A ventilated cooling ceiling with integrated latent heat storage: test room measurements

被引:3
|
作者
Weinlaeder, H. [1 ]
Kranl, D. [1 ]
Strieder, B. [2 ]
机构
[1] Bavarian Ctr Appl Energy Res ZAE Bayern, D-97074 Wurzburg, Germany
[2] Dorrken GmbH & Co KG, Wetterstr 58, D-58313 Herdecke, Germany
关键词
cooling ceiling; energy-efficient buildings; latent heat storage; phase change material; thermal comfort; ventilated;
D O I
10.1080/17508975.2013.775098
中图分类号
TU [建筑科学];
学科分类号
0813 ;
摘要
Aventilated cooling ceiling with phase change material (PCM) was installed and measured in a 20 m2 test room. The PCM used was DELTAw-COOL 24, a salt hydrate from the company Do "rken with a melting range of 22-288C. The PCM was encapsulated in polycarbonate containers which were laid on top of the bearing for the plaster boards. The amount of PCM installed was 9 kg/m(2). The ceiling was rear ventilated to improve heat transfer between the PCM and the room air. During the cooling mode, the ventilation was purely in circulating operation with a volume flow rate of 97 m3/h (air exchange rate of 2/h). To regenerate the PCM, cooled air was inserted into the ceiling with a volume flow rate of 140 m(3)/h (air exchange rate of 3/h). Different positions for the containers were tested. The PCM in the ceiling delayed the rise in the room air temperature significantly. The PCM stayed active for 12-16 h, depending on the position of the containers. While the cooling power of the air flow alone was very small (30-40 W for the 20 m(2) test room), a significant amount of heat was transferred directly through the plaster boards of the ceiling.
引用
收藏
页码:120 / 132
页数:13
相关论文
共 50 条
  • [21] Critical review of latent heat storage systems for free cooling in buildings
    Zeinelabdein, Rami
    Omer, Siddig
    Gan, Guohui
    RENEWABLE & SUSTAINABLE ENERGY REVIEWS, 2018, 82 : 2843 - 2868
  • [22] A SOLAR AIR COLLECTOR WITH INTEGRATED LATENT HEAT THERMAL STORAGE
    Charvat, Pavel
    Ostry, Milan
    Mauder, Tomas
    Klimes, Lubomir
    EFM11 - EXPERIMENTAL FLUID MECHANICS 2011, 2012, 25
  • [23] Passive Cooling of Protruding Electronic Components by Latent Heat of Fusion Storage
    Faraji, Mustapha
    El Qarnia, Hamid
    JOURNAL OF ELECTRONIC PACKAGING, 2009, 131 (02) : 0210111 - 02101110
  • [24] Transient heat transfer characteristics of cooling fluid loop with latent heat storage unit
    Zhang, Xuan
    Li, Bo
    Yu, Cheng
    INTERNATIONAL COMMUNICATIONS IN HEAT AND MASS TRANSFER, 2024, 159
  • [25] PERFORMANCE OF SOLAR SORPTION COOLING SYSTEMS WITH HEAT REJECTION ASSISTED BY A LATENT HEAT STORAGE
    Hagel, K.
    Helm, M.
    Schweigler, C.
    23RD IIR INTERNATIONAL CONGRESS OF REFRIGERATION, 2011, 23 : 2856 - 2863
  • [26] Thermal performance of a latent heat energy storage ventilated panel for electric load management
    Laouadi, A
    Lacroix, M
    INTERNATIONAL JOURNAL OF HEAT AND MASS TRANSFER, 1999, 42 (02) : 275 - 286
  • [27] Test and analysis of a flat plate latent heat storage design
    Johnson, M.
    Fiss, M.
    Klemm, T.
    Eck, M.
    2013 ISES SOLAR WORLD CONGRESS, 2014, 57 : 662 - 671
  • [28] Thermal cycle test of urea for latent heat storage applications
    Sharma, A
    Sharma, SD
    Buddhi, D
    Sawhney, RL
    INTERNATIONAL JOURNAL OF ENERGY RESEARCH, 2001, 25 (05) : 465 - 468
  • [29] Application of a phase change material to a thermoelectric ceiling radiant cooling panel as a heat storage layer
    Lim, Hansol
    Kang, Yong-Kwon
    Jeong, Jae-Weon
    JOURNAL OF BUILDING ENGINEERING, 2020, 32
  • [30] Evaluation of thermal comfort using combined CFD and experimentation study in a test room equipped with a cooling ceiling
    Catalina, Tiberiu
    Virgone, Joseph
    Kuznik, Frederic
    BUILDING AND ENVIRONMENT, 2009, 44 (08) : 1740 - 1750