Impact mechanism of the chip muffler on the cooling performance of super large-scale natural draft wet cooling tower under crosswind

被引:11
|
作者
Zhang, Xiaoyu [1 ]
Sun, Fengzhong [1 ]
Chen, Xuehong [2 ]
Deng, Weipeng [1 ]
Chen, Kun [1 ]
机构
[1] Shandong Univ, Sch Energy & Power Engn, Jinan 250061, Peoples R China
[2] Ludong Univ, Sch Energy & Power Engn, Yantai 264025, Peoples R China
关键词
Super large-scale natural draft wet cooling tower; Chip muffler; Layout pattern; Cooling performance; Crosswind; THERMAL PERFORMANCE; NOISE; SIMULATION;
D O I
10.1016/j.applthermaleng.2022.118753
中图分类号
O414.1 [热力学];
学科分类号
摘要
The noise attenuation of cooling towers mainly relies on the chip muffler, of which the layout pattern exerts a non-negligible impact on the cooling effect. This paper analyzes the impact mechanism of the chip muffler's layout pattern on the cooling performance of a super large-scale natural draft wet cooling tower (S-NDWCT) through a three-dimensional numerical study. The layout patterns of chip muffler include three installation angles (theta = 0, 15 and 30), three distances between the muffler and cooling tower (L = 0.0 m, 2.5 m and 5.0 m), and two layout angles of the muffler (alpha = 180 and 360). Results manifest that the chip muffler can enhance the cooling performance of S-NDWCT by improving the airflow uniformity in the tower. The optimal layout pattern is L = 0.0 m, theta = 0 and alpha = 360, under which the increment of circulating water temperature drop reaches a maximum of 1.04 celcius. The ventilation rate increases with the increase of L and the decrease of theta. The Merkel number increases with the decrease of L and theta. The circulating water temperature drop increases with the decrease of theta and shows little regularity with L. This paper can provide the reference for optimizing layout patterns and engineering applications of the chip muffler.
引用
收藏
页数:16
相关论文
共 50 条
  • [1] Theoretical study on impact of the dissipative muffler on the cooling performance of the hybrid mechanical draft wet cooling tower
    Zhang, Xiaoyu
    Sun, Fengzhong
    INTERNATIONAL COMMUNICATIONS IN HEAT AND MASS TRANSFER, 2025, 164
  • [2] Field test of the effect of crosswind on ventilation performance of a natural draft wet cooling tower
    Sun, F. (sfzh@sdu.edu.cn), 2012, Chinese Society for Electrical Engineering (32):
  • [3] Impact mechanism of the chip muffler layout patterns on the cooling performance of wet cooling towers
    Li, Xin
    Sun, Fengzhong
    Chen, Xuehong
    Liu, Chuanfei
    APPLIED THERMAL ENGINEERING, 2019, 161
  • [4] A CFD MODEL BASED ON WET DEPOSITION OF LARGE-SCALE NATURAL DRAFT COOLING TOWER
    Wang, Xuan
    Bao, Wenjie
    Huang, Xiaodong
    Wang, Xue
    Du, Fenglei
    Wang, Dezhong
    Wang, Bo
    REVISTA INTERNACIONAL DE CONTAMINACION AMBIENTAL, 2019, 35 : 23 - 32
  • [5] The cooling performance of a natural draft dry cooling tower under crosswind and an enclosure approach to cooling efficiency enhancement
    Wang, Weiliang
    Zhang, Hai
    Liu, Pei
    Li, Zheng
    Lv, Junfu
    Ni, Weidou
    APPLIED ENERGY, 2017, 186 : 336 - 346
  • [6] A Numerical Study on the Improving Techniques of the Cooling Performance of a Natural Draft Dry Cooling Tower under Crosswind
    Wang, Weiliang
    Liu, Pei
    Li, Zheng
    Ni, Weidou
    Liu, Jiangmin
    Li, Yongsheng
    PRES15: PROCESS INTEGRATION, MODELLING AND OPTIMISATION FOR ENERGY SAVING AND POLLUTION REDUCTION, 2015, 45 : 1081 - 1086
  • [7] Effect of cooling water salinity on the cooling performance of natural draft wet cooling tower
    Wan, Dawei
    Gao, Shasha
    Liu, Minghua
    Li, Shuguo
    Zhao, Yuanbin
    INTERNATIONAL JOURNAL OF HEAT AND MASS TRANSFER, 2020, 161
  • [8] A decoupled method to identify affecting mechanism of crosswind on performance of a natural draft dry cooling tower
    Weiliang Wang
    Junfu Lyu
    Hai Zhang
    Qing Liu
    Guangxi Yue
    Weidou Ni
    Frontiers in Energy, 2020, 14 : 318 - 327
  • [9] A decoupled method to identify affecting mechanism of crosswind on performance of a natural draft dry cooling tower
    Wang, Weiliang
    Lyu, Junfu
    Zhang, Hai
    Liu, Qing
    Yue, Guangxi
    Ni, Weidou
    FRONTIERS IN ENERGY, 2020, 14 (02) : 318 - 327
  • [10] The influence and analysis of natural crosswind on cooling characteristics of the high level water collecting natural draft wet cooling tower
    Ma, Libin
    Ren, Jianxing
    2017 3RD INTERNATIONAL CONFERENCE ON ENVIRONMENTAL SCIENCE AND MATERIAL APPLICATION (ESMA2017), VOLS 1-4, 2018, 108