Performance evolution on a dual-temperature CO2 transcritical refrigeration cycle with two cascade ejectors

被引:25
|
作者
Bai, Tao [1 ]
Yan, Gang [1 ]
Yu, Jianlin [1 ]
机构
[1] Xi An Jiao Tong Univ, Sch Energy & Power Engn, Dept Refrigerat & Cryogen Engn, Xian 710049, Peoples R China
基金
中国国家自然科学基金;
关键词
Thermodynamics; Exergy; CO2 transcritical cycle; Dual-temperature refrigeration; Ejector; INTERNAL HEAT-EXCHANGER; ADJUSTABLE EJECTOR; PRESSURE RECOVERY; OPTIMIZATION; EFFICIENCIES; SYSTEM;
D O I
10.1016/j.applthermaleng.2017.03.091
中图分类号
O414.1 [热力学];
学科分类号
摘要
This study proposes a modified dual-temperature CO2 transcritical refrigeration cycle, in which two cascade ejectors are applied to enhance the performance of a dual-temperature refrigeration system. The theoretical investigations with energetic and exergetic methods have been carried out, the results show that the dual-ejector cycle exhibits higher coefficient of performance (COP) and system exergy efficiency than that of the basic throttling refrigeration cycle and single ejector refrigeration cycle. In comparison with the single ejector refrigeration cycle at the given operation conditions, the proposed system improves the COP and exergy efficiency by 5.26-25.5% and 9.0-28.7%, and the pressure lift ratio of the two cascade ejectors could be improved by 6.0-12.2%. The largest exergy destruction of the proposed cycle occurs in the gas cooler, followed by the ejectors accounting for the 28.9% of the system exergy destruction rate. The performance characteristics of the double ejector cycle show its potential advantages in dual-temperature CO2 transcritical refrigeration systems. (C) 2017 Published by Elsevier Ltd.
引用
收藏
页码:26 / 35
页数:10
相关论文
共 50 条
  • [31] Investigation on performance of variable geometry ejectors for CO2 refrigeration cycles
    Liu, Fang
    Groll, Eckhard A.
    Li, Daqing
    [J]. ENERGY, 2012, 45 (01) : 829 - 839
  • [32] Performance Analysis and Comprehensive Evaluation of Solar Organic Rankine Cycle Combined with Transcritical CO2 Refrigeration Cycle
    Zhang, Na
    Xu, Po
    Wang, Yiming
    Tong, Wencai
    Yang, Zhao
    [J]. ENERGIES, 2023, 16 (14)
  • [33] Theoretical Study on CO2 Transcritical Cycle Combined Ejector Cycle Refrigeration System
    卢苇
    马一太
    李敏霞
    查世彤
    [J]. Transactions of Tianjin University, 2003, (04) : 316 - 320
  • [34] Performance improvement and multi-objective optimization of a two-stage and dual-temperature ejector auto-cascade refrigeration cycle driven by the waste heat
    Ye, Kai
    Liang, Youcai
    Zhu, Yan
    Ling, Xunjie
    Wu, Jintao
    Lu, Jidong
    [J]. Energy, 2024, 311
  • [35] Performance Analysis of Transcritical CO2 Compression Cycle
    Wang, Hongli
    Tian, Jingrui
    Liu, Huiqin
    [J]. INFORMATION COMPUTING AND APPLICATIONS, PT 2, 2012, 308 : 730 - 736
  • [36] Thermodynamic analysis of the effect of internal heat exchanger on the dual-ejector transcritical CO2 cycle for low-temperature refrigeration
    Zeng, Min-Qiang
    Zhang, Xue-Lai
    Mo, Fan-Yang
    Zhang, Xin-Rong
    [J]. INTERNATIONAL JOURNAL OF ENERGY RESEARCH, 2022, 46 (09) : 12702 - 12721
  • [37] Theoretical research of the performance of a novel enhanced transcritical CO2 refrigeration cycle for power and cold generation
    Megdouli, K.
    Sahli, H.
    Tashtoush, B. M.
    Nahdi, E.
    Kairouani, L.
    [J]. ENERGY CONVERSION AND MANAGEMENT, 2019, 201
  • [38] Thermodynamic analysis of CO2 transcritical two-stage compression refrigeration cycle systems with expanders
    Liu S.
    Sun Z.
    Li H.
    Dai B.
    Chen Y.
    [J]. Sun, Zhili (sunzhili@tjcu.edu.cn), 1600, Taylor and Francis Asia Pacific (24): : 70 - 77
  • [39] An investigation into the thermodynamic improvement potential of a transcritical automotive CO2 refrigeration cycle
    Song, Xia
    Yu, Binbin
    Zhang, Yun
    Shi, Junye
    Chen, Jiangping
    [J]. APPLIED THERMAL ENGINEERING, 2022, 216
  • [40] PID control for a single-stage transcritical CO2 refrigeration cycle
    Salazar, M.
    Mendez, F.
    [J]. APPLIED THERMAL ENGINEERING, 2014, 67 (1-2) : 429 - 438