Evaluation of audible noise from surface processing conductors for AC overhead transmission line

被引:15
|
作者
Miyajima, Kiyotomi [1 ]
Tanabe, Kazuo [1 ]
机构
[1] Cent Res Inst Elect Power Ind, Komae, Tokyo, Japan
关键词
corona discharge; audible noise; AC overhead transmission line; wetting property; TiO2;
D O I
10.1002/eej.20509
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
Corona discharge may cause audible noise, and it is frequently generated from wet conductors of high-voltage AC overhead transmission lines. Audible noise arises more easily from new conductors that have lubricating oil on their surface than from aged conductors. In this paper, the corona characteristics, particularly the audible noise, of conductors having various wetting properties are presented for the purpose of developing a corona-free conductor for AC overhead transmission lines. It was found that a conductor having a super-hydrophobic surface exhibited a minimized audible noise level, but it does not have sufficient durability for practical applications. Furthermore, a conductor having a super-hydrophilic surface made by thermal spraying of TiO2 showed good performance regarding the suppression of audible noise. The thermal spraying of TiO2 seems to be an effective processing technique that has sufficient durability for practical applications. (c) 2007 Wiley Periodicals, Inc.
引用
收藏
页码:19 / 25
页数:7
相关论文
共 50 条
  • [21] ASSESSING THE IMPACT OF AUDIBLE NOISE FROM ac TRANSMISSION LINES: A PROPOSED METHOD.
    Keast, David N.
    1979,
  • [22] Long-term evaluation of HVDC transmission line audible noise and its correlation with background noise
    Shin, Koo Yong
    Oh, Joon Arm
    Kwon, Gu Min
    Ju, Mun No
    Woo, Jeong Min
    AIP ADVANCES, 2019, 9 (09):
  • [23] Computation of Audible Noise from a 1200 kV UHV Power Transmission Line
    Kumar, K. Bharath
    Thomas, M. Joy
    IEEE TRANSACTIONS ON DIELECTRICS AND ELECTRICAL INSULATION, 2016, 23 (02) : 974 - 978
  • [24] On Calculating Surface Potential Gradient of Overhead Line Conductors
    Li, Q.
    Shuttleworth, R.
    Zhang, G.
    Rowland, S. M.
    Morris, R. S.
    CONFERENCE RECORD OF THE 2012 IEEE INTERNATIONAL SYMPOSIUM ON ELECTRICAL INSULATION (ISEI), 2012, : 540 - 544
  • [25] Calculating the Surface Potential Gradient of Overhead Line Conductors
    Li, Qi
    Rowland, Simon M.
    Shuttleworth, Roger
    IEEE TRANSACTIONS ON POWER DELIVERY, 2015, 30 (01) : 43 - 52
  • [26] SHAPE OPTIMIZATION OF OVERHEAD TRANSMISSION-LINE BUNDLED CONDUCTORS
    ALEKSANDROV, GN
    PODPORKIN, GV
    SELENZNEV, YG
    ELECTRICAL TECHNOLOGY, 1988, (04): : 1 - 15
  • [27] Recent technology trend of overhead transmission line conductors and fittings
    Katou A.
    IEEJ Transactions on Power and Energy, 2016, 136 (02) : 114 - 117
  • [28] A Finite-Element Approach for Electric Field Computation at the Surface of Overhead Transmission Line Conductors
    Farah, Arthur A. M.
    Afonso, Marcio M.
    Vasconcelos, Joao A.
    Schroeder, Marco A. O.
    IEEE TRANSACTIONS ON MAGNETICS, 2018, 54 (03)
  • [29] Environmental effect of high voltage AC transmission lines audible noise
    Al-Faraj, MA
    Shwehdi, MH
    Farag, AS
    IECEC-97 - PROCEEDINGS OF THE THIRTY-SECOND INTERSOCIETY ENERGY CONVERSION ENGINEERING CONFERENCE, VOLS 1-4: VOL.1: AEROSPACE POWER SYSTEMS AND TECHNOL; VOL 2: ELECTROCHEMICAL TECHNOL, CONVERSION TECHNOL, THERMAL MANAGEMENT; VOLS 3: ENERGY SYSTEMS, RENEWABLE ENERGY RESOURCES, ENVIRONMENTAL IMPACT, POLICY IMPACTS ON ENERGY; VOL 4: POST DEADLINE PAPERS, INDEX, 1997, : 2082 - 2087
  • [30] AUDIBLE NOISE AND VISUAL CORONA FROM HV AND EHV TRANSMISSION LINES AND SUBSTATION CONDUCTORS - LABORATORY TESTS
    TAYLOR, ER
    CHARTIER, VL
    RICE, DN
    IEEE TRANSACTIONS ON POWER APPARATUS AND SYSTEMS, 1969, PA88 (05): : 666 - &