra high voltage switchgear. Measured data by using the UHF partial discharge techniques for ultra high voltage switchgear was obtained from 200 places in Gumi, Yeosu, Taiwan and China's semiconductor plants, and also the partial discharge signals at 15 other places were found. It was confirmed that the partial discharge signal was destroyed by improving the work of junction bolt tightening check, and the cable head reinforcement insulation at 8 places with a possibility for preventing the interruption of service. Also, it was confirmed that the UHF partial discharge measurement techniques are also a prevention diagnosis method in actual industrial sites. The measured field data and the usage of the research for risk assessment techniques of the live wire status of power equipment make a valuable database for future improvements.
引用
收藏
页码:211 / 215
页数:5
相关论文
共 50 条
  • [1] Experimental Investigation of Partial Discharge Detection in Medium-voltage Switchgear Based on Ultra-High-Frequency Sensor
    Wang, Liuhuo
    Ning, Wenjun
    Wang, Lijun
    Lu, Hong
    Wang, Haijing
    Jia, Shenli
    Wu, Ji
    [J]. 2013 2ND INTERNATIONAL CONFERENCE ON ELECTRIC POWER EQUIPMENT - SWITCHING TECHNOLOGY (ICEPE-ST), 2013,
  • [2] Experience with Partial Discharge Detection at High Voltage Gas Insulated Switchgear by Ultra High Frequency (UHF) Method
    Chan, L. K.
    So, K. L.
    Chow, K. K.
    [J]. 2013 IEEE PES ASIA-PACIFIC POWER AND ENERGY ENGINEERING CONFERENCE (APPEEC), 2013,
  • [3] The Application of High Frequency and Ultra High Frequency Partial Discharge Detection to Gas Insulated Switchgear
    Lu, Yao
    Qiu, Zhibin
    Liao, Caibo
    Li, Tonghongfei
    Wu, Zijian
    Hu, Yong
    [J]. 2022 4TH ASIA ENERGY AND ELECTRICAL ENGINEERING SYMPOSIUM (AEEES 2022), 2022, : 712 - 716
  • [4] Detection and Analysis of Partial Discharge using Ultra High Frequency Sensor
    Reddy, P. Gurumurthy
    Kundu, Prasanta
    [J]. 2014 ANNUAL INTERNATIONAL CONFERENCE ON EMERGING RESEARCH AREAS: MAGNETICS, MACHINES AND DRIVES (AICERA/ICMMD), 2014,
  • [5] New ultra high frequency sensor for detection of partial discharge for GIS
    Hu, Di-Jun
    Chen, Jie-Hua
    Li, Zhong
    Feng, Yun-Ping
    [J]. Gaoya Dianqi/High Voltage Apparatus, 2003, 39 (04):
  • [6] Application of Online Partial Discharge Detection of Switchgear Based on Ultra-High Frequency Method
    Wang, Yongning
    Zhang, Chi
    Liu, Guangzhen
    Ma, Xiaoguang
    He, Jin
    Xu, Xuan
    Han, Qiubo
    Shan, Bingliang
    Huang, Meng
    Li, Chengrong
    [J]. 2018 12TH INTERNATIONAL CONFERENCE ON THE PROPERTIES AND APPLICATIONS OF DIELECTRIC MATERIALS (ICPADM 2018), 2018, : 542 - 545
  • [7] Online Monitoring of Partial Discharge In High Voltage Switchgear Using a Differential Electric Field Sensor
    Zeng, Xiaoming
    Li, Hongjie
    Lu, Yuxin
    Chen, Yufei
    [J]. 2017 IEEE CONFERENCE ON ELECTRICAL INSULATION AND DIELECTRIC PHENOMENON (CEIDP), 2017, : 385 - 388
  • [8] Development of smart sensor for ultra-high-frequency partial discharge detection
    State Key Laboratory of Power Transmission Equipment & System Security and New Technology, Chongqing University, Chongqing
    400030, China
    不详
    650217, China
    不详
    330096, China
    [J]. Gaodianya Jishu, 12 (3944-3951):
  • [9] Research on the UHF Microstrip Antenna for Partial Discharge Detection in High Voltage Switchgear
    Luo, Hanwu
    Cheng, Peng
    Liu, Haibo
    Kang, Kai
    Yang, Fan
    Liu, Kai
    [J]. PROCEEDINGS OF THE 2016 IEEE 11TH CONFERENCE ON INDUSTRIAL ELECTRONICS AND APPLICATIONS (ICIEA), 2016, : 2273 - 2276
  • [10] Ultra-high frequency detection and analysis for partial discharge in high-voltage cable accessories
    Tang, Ju
    Li, Wei
    Yang, Hao
    Zhang, Xiao-Xing
    Wei, Gang
    [J]. Gaodianya Jishu/High Voltage Engineering, 2009, 35 (07): : 1571 - 1577