Assessment of energy savings potential from the use of demand controlled ventilation in general office spaces in California

被引:0
|
作者
Tianzhen Hong
William J. Fisk
机构
[1] Lawrence Berkeley National Laboratory,Environmental Energy Technologies Division
来源
Building Simulation | 2010年 / 3卷
关键词
building simulation; building energy standard; demand controlled ventilation; energy savings;
D O I
暂无
中图分类号
学科分类号
摘要
A prototypical office building meeting the prescriptive requirements of the 2008 California Building Energy Efficiency Standards (Title 24) was used in EnergyPlus simulations to calculate the energy savings potential of demand controlled ventilation (DCV) in five typical California climates per three design occupancy densities and two minimum ventilation rates. The assumed minimum ventilation rates in offices without DCV, based on two different measurement methods employed in a large survey, were 38 and 13 L/s per occupant. The results of the life cycle cost analysis show DCV is cost effective for office spaces if the typical minimum ventilation rate without DCV is 38 L/s per person, except at the low design occupancy of 10.8 people per 100 m2 in climate zones 3 (north coast) and 6 (south coast). DCV was not found to be cost effective if the typical minimum ventilation rate without DCV is 13 L/s per occupant, except at high design occupancy of 21.5 people per 100 m2 in climate zones 14 (desert) and 16 (mountains). Until the large uncertainties about the base case ventilation rates in offices without DCV are reduced, the case for requiring DCV in general office spaces will be a weak case. Under the Title 24 standard office occupant density of 10.8 people per 100 m2, DCV becomes cost effective when the base case minimum ventilation rate is greater than 42.5, 43.0, 24.0, 19.0, and 18.0 L/s per person for climate zones 3, 6, 12, 14, and 16, respectively.
引用
收藏
页码:117 / 124
页数:7
相关论文
共 42 条
  • [1] Assessment of energy savings potential from the use of demand controlled ventilation in general office spaces in California
    Hong, Tianzhen
    Fisk, William J.
    BUILDING SIMULATION, 2010, 3 (02) : 117 - 124
  • [2] A simplified model for evaluating the energy saving potential of adopting demand controlled ventilation in office buildings in Hong Kong
    Jia, Jie
    Lee, Wai-Ling
    Chen, Hua
    Li, Han
    INDOOR AND BUILT ENVIRONMENT, 2018, 27 (01) : 47 - 58
  • [3] Energy savings in cleanrooms from demand-controlled filtration
    Faulkner, D
    Fisk, WJ
    Walton, JT
    JOURNAL OF THE INSTITUTE OF ENVIRONMENTAL SCIENCES, 1996, 39 (06): : 21 - 27
  • [4] Impact of demand controlled ventilation on system performance and energy use
    Delwati, Muhannad
    Merema, Bart
    Breesch, Hilde
    Helsen, Lieve
    Sourbron, Maarten
    ENERGY AND BUILDINGS, 2018, 174 : 111 - 123
  • [5] CO2 demand controlled ventilation using on-off control for energy savings
    Hajiah, AEH
    Proceedings of the Fifth IASTED International Conference on Modelling, Simulation, and Optimization, 2005, : 312 - 317
  • [6] A simplified method to estimate cooling energy savings from night ventilation for office buildings
    Liu, Xiang
    Krarti, Moncef
    PROCEEDINGS OF THE ENERGY SUSTAINABILITY CONFERENCE 2007, 2007, : 781 - 786
  • [7] Study of the potential savings on energy demand and HVAC energy consumption by using coated glazing for office buildings in Madrid
    Cordoba, J
    Macias, M
    Espinosa, JM
    ENERGY AND BUILDINGS, 1998, 27 (01) : 13 - 19
  • [8] Energy savings in existing swedish apartment buildings some aspects on demand controlled ventilation and individual metering
    Building Services Engineering, Department of Energy and Environment, Chalmers University of Technology, Göteborg, Sweden
    不详
    Doktorsavh. Chalmers Tek. Hogsk., 2006, 2414 (1-166):
  • [9] Demand-controlled ventilation in new residential buildings: Consequences on indoor air quality and energy savings
    Hesaraki, Arefeh
    Holmberg, Sture
    INDOOR AND BUILT ENVIRONMENT, 2015, 24 (02) : 162 - 173
  • [10] DEMAND CONTROLLED VENTILATION BY ROOM CO2 CONCENTRATION - A COMPARISON OF SIMULATED ENERGY SAVINGS IN AN AUDITORIUM SPACE
    WARREN, BF
    HARPER, NC
    ENERGY AND BUILDINGS, 1991, 17 (02) : 87 - 96