Overhead lines fault location and arc voltage estimation numerical algorithm derived in time domain

被引:0
|
作者
Djuric, MB [1 ]
Terzija, VV [1 ]
Radojevic, ZM [1 ]
机构
[1] Univ Belgrade, Fac Elect Engn, YU-11001 Belgrade, Yugoslavia
来源
ELECTRICAL ENGINEERING | 1998年 / 81卷 / 01期
关键词
D O I
10.1007/BF01233056
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
A new fault location numerical algorithm based on terminal data and derived in time domain is presented. The fault location and its nature (arcing or arcless fault) are estimated using least error squares technique. The faulted phase voltage is modelled as a serial connection of fault resistance and are voltage. The new approach does not require the line zero sequence resistance as an input datum. In the paper some important features of are voltage are given. The algorithm is derived for the most frequent case of single-phase line to ground unsymmetrical fault. The results of algorithm testing by computer simulation and under laboratory conditions are given. The influences of remote infeed, fault resistance, higher order harmonics, network topology and other factors are investigated and presented.
引用
收藏
页码:45 / 53
页数:9
相关论文
共 50 条
  • [1] Overhead lines fault location and arc voltage estimation numerical algorithm derived in time domainLichtbogenspannung und Fehlerdistanz Schätzung in Freileitungsnetzen mittels im Zeitbereich entwickelten numerischen Algorithmus
    M. B. Djurić
    V. V. Terzija
    Z. M. Radojević
    Electrical Engineering, 1998, 81 (1) : 45 - 53
  • [2] On time domain overhead lines numerical protection
    Djuric, MB
    Radojevic, ZM
    Terzija, VV
    ELECTRIC MACHINES AND POWER SYSTEMS, 1999, 27 (08): : 889 - 904
  • [3] Time domain solution of fault distance estimation and arcing faults detection on overhead lines
    Djuric, MB
    Radojevic, ZM
    Terzija, VV
    IEEE TRANSACTIONS ON POWER DELIVERY, 1999, 14 (01) : 60 - 67
  • [4] Secondary Arc and Critical Time of Fault Clearance in Overhead Lines
    Arias Velasquez, R. M.
    Mejia Lara, J. V.
    IEEE LATIN AMERICA TRANSACTIONS, 2018, 16 (03) : 859 - 868
  • [6] FAULT LOCATION FOR OVERHEAD DISTRIBUTION LINES
    EVANS, JH
    ELECTRICAL REVIEW, 1972, 191 (09): : 317 - &
  • [7] A fault location algorithm for high voltage overhead power transmission line based on line parameter estimation
    Liang, Jun
    Ma, Chang-Hui
    Yun, Zhi-Hao
    Power System Technology, 2004, 28 (04) : 60 - 63
  • [8] Arc fault location: A nonlinear time varying fault model and frequency domain parameter estimation approach
    Ferraz, Renato G.
    Iurinic, Leonardo U.
    Filomena, Andre D.
    Gazzana, Daniel S.
    Bretas, Arturo S.
    INTERNATIONAL JOURNAL OF ELECTRICAL POWER & ENERGY SYSTEMS, 2016, 80 : 347 - 355
  • [9] Effective algorithm for fault discrimination and estimation of fault location in transmission lines
    Gangolu, Suryanarayana
    Raja, P.
    Selvan, M. P.
    Murali, Venkata Kirthiga
    IET GENERATION TRANSMISSION & DISTRIBUTION, 2019, 13 (13) : 2789 - 2798
  • [10] Numerical algorithm for medium voltage overhead lines protection and adaptive autoreclosure
    V. V. Terzija
    Z. M. Radojević