In-service ageing comparison study of natural ester and mineral oil filled distribution transformers

被引:3
|
作者
Zhao, Yaohong [1 ]
Qian, Yihua [1 ]
Wei, Bin [2 ]
Wang, Ruifeng [3 ]
Rapp, Kevin James [4 ]
Xu, Yang [5 ]
机构
[1] Guangdong Power Grid Co Ltd, Elect Power Res Inst, CSG, Guangzhou, Guangdong, Peoples R China
[2] Shaanxi Power Grid Co Ltd, Xianyang Power Supply Bur, SGCC, Xianyang, Peoples R China
[3] Cargill, Shanghai, Peoples R China
[4] Cargill, Plymouth, MN, Peoples R China
[5] Xi An Jiao Tong Univ, State Key Lab, Xian, Shaanxi, Peoples R China
基金
中国国家自然科学基金;
关键词
natural ester; distribution transformer; in-service operation;
D O I
10.1109/icdl.2019.8796673
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
In 2011, Shaanxi Power Grid Corporation, a Chinese utility, launched the first batch of natural ester-filled transformers in China to investigate the effectiveness of environmentally friendly insulating liquid in operating transformers. After 7 years continuous operation, two healthy 10kV 200kVA units were selected for study, one is filled with a soybean based natural ester liquid, EnvirotempT FR3T Fluid, the other is filled with mineral oil. These two distribution transformers (DT) were operating in the same city for about the same time period. Each transformer is made by a different manufacturers but have similar designs, however, their loading profiles differed significantly. The transformers were taken off the grid in June of 2018. Routine tests of the transformers and oils show that the transformers are in good condition. In January of 2019, both transformers were disassembled to test the oil and winding paper insulation samples. The oil condition, degree of polymerization and water content of paper samples from both units were compared. The details of the teardown and laboratory analysis are presented in this paper. In view of this in-service 7 year test, the compatibility of NE liquid with transformer construction materials under normal loading rate condition is confirmed. Also, the results offer useful status information about oil-paper insulating system for performance diagnosis in daily operation.
引用
收藏
页数:4
相关论文
共 50 条
  • [1] Assessment of In-Service Transformers Filled with Synthetic Ester at 33 kV and Below
    Daghrah, Muhammad
    Onay, Oguz
    [J]. IEEE ELECTRICAL INSULATION MAGAZINE, 2021, 37 (05) : 6 - 13
  • [2] Challenges in Oil Test Database Analysis for Ageing Assessment of In-Service Transformers
    Tee, S. J.
    Liu, Q.
    Wang, Z. D.
    Wilson, G.
    Jarman, P.
    Hooton, R.
    Walker, D.
    Dyer, P.
    [J]. 2015 50TH INTERNATIONAL UNIVERSITIES POWER ENGINEERING CONFERENCE (UPEC), 2015,
  • [3] Ageing of Crepe Paper in Mineral Oil and Natural Ester
    Fernandez-Diego, Cristina
    Ortiz, Alfredo
    Fernandez, Inmaculada
    Renedo, Carlos J.
    Delgado, Fernando
    [J]. PROCEEDINGS OF 2020 INTERNATIONAL SYMPOSIUM ON ELECTRICAL INSULATING MATERIALS (ISEIM 2020), 2020, : 217 - 220
  • [4] Study on the Contamination Rate of Mineral Oil in Natural-Ester Retrofilled Transformers
    Montero, Andres
    Garcia, Belen
    Burgos, Juan Carlos
    [J]. IEEE TRANSACTIONS ON DIELECTRICS AND ELECTRICAL INSULATION, 2023, 30 (04) : 1641 - 1648
  • [5] Factorial analysis for ageing assessment of in-service transformers
    Wang, Dongmiao
    Tee, Sheng Ji
    Liu, Qiang
    Wang, Zhongdong
    [J]. IET GENERATION TRANSMISSION & DISTRIBUTION, 2018, 12 (13) : 3177 - 3185
  • [6] Condition monitoring of in-service oil-filled transformers: Case studies and experience
    Rao, U. Mohan
    Fofana, I.
    Betie, A.
    Senoussaoui, M. L.
    Brahami, M.
    Briosso, E.
    [J]. IEEE ELECTRICAL INSULATION MAGAZINE, 2019, 35 (06) : 33 - 42
  • [7] Evaluation of High Temperature Operation of Natural Ester Filled Distribution Transformers
    Vaidya, Chinmay V.
    Karady, George G.
    Sbravati, Alan
    Valmus, Jeff
    Dyer, Michael
    [J]. 2018 NORTH AMERICAN POWER SYMPOSIUM (NAPS), 2018,
  • [8] Natural and Synthetic Ester Liquids as alternative to mineral oil for power transformers
    Gockenbach, E.
    Borsi, H.
    [J]. 2008 IEEE CONFERENCE ON ELECTRICAL INSULATION AND DIELECTRIC PHENOMENA, 2008, : 663 - 666
  • [9] Comparative Study on Power Transformers Vegetable and Mineral Oil Ageing
    Ciuriuc, Alexandra
    Vihacencu, Mirela Stefania
    Dumitran, Laurentiu Marius
    Notingher, Petru V.
    [J]. 2012 INTERNATIONAL CONFERENCE ON APPLIED AND THEORETICAL ELECTRICITY (ICATE), 2012,
  • [10] Assessment of In-Service Transformers Filled with Synthetic Ester at 33 kV and Below-Part 2
    Aljarrah, Rafat
    Daghrah, Muhammad
    Bakeer, Ayham
    [J]. IEEE ELECTRICAL INSULATION MAGAZINE, 2024, 40 (01) : 7 - 14