Study of Ablation of Arc Contacts and Dynamic Contact Resistance in High Current Breaker

被引:1
|
作者
Licheng Xing
Xiaodong Zhang
Qingbin Tong
Gaoqi Xing
机构
[1] Beijing Jiaotong University,School of Electrical Engineering
[2] State Grid Shandong Power Company,undefined
关键词
Arc ablation; Arcing time; Breaking arc; Contacting resistance; Mass loss;
D O I
暂无
中图分类号
学科分类号
摘要
The fault of power circuit breaker (PCB) can lead very serious problems, especially in high voltage–power grid. The structure of contacts may be composed of main contacts and arc contacts, and this structure can avoid ablation of main contacts efficiently. It is necessary to study the eroded state of the arc contacts and the dynamic contact resistance of arc contacts to estimate the operating state of the PCB. The wear of contacts contains arc ablation and mechanical wear through the characteristics of contacts. The arc ablation is caused by the high temperature of the arc and the mechanical wear is caused by the mechanical friction of static and movable contacts. Some experiments have been done under different size of contacts and different current through them. The results show that the mechanical wear increases, sometimes heavier, with the increase of the size of fixed contacts and the decrease of the size of movable ones because the force between fixed and movable contacts becomes larger. The results also show that the ablation of arc contacts increases with the increase of current, especially when the current is up to 20 kA. With the high temperature of arc reaching the hardness point of copper, the arc ablation and mechanical erosion are increasing obviously since the contacts become soft and easy to wear. Another result of the study shows it is important to choose the material of contacts and the force between movable and fixed contacts. The harder and less resistance the material of contacts, the better the operating situation. To monitor the operating situation of the breaker, the dynamic contact resistance was measured 25 times. As a result, the dynamic contact resistance is sensitive to the current and increasing with the increase of continuous experiment time because of the increasing of metal ions. Furthermore, if the SF6 in the PCB is changes, the dynamic contact resistance would be changed. The dynamic contact resistance in this experiment varies substantially within the range of 80–250 μΩ at the current of 20 kA.
引用
收藏
页码:1015 / 1023
页数:8
相关论文
共 50 条
  • [31] Arc characteristic and ablation resistance of WCu electrical contact material with different microstructure
    Wang, Xingang
    Zhang, Huailong
    Shi, Bin
    Yang, Zhimao
    Xiyou Jinshu/Chinese Journal of Rare Metals, 2014, 38 (03): : 371 - 378
  • [32] High contact resistance readings on clean microwave mobile contacts
    Kwiatkowski, R
    Vladimirescu, M
    Zybura, A
    Bradic, J
    ELECTRICAL CONTACTS-2004: PROCEEDINGS OF THE 50TH IEEE HOLM CONFERENCE ON ELECTRICAL CONTACTS/THE 22ND INTERNATIONAL CONFERENCE ON ELECTRICAL CONTACTS, 2004, : 160 - 167
  • [33] Prediction of the dynamic contact resistance of circuit breaker based on the kernel partial least squares
    Liu, Yakui
    Zhang, Guogang
    Qin, Hao
    Geng, Yingsan
    Wang, Jianhua
    Yang, Jinggang
    Zhao, Ke
    IET GENERATION TRANSMISSION & DISTRIBUTION, 2018, 12 (08) : 1815 - 1821
  • [34] ARC VOLTAGE DURING CLOSING WITH REBOUNDS ON HIGH-CURRENT CONTACTS
    WALCZUK, E
    ETZ ARCHIV, 1982, 4 (08): : 249 - 252
  • [35] Arc Erosion of Polarised Contacts Ag-W by High Current
    Borkowski, Piotr
    Hasegawa, Makoto
    IEICE TRANSACTIONS ON ELECTRONICS, 2010, E93C (09): : 1416 - 1423
  • [36] Numerical Study on Arc Plasma Behavior During Arc Commutation Process in Direct Current Circuit Breaker
    杨飞
    马瑞光
    吴翊
    孙昊
    纽春萍
    荣命哲
    Plasma Science and Technology, 2012, (02) : 167 - 171
  • [37] Numerical Study on Arc Plasma Behavior During Arc Commutation Process in Direct Current Circuit Breaker
    Yang Fei
    Ma Ruiguang
    Wu Yi
    Sun Hao
    Niu Chunping
    Rong Mingzhe
    PLASMA SCIENCE & TECHNOLOGY, 2012, 14 (02) : 167 - 171
  • [38] Numerical Study on Arc Plasma Behavior During Arc Commutation Process in Direct Current Circuit Breaker
    杨飞
    马瑞光
    吴翊
    孙昊
    纽春萍
    荣命哲
    Plasma Science and Technology, 2012, 14 (02) : 167 - 171
  • [39] Influence of the Splitter Plates on the High Current Air Arc in Low Voltage Circuit Breaker
    Liu, Hongwu
    Guan, Ruiliang
    Yin, Nairui
    Xie, Xinyi
    Chen, Degui
    IEICE TRANSACTIONS ON ELECTRONICS, 2013, E96C (09): : 1119 - 1123
  • [40] Simulation Study of the Influence of Wall Ablation on Arc Behavior in a Low-Voltage Circuit Breaker
    Ma, Qiang
    Rong, Mingzhe
    Murphy, Anthony B.
    Wu, Yi
    Xu, Tiejun
    IEEE TRANSACTIONS ON PLASMA SCIENCE, 2009, 37 (01) : 261 - 269