Experimental Investigation of the Effect of Fire Protection Lobby on Stair Pressurization System in a High-Rise Building

被引:0
|
作者
Busra Hepguzel Acikyol
Gokhan Balik
Abdurrahman Kilic
机构
[1] Istanbul Technical University,Faculty of Mechanical Engineering
[2] Etik Muhendislik Danismanlik Tasarim ve Egitim Hizmetleri Ltd. Sti.,undefined
来源
Fire Technology | 2017年 / 53卷
关键词
Stair pressurization; High-rise building; Fire protection lobby; Non-pressurized vestibule;
D O I
暂无
中图分类号
学科分类号
摘要
In this study, the stair pressurization system in a 40-storey high office building in Istanbul is investigated through field tests, in order to understand the effect of the presence of a non-pressurized vestibule (fire protection lobby, FPL) before entering the stair at each floor. The building without FPL is simulated by keeping only one of the two doors (of the stair and FPL) open at each floor. This method gave an opportunity to fix other parameters affecting the stair pressurization system and check solely the effect of FPL. Two different cases are taken into account, where the first one (all doors closed) analyses the condition that all stair doors are kept closed and the second one (critical doors are open) is conducted when the stairwell is opened to the floor on a given level (fire floor) and the stair termination door at the discharge floor is kept open. For both cases, the availability of the FPL is investigated by using the aforementioned arrangement. Under the conditions with approximately the same pressurized air flow rate at all doors closed condition, it is found that the availability of FPL increases the pressure difference between the stairwell and the corridor by a factor of approximately 2.2. This is also justified by using empirical formulations available in literature, where this ratio is calculated as 2.0. The results of this study showed that the FPL arrangement improves the effectiveness of pressurization system in a very high-rise building, despite some tolerable drawbacks.
引用
收藏
页码:135 / 151
页数:16
相关论文
共 50 条
  • [21] Jakarta Fire Safety System Management Practices for High-Rise Building
    Wardani, Tri Kusuma
    Nurcahyo, Rahmat
    Dachyar, M.
    2018 5TH IEEE INTERNATIONAL CONFERENCE ON ENGINEERING TECHNOLOGIES AND APPLIED SCIENCES (IEEE ICETAS), 2018,
  • [22] FIELD CHECKS ON BUILDING PRESSURIZATION FOR SMOKE CONTROL IN HIGH-RISE BUILDINGS
    TAMURA, GT
    SHAW, CY
    ASHRAE JOURNAL-AMERICAN SOCIETY OF HEATING REFRIGERATING AND AIR-CONDITIONING ENGINEERS, 1981, 23 (02): : 21 - 25
  • [23] Investigation on the fire behaviour and propagation rule of fire overflow in the high-rise concave building structure
    Lu, Xin-Xiao
    Shi, Guo-Yu
    Song, Si-Yuan
    INDOOR AND BUILT ENVIRONMENT, 2023, 32 (01) : 214 - 229
  • [24] The effect of damper leakage and fire size on the performance of smoke control system in high-rise building
    Sung, Kun Hyuk
    Shin, Hyun Ju
    Baek, Dabin
    Ryou, Hong Sun
    JOURNAL OF MECHANICAL SCIENCE AND TECHNOLOGY, 2017, 31 (08) : 4029 - 4034
  • [25] The effect of damper leakage and fire size on the performance of smoke control system in high-rise building
    Kun Hyuk Sung
    Hyun Ju Shin
    Dabin Baek
    Hong Sun Ryou
    Journal of Mechanical Science and Technology, 2017, 31 : 4029 - 4034
  • [26] Experimental and analytical investigation of hydronic system retrofits in an urban high-rise mixed use building
    Waite, Michael
    Deshmukh, Ankita
    Modi, Vijay
    ENERGY AND BUILDINGS, 2017, 136 : 173 - 188
  • [27] Evaluating method for fire prevention of high-rise building
    Wang Rui
    Jin Shan
    Zhang Xiangyang
    Zhuang Damin
    PROGRESS IN SAFETY SCIENCE AND TECHNOLOGY, VOL 6, PTS A AND B, 2006, 6 : 686 - 689
  • [28] PATTON REPORT - FIRE SAFETY FOR HIGH-RISE BUILDING
    PATTON, RM
    ASHRAE JOURNAL, 1971, 13 (04): : 39 - &
  • [29] Simulation of Fire Evacuation in a High-Rise Office Building
    Bai, W.
    Huo, Y.
    Zou, G. W.
    Gao, Y.
    2015 IEEE INTERNATIONAL CONFERENCE ON INDUSTRIAL ENGINEERING AND ENGINEERING MANAGEMENT (IEEM), 2015, : 1704 - 1708
  • [30] HRBFS - a network simulator of fire in high-rise building
    Xie, XY
    Ren, AZ
    Zhou, XQ
    COMPUTATIONAL METHODS IN ENGINEERING AND SCIENCE, PROCEEDINGS, 2003, : 633 - 640