AN ANALYTICAL EXAMINATION OF METHODS FOR IMPROVING THE PERFORMANCE OF DESICCANT COOLING SYSTEMS

被引:25
|
作者
COLLIER, RK
COHEN, BM
机构
[1] FLORIDA SOLAR ENERGY CTR,CAPE CANAVERAL,FL 32920
[2] TECOGEN INC,WALTHAM,MA 02254
关键词
D O I
10.1115/1.2930487
中图分类号
TE [石油、天然气工业]; TK [能源与动力工程];
学科分类号
0807 ; 0820 ;
摘要
The conventional Pennington Cycle desiccant cooling system offers a clear opportunity for heat-actuated air conditioning. However, efforts to translate this opportunity into commercially viable hardware have not been successful. The performance of the hardware has been inadequate, resulting in excessive solar collector requirements or, in the case of gas-fired equipment, uneconomical use of natural gas. Two methods for improving the coefficient of performance (COP) of these systems are: (1) the addition of inert heat capacity to the desiccant matrix, and (2) "staging" the regeneration air stream. An analysis is presented in this paper which explains the benefits and drawbacks of these methods based upon the wave nature of the heat and mass transfer processes occurring within the desiccant bed. The results indicate that the best overall system performance is obtained by staging the regeneration process while minimizing the amount of inert heat capacity.
引用
收藏
页码:157 / 163
页数:7
相关论文
共 50 条
  • [41] Cycle performance of heat pump in desiccant cooling system
    School of Environmental Science and Engineering, Tianjin University, Tianjin 300072, China
    不详
    不详
    Huagong Xuebao, 2009, 9 (2177-2182): : 2177 - 2182
  • [42] Performance study of new adsorbent for solid desiccant cooling
    Cui, Q
    Chen, HJ
    Tao, G
    Yao, HQ
    ENERGY, 2005, 30 (2-4) : 273 - 279
  • [43] PERFORMANCE ASSESSMENT OF A SOLAR ASSISTED DESICCANT COOLING SYSTEM
    Gagliano, Antonio
    Patania, Francesco
    Nocera, Francesco
    Galesi, Aldo
    THERMAL SCIENCE, 2014, 18 (02): : 563 - 576
  • [44] Evaporative Cooling Integrated with Solid Desiccant Systems: A Review
    Lai, Lanbo
    Wang, Xiaolin
    Kefayati, Gholamreza
    Hu, Eric
    ENERGIES, 2021, 14 (18)
  • [45] A methodology for the performance evaluation of an experimental desiccant cooling system
    Çarpinlioglu, MO
    Yildirim, M
    INTERNATIONAL COMMUNICATIONS IN HEAT AND MASS TRANSFER, 2005, 32 (10) : 1400 - 1410
  • [46] Performance of a Hybrid Desiccant Cooling System in a Residential Environment
    Ahn, Joon
    Kim, Jaeyul
    Kang, Byung Ha
    HEAT TRANSFER ENGINEERING, 2016, 37 (7-8) : 633 - 639
  • [47] PERFORMANCE OF AN OPEN-CYCLE DESICCANT COOLING SYSTEM USING ADVANCED DESICCANT MATRICES
    MAJUMDAR, P
    WOREK, WM
    HEAT RECOVERY SYSTEMS & CHP, 1989, 9 (04): : 299 - 311
  • [48] Performance evaluation of a desiccant-evaporative cooling system
    Sheer, TJ
    Thom, MG
    NATURAL WORKING FLUIDS'98: IIR - GUSTAV LORENTZEN CONFERENCE, 1998, 1998 (04): : 114 - 124
  • [49] Energy storage for desiccant cooling systems component development
    Kessling, W
    Laevemann, E
    Kapfhammer, C
    SOLAR ENERGY, 1998, 64 (4-6) : 209 - 221
  • [50] Experimental performance analysis and modelling of liquid desiccant cooling systems for air conditioning in residential buildings
    Pietruschka, D
    Eicker, U
    Huber, M
    Schumacher, J
    INTERNATIONAL JOURNAL OF REFRIGERATION-REVUE INTERNATIONALE DU FROID, 2006, 29 (01): : 110 - 124