Enhanced Security-Constrained OPF With Distributed Battery Energy Storage

被引:56
|
作者
Wen, Yunfeng [1 ]
Guo, Chuangxin [1 ]
Kirschen, Daniel S. [2 ]
Dong, Shufeng [1 ]
机构
[1] Zhejiang Univ, Coll Elect Engn, Hangzhou 310027, Zhejiang, Peoples R China
[2] Univ Washington, Dept Elect Engn, Seattle, WA 98195 USA
基金
中国国家自然科学基金;
关键词
Benders decomposition; energy storage; optimal power flow; security-constrained optimal power flow; OPTIMAL POWER-FLOW; SYSTEMS;
D O I
10.1109/TPWRS.2014.2321181
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
This paper discusses how fast-response distributed battery energy storage could be used to implement post-contingency corrective control actions. Immediately after a contingency, the injections of distributed batteries could be adjusted to alleviate overloads and reduce flows below their short-term emergency rating. This ensures that the post-contingency system remains stable until the operator has redispatched the generation. Implementing this form of corrective control would allow operators to take advantage of the difference between the short-and long-term ratings of the lines and would therefore increase the available transmission capacity. This problem is formulated as a two-stage, enhanced security-constrained OPF problem, in which the first-stage optimizes the pre-contingency generation dispatch, while the second-stage minimizes the corrective actions for each contingency. Case studies based on a six-bus test system and on the RTS 96 demonstrate that the proposed method provides effective corrective actions and can guarantee operational reliability and economy.
引用
收藏
页码:98 / 108
页数:11