Partial discharge diagnosis techniques using ultra high frequencies do not affect load movement, because there is no interruption of power. Consequently, these techniques are popular among the prevention diagnosis methods. For the first time, this measurement technique has been applied to the GIS, and has been tested by applying an extra high voltage switchboard. This particular technique makes it easy to measure in the live state, and is not affected by the noise generated by analyzing the causes of faults ? thereby making risk analysis possible. It is reported that the analysis data and the evaluation of the risk level are improved, especially for poor location, and that the measurement of Ultra high frequency (UHF) partial discharge of the real live wire in industrial switchgear is spectacular. Partial discharge diagnosis techniques by using the Ultra High Frequency sensor have been recently highlighted, and it is verified by applying them to the GIS. This has become one of the new and various power equipment techniques. Diagnosis using a UHF sensor is easy to measure, and waveform analysis is already standardized, due to numerous past case experiments. This technique is currently active in research and development, and commercialization is becoming a reality. Another aspect of this technique is that it can determine the occurrences and types of partial discharge, by the application diagnosis for live wire of ultra high voltage switchgear. Measured data by using the UHF partial discharge techniques for ultra high voltage switchgear was obtained from 200 places in Gumi, Yeosu, Taiwan and China's semiconductor plants, and also the partial discharge signals at 15 other places were found. It was confirmed that the partial discharge signal was destroyed by improving the work of junction bolt tightening check, and the cable head reinforcement insulation at 8 places with a possibility for preventing the interruption of service. Also, it was confirmed that the UHF partial discharge measurement techniques are also a prevention diagnosis method in actual industrial sites. The measured field data and the usage of the research for risk assessment techniques of the live wire status of power equipment make a valuable database for future improvements.
引用
收藏
页码:211 / 215
页数:5
相关论文
共 50 条
  • [31] Application of ultra-high-frequency partial discharge detection in power transformers
    Zhao, Xiao-Hui
    Lu, Xiu-Li
    Yang, Jing-Gang
    Yuan, Peng
    Li, Yan-Ming
    Gaodianya Jishu/High Voltage Engineering, 2007, 33 (08): : 111 - 114
  • [32] Ultra-high-frequency Partial Discharge Detection with Scanning and Comparing Method
    Yan, Jinping
    Du, Lin
    Li, Jian
    Wang, Youyuan
    2014 INTERNATIONAL CONFERENCE ON HIGH VOLTAGE ENGINEERING AND APPLICATION (ICHVE), 2014,
  • [33] Development of Transient Earth Voltage Sensor for Partial Discharge Detection in Gas-insulated Switchgear
    Kuo, Cheng-Chien
    Liu, Yu-Ming
    Chen, Hung-Cheng
    SENSORS AND MATERIALS, 2023, 35 (10) : 4697 - 4706
  • [34] Partial Discharge Detection Approach for a Medium Voltage Switchgear System
    Cai, ZhuoLun
    Wilkinson, Richardt H.
    Bojovschi, Alexe
    PROGRESS IN ELECTROMAGNETICS RESEARCH-PIER, 2014, 144 : 221 - 228
  • [35] Experimental Research on the Sensitivity of Partial Discharge Ultra High Frequency Sensor Structure Parameters
    Li, Wen-Yi
    JOURNAL OF NANOELECTRONICS AND OPTOELECTRONICS, 2021, 16 (07) : 911 - 918
  • [36] Design of External Ultra-high Frequency Partial Discharge Sensor for Large Transformer
    Zhang X.
    Zhang J.
    Xiao S.
    Gaodianya Jishu/High Voltage Engineering, 2019, 45 (02): : 499 - 504
  • [37] A novel type of ultra-high frequency sensor for partial discharge source location
    Ye, H.F.
    Qian, Y.
    Sheng, G.H.
    Li, X.W.
    Jiang, X.C.
    Australian Journal of Electrical and Electronics Engineering, 2014, 11 (02): : 144 - 152
  • [38] Partial discharge detection for GIS using narrow band ultra-high-frequency (UHF) method
    Sun, YZ
    Yin, H
    Zhang, QG
    Yu, FS
    Wang, H
    Qiu, YC
    Proceedings of the 2005 International Symposium on Electrical Insulating Materials, Vols, 1-3, 2005, : 748 - 751
  • [39] Partial Discharge Monitoring of High Voltage Equipment Using Chipless RFID Sensor
    Amin, Emran Md
    Karmakar, Nemai
    ASIA-PACIFIC MICROWAVE CONFERENCE 2011, 2011, : 1522 - 1525
  • [40] Electromagnetic Interference of Partial Discharge in Ultra High Voltage Substation
    Wei, Xu
    Yang, Xiaoping
    Xie, Tianxi
    Li, Jiansheng
    Wang, Tonglei
    Wang, Shengquan
    2019 5TH INTERNATIONAL CONFERENCE ON ENVIRONMENTAL SCIENCE AND MATERIAL APPLICATION, 2020, 440