DETECTION AND LOCATION OF INTERNAL DEFECTS IN THE INSULATION OF POWER TRANSFORMERS

被引:53
|
作者
FUHR, J
HAESSIG, M
BOSS, P
TSCHUDI, D
KING, RA
机构
[1] ABB SECHERON LTD,GENEVA,SWITZERLAND
[2] ROYAL MIL COLL SCI,SWINDON SN6 8LA,WILTS,ENGLAND
来源
关键词
D O I
10.1109/14.249379
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
Reliable methods and suitable equipment for sensitive detection and for precise location of internal defects in the insulating systems of power transformers during commissioning tests are still very much a subject of discussion among testing engineers and researchers. Currently, the widely applied electrical and acoustical partial discharge (PD) measurement techniques fulfill only partly the requirements to assess the risk and the location of detected internal defects during commissioning tests. With the development of both fast and low cost analog-digital converters (ADC) and new mathematical procedures for waveform description, e.g. time encoded signal processing and recognition (TESPAR), novel approaches to detect and locate internal defects in the insulation of power transformers become feasible if the following requirements are fulfilled: the equivalent circuit of the insulating system suitable for fast PD signals with rise times similar to 10 ns is known, the response of the insulating system to PD signals injected at least at three different sites of each winding (top, center, bottom) are calculated or measured at the signal tap-off points (i.e. bushings), and the pattern matrix of all calculated or measured signals exists e.g. encoded and signal processed with TESPAR as a reference. In this contribution, the above mentioned requirements for quasi-simultaneous detection and location of internal defects in power transformers will be examined and this method applied to PD measurements on power transformers.
引用
收藏
页码:1057 / 1067
页数:11
相关论文
共 50 条
  • [21] Study on the Ultrasonic Detection Method for Internal Defects of Insulation Pull Rod in Circuit Breakers
    Song, Wenjin
    Meng, Yongpeng
    Men, Chuang
    Zhu, Bowen
    Cheng, Yonghong
    2016 INTERNATIONAL CONFERENCE ON CONDITION MONITORING AND DIAGNOSIS (CMD), 2016, : 384 - 387
  • [22] A novel technique for internal fault detection of power transformers based on moving windows
    Abniki, Hassan
    Sanaye-Pasand, Majid
    INTERNATIONAL TRANSACTIONS ON ELECTRICAL ENERGY SYSTEMS, 2014, 24 (09): : 1263 - 1278
  • [23] Detection of Inrush and Internal Fault in Power Transformers Based on Bacterial Foraging Optimization
    Gopila, M.
    Gnanambal, I.
    JOURNAL OF SCIENTIFIC & INDUSTRIAL RESEARCH, 2017, 76 (01): : 32 - 37
  • [24] Analysis of Insulation Characteristics of Coconut Oil as an Alternative to the Liquid Insulation of Power Transformers
    Ranawana, S.
    Ekanayaka, C. M. B.
    Kurera, N. A. S. A.
    Fernando, M. A. R. M.
    Perera, K. A. R.
    IEEE REGION 10 COLLOQUIUM AND THIRD INTERNATIONAL CONFERENCE ON INDUSTRIAL AND INFORMATION SYSTEMS, VOLS 1 AND 2, 2008, : 884 - 888
  • [25] Thermal Degradation of Cellulose Paper Insulation in Power Transformers
    Mirzaie, M.
    Gholami, A.
    Tayyebi, H.
    2007 IEEE INTERNATIONAL CONFERENCE ON SOLID DIELECTRICS, VOLS 1 AND 2, 2007, : 673 - +
  • [26] Measurement and localisation of partial discharges in the insulation of power transformers
    Bednarczyk, Tomasz
    Koltunowicz, Wojciech
    Krueger, Michael
    Ranninger, Udo
    PRZEGLAD ELEKTROTECHNICZNY, 2022, 98 (10): : 107 - 110
  • [27] Creepage Discharge on Insulation Barriers in Aged Power Transformers
    Dai, J.
    Wang, Z. D.
    Jarman, P.
    IEEE TRANSACTIONS ON DIELECTRICS AND ELECTRICAL INSULATION, 2010, 17 (04) : 1327 - 1335
  • [28] BASIC INSULATION CHARACTERISTICS OF PERFLUOROCARBON FOR LARGE POWER TRANSFORMERS
    TAKAGI, I
    HIGAKI, M
    ENDOO, K
    SHIRONE, T
    HIRAISHI, K
    KAWASHIMA, K
    IEEE TRANSACTIONS ON POWER DELIVERY, 1988, 3 (04) : 1809 - 1815
  • [29] Improving the insulation condition of power transformers with an innovative paper insulation demoisturing procedure
    Wasserberg, V
    Borsi, H
    Gockenbach, E
    PROCEEDINGS OF THE 6TH INTERNATIONAL CONFERENCE ON PROPERTIES AND APPLICATIONS OF DIELECTRIC MATERIALS, VOLS 1 & 2, 2000, : 85 - 88
  • [30] A survey of new techniques in insulation monitoring of power transformers
    Ward, BH
    IEEE ELECTRICAL INSULATION MAGAZINE, 2001, 17 (03) : 16 - 23