Impact analysis of tap switch out of step for converter transformer

被引:0
|
作者
Zhang Hong-yue [1 ]
Zhang Zhen-hua [1 ]
Xiong Zhang-xue [1 ]
Yu Gao-wang [1 ]
机构
[1] XJ Grp Ltd, Xuchang 461000, Peoples R China
关键词
D O I
10.1088/1755-1315/69/1/012200
中图分类号
TE [石油、天然气工业]; TK [能源与动力工程];
学科分类号
0807 ; 0820 ;
摘要
AC transformer load regulation is mainly used to adjust the load side voltage level, improve the quality of power supply, the voltage range is relatively narrow. In DC system, converter transformer is the core equipment of AC and DC power converter and inverter. converter transformer tap adjustment can maintain the normal operation of the converter in small angle range control, the absorption of reactive power, economic operation, valve less stress, valve damping circuit loss, AC / DC harmonic component is also smaller. In this way, the tap switch action is more frequent, and a large range of the tap switch adjustment is required. Converter transformer with a more load voltage regulation switch, the voltage regulation range of the switch is generally 20 similar to 30%, the adjustment of each file is 1%similar to 2%. Recently it is often found that the tap switch of Converter Transformers is out of step in Converter station. In this paper, it is analyzed in detail the impact of tap switch out of step for differential protection, overexcitation protection and zero sequence over current protection. Analysis results show that: the tap switch out of step has no effect on the differential protection and the overexcitation protection including the tap switch. But the tap switch out of step has effect on zero sequence overcurrent protection of out of step star-angle converter transformer. The zero sequence overcurrent protection will trip when the tap switch out of step is greater than 3 for out of step star-angle converter transformer.
引用
收藏
页数:10
相关论文
共 50 条
  • [1] Analysis on ferroresonance over-voltage of UHV converter transformer bushing tap
    Tang Ming
    Ding LiJie
    Tang Fan
    Chen Gang
    PROCEEDINGS OF THE 2015 4TH NATIONAL CONFERENCE ON ELECTRICAL, ELECTRONICS AND COMPUTER ENGINEERING ( NCEECE 2015), 2016, 47 : 1306 - 1312
  • [2] Behavioral analysis of a single-switch step up converter
    Tatakis, Emmanuel C.
    Kalogeropoulou, Margarita
    Christidis, Georgios C.
    PROCEEDINGS OF THE 2011-14TH EUROPEAN CONFERENCE ON POWER ELECTRONICS AND APPLICATIONS (EPE 2011), 2011,
  • [3] Characterizing the diverter switch of a load tap changer in a transformer using wavelet and modal analysis
    Rivas-Trujillo, Edwin
    Laniado-Jacome, Edwin
    Luis San-Roman, Jose
    Diaz, Vicente
    ENGINEERING STRUCTURES, 2010, 32 (10) : 3011 - 3017
  • [5] Analysis and Peak Current Mode Control of Active Clamp Forward Converter with Center Tap Transformer
    Rajguru, V. S.
    Chaudhari, B. N.
    IEEE INTERNATIONAL CONFERENCE ON POWER ELECTRONICS, DRIVES AND ENERGY SYSTEMS (PEDES 2012), 2012,
  • [6] A Novel Single Switch Step Down Converter
    Botila, Delia-Anca
    Pop-Calimanu, Ioana-Monica
    Lascu, Dan
    2021 IEEE 19TH INTERNATIONAL POWER ELECTRONICS AND MOTION CONTROL CONFERENCE (PEMC), 2021, : 31 - 38
  • [7] A novel thyristor assisted diverter switch for on load transformer tap changer
    Gao, DW
    IEEE/PES TRANSMISSION AND DISTRIBUTION CONFERENCE AND EXHIBITION 2002: ASIA PACIFIC, VOLS 1-3, CONFERENCE PROCEEDINGS: NEW WAVE OF T&D TECHNOLOGY FROM ASIA PACIFIC, 2002, : 297 - 300
  • [8] NEW THYRISTOR ASSISTED DIVERTOR SWITCH FOR ON LOAD TRANSFORMER TAP CHANGERS
    COOKE, GH
    WILLIAMS, KT
    IEE PROCEEDINGS-B ELECTRIC POWER APPLICATIONS, 1992, 139 (06): : 507 - 511
  • [9] Single-Switch High Step-up Converter With Coupled-Inductor and Built-In Transformer
    Lu, Yiwen
    Liu, Huawu
    Hu, Haibing
    Wu, Hongfei
    Xing, Yan
    PROCEEDINGS OF THE 2015 10TH IEEE CONFERENCE ON INDUSTRIAL ELECTRONICS AND APPLICATIONS, 2015, : 1186 - 1191
  • [10] Modelling and Control of Active Clamp Forward Converter with Centre Tap Transformer
    Rajguru, Vijaya Sanjay
    Chaudhari, Bhalchandra Nemichand
    IETE JOURNAL OF RESEARCH, 2015, 61 (05) : 447 - 456