Investigation of the performance of a cylindrical PCM-to-air heat exchanger (PAHE) for free ventilation cooling in fluctuating ambient environments

被引:18
|
作者
Yang, Dong [1 ,2 ]
Shi, Rui [1 ,2 ]
Wei, Haibin [1 ,2 ]
Du, Jinhui [1 ,2 ]
Wang, Jilibo [1 ,2 ]
机构
[1] Chongqing Univ, Sch Civil Engn, Chongqing 400044, Peoples R China
[2] Natl Ctr Int Res Low Carbon & Green Bldg, Chongqing 400044, Peoples R China
基金
中国国家自然科学基金;
关键词
Phase change material; Free cooling; Fluctuating thermal environment; Latent heat transfer; Peak temperature shaving; Cooling load reduction; PHASE-CHANGE MATERIAL; THERMAL PERFORMANCE; BUILDINGS; STORAGE; TECHNOLOGIES; COMFORT; WALL; INTEGRATION; SIMULATION; REDUCTION;
D O I
10.1016/j.scs.2019.101764
中图分类号
TU [建筑科学];
学科分类号
0813 ;
摘要
This paper proposes the use of a cylindrical annulus composed of phase change material (PCM), referred to as a PCM-air heat exchanger (PAHE), to regulate the supplied air temperature in ventilated buildings exposed to fluctuating thermal environments. The forced convection inside the PAHE tube enhances the heat transfer between the air and PCM, and thus both the sensible and latent heat transfer contribute to reducing the air temperature fluctuations and peak cooling/heating loads. Both experiments and numerical simulations are performed to investigate the performance of a PAHE exposed to fluctuating ambient temperatures. The effects of three PAHE parameters, i.e., the flow rate through the PAHE tube, melting temperature of the PCM, external diameter of the PAHE, and the tube length on the PAHE performance were investigated numerically. Maintaining a stable inner surface temperature in the PAHE is crucial for maximizing its ability to reduce air temperature fluctuation amplitude. For this purpose, these key parameters should be appropriately selected. The cooling performance of the PAHE in a region with hot summers and cold winters region was evaluated. The simulation incorporated real meteorological data of two transitional seasons and a summer, and demonstrated a maximum reduction in air temperature of 5.4 degrees C.
引用
收藏
页数:11
相关论文
共 24 条
  • [21] Energy, exergy, and economic (3E) analyses of nanoparticle-enriched phase change material in an air-PCM heat exchanger applied for buildings free cooling
    Safarzadeh, Sajjad
    Yousefi, Milad
    Kazemi, Mahdi
    Kianifar, Ali
    JOURNAL OF THERMAL ANALYSIS AND CALORIMETRY, 2023, 148 (16) : 8533 - 8545
  • [22] Characteristic studies of heat sources and performance analysis of free-cooling assisted air conditioning and ventilation systems for working faces of mineral mines
    Rang Tu
    Lijuan Huang
    Aibing Jin
    Mingfeng Zhang
    Xiao Hai
    Building Simulation, 2021, 14 : 1725 - 1736
  • [23] Characteristic studies of heat sources and performance analysis of free-cooling assisted air conditioning and ventilation systems for working faces of mineral mines
    Tu, Rang
    Huang, Lijuan
    Jin, Aibing
    Zhang, Mingfeng
    Hai, Xiao
    BUILDING SIMULATION, 2021, 14 (06) : 1725 - 1736
  • [24] Investigation of the impact of pipe geometric form on earth-to-air heat exchanger performance using Complex Finite Fourier Transform analysis. Part I: Operation in cooling mode
    Benhammou, M.
    Sahli, Y.
    Moungar, H.
    INTERNATIONAL JOURNAL OF THERMAL SCIENCES, 2022, 177