Measuring partial discharges in MV cables under DC voltage: procedures and results in steady state conditions

被引:0
|
作者
Naderiallaf, Hadi [1 ]
Cavallini, Andrea [1 ]
Esterl, Florian [2 ]
Plath, Ronald [2 ]
Seri, Paolo [1 ]
Montanari, Gian Carlo [3 ]
机构
[1] Univ Bologna, DEI, Bologna, Italy
[2] Tech Univ Berlin, Dept High Voltage Technol, Berlin, Germany
[3] Florida State Univ, CAPS, Tallahassee, FL 32306 USA
关键词
partial discharges; DC and AC measurements; partial discharge inception voltage; PDIV model;
D O I
10.1109/eic47619.2020.9158726
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
Starting from measurements performed on insulation models, estimation of partial discharge inception voltage, PDIV, and inference of the different behavior of PD for a MV cable models are presented and discussed. The estimations are validated through laboratory testing on a cable with an artificial defect. It is shown that PDIV under DC can become considerably higher or lower than that under AC, depending on temperature and material properties, which affect PD repetition rate as well. However, resorting to the model presented in this paper, measuring PD under AC will help to identify and validate the results of the PD DC measurements.
引用
收藏
页码:18 / 21
页数:4
相关论文
共 50 条
  • [11] Effect of Temperature on Main Partial Discharges Phenomena Under DC Voltage Stress
    Di Fatta, Alessio
    Imburgia, Antonino
    Rizzo, Giuseppe
    Akbar, Ghulam
    Li Vigni, Vincenzo
    Romano, Pietro
    Ala, Guido
    [J]. 2023 IEEE CONFERENCE ON ELECTRICAL INSULATION AND DIELECTRIC PHENOMENA, CEIDP, 2023,
  • [12] Feature extraction and ageing state recognition using partial discharges in cables under HVDC
    Morette, Nathalie
    Ditchi, Thierry
    Oussar, Yacine
    [J]. ELECTRIC POWER SYSTEMS RESEARCH, 2020, 178
  • [13] PARTIAL DISCHARGES IN GASEOUS CAVITIES IN SOLID DIELECTRICS UNDER IMPULSE VOLTAGE CONDITIONS
    DENSLEY, RJ
    SALVAGE, B
    [J]. IEEE TRANSACTIONS ON ELECTRICAL INSULATION, 1971, EI 6 (02): : 54 - &
  • [14] Impact of DC Voltage Enhancement on Partial Discharges in Medium Voltage Cables-An Empirical Study with Defects at Semicon-Dielectric Interface
    Shekhar, Aditya
    Feng, Xianyong
    Gattozzi, Angelo
    Hebner, Robert
    Wardell, Douglas
    Strank, Shannon
    Rodrigo-Mor, Armando
    Ramirez-Elizondo, Laura
    Bauer, Pavol
    [J]. ENERGIES, 2017, 10 (12)
  • [15] Research Prospects for Partial Discharge of High Voltage DC Cables Under Multi-physics
    Peng X.
    Chen Y.
    Jia S.
    Li M.
    Dong L.
    Wang H.
    [J]. Zhongguo Dianji Gongcheng Xuebao/Proceedings of the Chinese Society of Electrical Engineering, 2023, 43 (03): : 1210 - 1221
  • [16] Characterization of Partial Discharges in Solid Insulators under DC Voltage Using Physical Cavity Properties
    Morette, Nathalie
    Daassi-Gnaba, Hela
    Ditchi, Thierry
    Oussar, Yacine
    [J]. 2017 INTERNATIONAL SYMPOSIUM ON ELECTRICAL INSULATING MATERIALS (ISEIM), VOLS 1 & 2, 2017, : 374 - 377
  • [17] Effect of Cellulose Impurities on Partial Discharges in Oil-pressboard Insulation under DC Voltage
    Li, Yuan
    Zhang, Qiaogen
    Ding, Yuqin
    Zhao, Yi
    [J]. IEEE TRANSACTIONS ON DIELECTRICS AND ELECTRICAL INSULATION, 2017, 24 (04) : 2271 - 2273
  • [18] Simulation Analysis of Steady-state Ampacity of ±500 kV High-voltage DC Submarine Cables Under Different Laying Methods
    Qiao J.
    Zhao X.
    Xia Y.
    Feng Y.
    Xiao Y.
    Yang L.
    [J]. Gaodianya Jishu/High Voltage Engineering, 2023, 49 (02): : 597 - 607
  • [19] Comparative investigation on pulse shape parameters of partial discharges in air under AC and DC voltage stress
    Luehring, Ulrich
    Wienold, Daniel
    Jenau, Frank
    [J]. 2016 51ST INTERNATIONAL UNIVERSITIES POWER ENGINEERING CONFERENCE (UPEC), 2016,
  • [20] Degradation Characteristics of Oil-immersed Pressboard Samples Induced by Partial Discharges under DC Voltage
    Li, Yuan
    Zhang, Qiaogen
    Wang, Tonglei
    Li, Jinzhong
    Guo, Can
    Ni, Heli
    [J]. IEEE TRANSACTIONS ON DIELECTRICS AND ELECTRICAL INSULATION, 2017, 24 (02) : 1110 - 1117