Interruption in Air for Different Medium-Voltage Switching Duties

被引:10
|
作者
Jonsson, Erik [1 ]
Runde, Magne [2 ]
机构
[1] Norwegian Univ Sci & Technol NTNU, Dept Elect Power Engn, NO-7491 Trondheim, Norway
[2] SINTEF Energy Res, NO-7465 Trondheim, Norway
关键词
Air; current interruption; current zero; load break switch; medium-voltage (MV) switchgear; puffer; thermal interruption; GASES;
D O I
10.1109/TPWRD.2014.2345129
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
Air is an environmentally benign alternative to SF for use in medium-voltage load-break switches. A simple, axisymmetric test switch has been used for empirical studies of the thermal phase of current interruption in atmospheric air. The purpose is to quantify how the pressure drop across the nozzle influences the interrupting capability at a different rate of rise of the recovery voltages (RRRVs) and with different current amplitudes. Tests with pressure drops in the range 0.1-1.1 bar, RRRVs of 40, 80, and 160 V/mu s, and currents of 300, 600, and 900 A were carried out. In general, the current that can be successfully interrupted is proportional with the pressure drop. Likewise, a steeper RRRV requires a proportionally higher pressure drop for the interruption to be successful. For compact air load-break switches for the important 24 kV/630-A class, it seems sufficient to provide a pressure drop of around 0.25 bar lasting for at least 20 ms to comply with the "mainly active load" test-type requirements.
引用
下载
收藏
页码:161 / 166
页数:6
相关论文
共 50 条
  • [1] Current Interruption in Air for a Medium-Voltage Load Break Switch
    Jonsson, Erik
    Aanensen, Nina Sasaki
    Runde, Magne
    IEEE TRANSACTIONS ON POWER DELIVERY, 2014, 29 (02) : 870 - 875
  • [2] Self-Blast Current Interruption and Adaption to Medium-Voltage Load Current Switching
    Taxt, Henning
    Niayesh, Kaveh
    Runde, Magne
    IEEE TRANSACTIONS ON POWER DELIVERY, 2019, 34 (06) : 2204 - 2210
  • [3] Medium-Voltage Load Current Interruption in the Presence of Ablating Polymer Material
    Taxt, Henning
    Niayesh, Kaveh
    Runde, Magne
    IEEE TRANSACTIONS ON POWER DELIVERY, 2018, 33 (05) : 2535 - 2540
  • [4] Arcing Voltage for a Medium-Voltage Air Load Break Switch
    Stoa-Aanensen, Nina
    Runde, Magne
    Teigset, Anders Dall'Osso
    PROCEEDINGS OF THE 2015 SIXTY-FIRST IEEE HOLM CONFERENCE ON ELECTRICAL CONTACTS (HOLM), 2015, : 101 - 106
  • [5] Interruption of small, medium-voltage transformer current with a vacuum circuit breaker
    Xemard, Alain
    Jurisic, Bruno
    Rioual, Michel
    Olivier, Arthur
    Sellin, Eric
    ELECTRIC POWER SYSTEMS RESEARCH, 2020, 187
  • [6] Numerical Simulation of Overvoltage Generated at Switching on Medium-voltage Motors with the aid of Different Circuit Breakers
    Chaly, A. M.
    Minaev, V. S.
    25TH INTERNATIONAL SYMPOSIUM ON DISCHARGES AND ELECTRICAL INSULATION IN VACUUM (ISDEIV 2012), 2012, : 240 - 243
  • [7] PROTECTING AND SWITCHING MEDIUM-VOLTAGE INDUSTRIAL POWER-SYSTEMS
    PALKO, E
    PLANT ENGINEERING, 1978, 32 (08) : 104 - 109
  • [8] New switching technologies in medium-voltage systems - Application and requirements
    Heinrich, C
    Schmitt, H
    Hoever, I
    SEVENTH INTERNATIONAL CONFERENCE ON AC-DC POWER TRANMISSION, 2001, (485): : 282 - 287
  • [9] Reducing interrupting duties of medium-voltage circuit breakers by increasing contact parting time
    Das, J. C.
    IEEE Conference Record of 2007 Annual Pulp and Paper Industry Technical Conference, 2007, : 257 - 264
  • [10] Medium-Voltage Arc Flash in Open Air and Padmounted Equipment
    Short, T. A.
    Eblen, M. L.
    2011 IEEE RURAL ELECTRIC POWER CONFERENCE (REPC), 2011,