Core balance ground fault protection of motors on a low-resistance grounded, medium-voltage system

被引:4
|
作者
Breitkreutz, B [1 ]
Frere, A [1 ]
机构
[1] GE CO,HOUSTON,TX 77036
关键词
D O I
10.1109/28.475732
中图分类号
T [工业技术];
学科分类号
08 ;
摘要
The core balance current transformer is the basis for sensitive ground fault protection of motors. All phase conductors pass through the same opening in the current transformer so that it senses only zero sequence or ground current. Possible sources of nonfault relay current include current transformer error, harmonics, and unbalanced currents through impedances to ground, especially capacitances. The core balance connected ground fault relay is usually an instantaneous type, or a time-delay type of the short time or very inverse characteristic. The standards provide typical ranges of relay settings. They do not provide a procedure for determining the minimum settings that will not result in nuisance trips from nonfault currents nor the maximum settings that will provide adequate protection. This paper develops that procedure.
引用
收藏
页码:1398 / 1401
页数:4
相关论文
共 50 条
  • [21] MV generator low-resistance grounding and stator ground fault damage
    Wu, A
    Tang, YS
    Finney, D
    IEEE TRANSACTIONS ON INDUSTRY APPLICATIONS, 2004, 40 (02) : 672 - 679
  • [22] Performance testing low voltage ground fault protection
    Coyle, T
    2001 IEEE INDUSTRIAL AND COMMERCIAL POWER SYSTEMS TECHNICAL CONFERENCE, CONFERENCE RECORD, 2001, : 147 - 156
  • [23] ARC-FLASH PROTECTION FOR LOW- AND MEDIUM-VOLTAGE PANELS
    Rocha, Geraldo
    Zanirato, Eduardo
    Ayello, Fernando
    Taninaga, Roberto
    2011 RECORD OF CONFERENCE PAPERS INDUSTRY APPLICATIONS SOCIETY 58TH ANNUAL IEEE PETROLEUM AND CHEMICAL INDUSTRY CONFERENCE (PCIC), 2011,
  • [24] CHANGES IN OVERCURRENT PROTECTION PARADIGMS OF LOW AND MEDIUM-VOLTAGE SMART GRIDS
    Gomez, J. C.
    Morcos, M. M.
    2013 NORTH AMERICAN POWER SYMPOSIUM (NAPS), 2013,
  • [25] Detection of Single-Phase to Ground Faults in Low-Resistance Grounded MV Systems
    Chen, Jiaquan
    Li, Haifeng
    Deng, Chengjiang
    Wang, Gang
    IEEE TRANSACTIONS ON POWER DELIVERY, 2021, 36 (03) : 1499 - 1508
  • [26] Ground fault location in low-voltage high-resistance grounded systems via the single-processor concept for circuit protection
    Valdes, Marcelo
    Papallo, Tom
    Premerlani, Bill
    CONFERENCE RECORD OF 2006 ANNUAL PULP AND PAPER INDUSTRY TECHNICAL CONFERENCE, 2006, : 61 - +
  • [27] Locating a ground fault in low-voltage high-resistance grounded systems via the single-processor concept for circuit protection
    Valdes, M
    Papallo, T
    Premerlani, B
    Industry Applications Society 52nd Annual Petroleum and Chemical Industry Conference, 2005, : 63 - 69
  • [28] Phase-Ground Fault Current Analysis and Protection of a High-Resistance Grounded Power System
    Paul, Dev
    IEEE TRANSACTIONS ON INDUSTRY APPLICATIONS, 2020, 56 (04) : 3306 - 3314
  • [29] Phase-Ground Fault Current Analysis and Protection of a High-Resistance Grounded Power System
    Pe, Dev Paul
    2019 IEEE INDUSTRY APPLICATIONS SOCIETY ANNUAL MEETING, 2019,
  • [30] Grounding and ground fault protection of multiple generator installations on medium-voltage industrial and commercial systems - Part 2: Grounding methods
    Pillai, P
    Pierce, A
    Bailey, B
    Douglas, B
    Mozina, C
    Normand, C
    Love, D
    Shipp, D
    Dalke, G
    Jones, JR
    Fischer, J
    Bowen, J
    Padden, L
    Powell, L
    Nichols, N
    Young, R
    Stringer, NT
    CONFERENCE RECORD OF THE 2002 IEEE INDUSTRY APPLICATIONS CONFERENCE, VOLS 1-4, 2002, : 1888 - 1895