Energy efficient fuzzy based combined variable refrigerant volume and variable air volume air conditioning system for buildings

被引:63
|
作者
Karunakaran, R. [2 ]
Iniyan, S. [1 ]
Goic, Ranko [3 ]
机构
[1] Anna Univ, Dept Mech Engn, Inst Energy Studies, Madras 600025, Tamil Nadu, India
[2] Anna Univ Tiruchirappalli, Dept Mech Engn, Tiruchirappalli, Tamil Nadu, India
[3] Univ Split, Fac Elect Engn Mech Engn & Naval Architecture, Split, Croatia
关键词
Energy conservation; Fuzzy logic; Indoor air quality; Thermal comfort; Ventilation; Variable refrigerant volume; Variable air volume; DYNAMIC-MODEL; SIMULATION;
D O I
10.1016/j.apenergy.2009.08.013
中图分类号
TE [石油、天然气工业]; TK [能源与动力工程];
学科分类号
0807 ; 0820 ;
摘要
Energy conservative building design has triggered greater interests in developing flexible and sophisticated air conditioning systems capable of achieving enhanced energy-savings potential without sacrificing the desired thermal comfort and indoor air quality (IAQ). This research work greatly aimed at achieving enhanced energy conservation, good thermal comfort and better IAQ for space conditioning with the application of combined variable refrigerant volume (VRV) and variable air volume (VAV) air conditioning (A/C) systems. Experimental investigation on the proposed combined air conditioning system with the application of intelligent fuzzy logic controller was performed for summer and winter climatic conditions to substantiate the energy-savings capability. The proposed system experimentally analyzed under fixed ventilation, demand controlled ventilation (DCV) and combined DCV and economizer cycle (EC) ventilation techniques effectively conserved 44% and 63% of per day average energy-savings in summer and winter design conditions respectively, while compared to the conventional constant air volume (CAV) A/C system. The results of the present investigation have proved that the proposed combined air conditioning system operated under the different ventilation strategies and controlled by the intelligent fuzzy logic controller (FLC) can be considered as an efficient technology to achieve good thermal comfort, IAQ and energy conservation in the modern heating, ventilation and air conditioning (HVAC) applications. (C) 2009 Elsevier Ltd. All rights reserved.
引用
收藏
页码:1158 / 1175
页数:18
相关论文
共 50 条
  • [31] Decoupling Control of a Variable-Air-Volume Air-Conditioning System Based on State Feedback
    Huang, Yonghong
    Yang, Xuejun
    [J]. 2008 INTERNATIONAL SYMPOSIUM ON INTELLIGENT INFORMATION TECHNOLOGY APPLICATION, VOL III, PROCEEDINGS, 2008, : 589 - +
  • [32] Dynamic Model-Based Fault Tolerant Control of Variable Air Volume Air Conditioning System
    Talukdar, Atanu
    Patra, Amit
    [J]. HVAC&R RESEARCH, 2010, 16 (02): : 233 - 254
  • [33] VARIABLE AIR VOLUME
    URBAN, RA
    [J]. ASHRAE JOURNAL, 1970, 12 (11): : 8 - &
  • [34] VARIABLE AIR VOLUME
    GUPTA, VK
    INTHOUT, D
    ROBERTS, MM
    WESSEL, DJ
    BRICKMAN, H
    WAELDNER, W
    [J]. ASHRAE JOURNAL-AMERICAN SOCIETY OF HEATING REFRIGERATING AND AIR-CONDITIONING ENGINEERS, 1987, 29 (08): : 22 - &
  • [35] VARIABLE AIR VOLUME
    RICKELTON, D
    BECKER, HP
    [J]. ASHRAE JOURNAL, 1972, 14 (09) : 31 - +
  • [36] Simulation design of automatic control system of variable air volume air conditioning under simple air volume control algorithm
    Hu Nan Financial & Industry Vocational-Technical College, Hu Nan
    421000, China
    不详
    不详
    [J]. Int. J. Mech. Appl. Mech, 2020, 8 (70-76):
  • [37] VARIABLE AIR VOLUME
    STEINACHER, HE
    [J]. REFRIGERATION AND AIR CONDITIONING, 1976, 79 (936): : 41 - &
  • [38] VARIABLE AIR VOLUME
    BECKER, HP
    [J]. ASHRAE JOURNAL, 1970, 12 (08): : 4 - +
  • [39] VARIABLE AIR VOLUME
    STEINACHER, HE
    [J]. REFRIGERATION AND AIR CONDITIONING, 1976, 79 (935): : 36 - &
  • [40] ROOM AIR DISTRIBUTION WITH A VARIABLE AIR VOLUME SYSTEM
    STRAUB, HE
    [J]. ASHRAE JOURNAL, 1969, 11 (06): : 69 - &