DETECTION AND LOCATION OF INTERNAL DEFECTS IN THE INSULATION OF POWER TRANSFORMERS

被引:53
|
作者
FUHR, J
HAESSIG, M
BOSS, P
TSCHUDI, D
KING, RA
机构
[1] ABB SECHERON LTD,GENEVA,SWITZERLAND
[2] ROYAL MIL COLL SCI,SWINDON SN6 8LA,WILTS,ENGLAND
来源
关键词
D O I
10.1109/14.249379
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
Reliable methods and suitable equipment for sensitive detection and for precise location of internal defects in the insulating systems of power transformers during commissioning tests are still very much a subject of discussion among testing engineers and researchers. Currently, the widely applied electrical and acoustical partial discharge (PD) measurement techniques fulfill only partly the requirements to assess the risk and the location of detected internal defects during commissioning tests. With the development of both fast and low cost analog-digital converters (ADC) and new mathematical procedures for waveform description, e.g. time encoded signal processing and recognition (TESPAR), novel approaches to detect and locate internal defects in the insulation of power transformers become feasible if the following requirements are fulfilled: the equivalent circuit of the insulating system suitable for fast PD signals with rise times similar to 10 ns is known, the response of the insulating system to PD signals injected at least at three different sites of each winding (top, center, bottom) are calculated or measured at the signal tap-off points (i.e. bushings), and the pattern matrix of all calculated or measured signals exists e.g. encoded and signal processed with TESPAR as a reference. In this contribution, the above mentioned requirements for quasi-simultaneous detection and location of internal defects in power transformers will be examined and this method applied to PD measurements on power transformers.
引用
收藏
页码:1057 / 1067
页数:11
相关论文
共 50 条
  • [31] THE KINETICS AND MECHANISMS OF DEGRADATION OF CELLULOSIC INSULATION IN POWER TRANSFORMERS
    EMSLEY, AM
    POLYMER DEGRADATION AND STABILITY, 1994, 44 (03) : 343 - 349
  • [32] Calculation of the Remaining Lifetime of Power Transformers Paper Insulation
    Gorgan, Bogdan
    Notingher, Petru V.
    Wetzer, Jos M.
    Verhaart, Harry F. A.
    Wouters, Peter A. A. F.
    van Schijndel, Arjan
    Tanasescu, Gabriel
    PROCEEDINGS OF THE 13TH INTERNATIONAL CONFERENCE ON OPTIMIZATION OF ELECTRICAL AND ELECTRONIC EQUIPMENT, VOLS 1-5, 2012, : 293 - 300
  • [33] Insulation Resistance of Power Transformers - Method for Optimized Analysis
    Marques, Andre P.
    Azevedo, Claudio H. B.
    dos Santos, Jose A. L.
    Sousa, Felipe R. de C.
    Moura, Nicolas K.
    Ribeiro, Cacilda J.
    Dias, Yuri A.
    Rodrigues, Adonay
    Rocha, Adson S.
    Brito, Leonardo da C.
    2017 IEEE 19TH INTERNATIONAL CONFERENCE ON DIELECTRIC LIQUIDS (ICDL), 2017,
  • [34] Correlation of Dielectric Parameters and Insulation Properties of Power Transformers
    Anglhuber, Martin
    PROCEEDINGS OF THE 21ST INTERNATIONAL SYMPOSIUM ON HIGH VOLTAGE ENGINEERING, VOL 2, 2020, 599 : 640 - 649
  • [35] Dielectric Analysis Applied to Power Transformers Insulation Design
    Bueno, D. M.
    Medeiros, L. H.
    Bender, V. C.
    Marchesan, T. B.
    Marin, M. A.
    Wilhelm, H. M.
    2021 96TH IEEE CONFERENCE ON ELECTRICAL INSULATION AND DIELECTRIC PHENOMENA (CEIDP 2021) / 16TH IEEE NANOTECHNOLOGY MATERIALS AND DEVICES CONFERENCE (IEEE NMDC 2021), 2021, : 498 - 501
  • [36] Influence of cellulose degradation on insulation life in power transformers
    Emsley, A.M.
    Use of Minerals in Papermaking, 1998, : 115 - 124
  • [37] Research on insulation condition monitoring system for power transformers
    Ren, Shuangzan
    Yang, Xu
    Yang, Wenhu
    Xi, Baofeng
    Cao, Xiaolong
    PROCEEDINGS OF 2008 INTERNATIONAL CONFERENCE ON CONDITION MONITORING AND DIAGNOSIS, 2007, : 1005 - 1007
  • [38] Suspended particles in the liquid insulation of aging power transformers
    Ferguson, R
    Lobeiras, A
    Sabau, J
    IEEE ELECTRICAL INSULATION MAGAZINE, 2002, 18 (04) : 17 - 23
  • [39] Sensitivity analysis for winding support and insulation of power transformers
    Schmidt, Erich
    Hamberger, Peter
    2007 CANADIAN CONFERENCE ON ELECTRICAL AND COMPUTER ENGINEERING, VOLS 1-3, 2007, : 145 - 148
  • [40] Analyzing Method Efficiency for Power Transformers Insulation Design
    Capuder, Kosjenka
    Janic, Zarko
    Stih, Zeljko
    2013 IEEE EUROCON, 2013, : 1536 - 1541