A review of methods to evaluate borehole thermal resistances in geothermal heat-pump systems

被引:257
|
作者
Lamarche, Louis [1 ]
Kajl, Stanislaw [1 ]
Beauchamp, Benoit [1 ]
机构
[1] Ecole Technol Super, Montreal, PQ H3C 1K3, Canada
基金
加拿大自然科学与工程研究理事会;
关键词
Geothermal; Borehole resistance: Ground-source heat pump; Ground loop heat exchanger; Numerical solution; EXCHANGERS;
D O I
10.1016/j.geothermics.2010.03.003
中图分类号
TE [石油、天然气工业]; TK [能源与动力工程];
学科分类号
0807 ; 0820 ;
摘要
In the design of a ground-source heat pump (GSHP) system, the heat transfer from the fluid to the ground is influenced by the thermal borehole resistance between the fluid and the borehole surface and also by the interference resistance between the two (or four) pipes inside the borehole. Several authors have proposed empirical and theoretical relations to evaluate these resistances as well as methods to evaluate them experimentally. The paper compares the different approaches and proposes good practice to evaluate the resistances. The impact of the different approaches on the design of heat exchanger is also examined. Two-dimensional and fully three-dimensional numerical simulations are used to evaluate the different methods. A new method is also proposed to evaluate the borehole resistances from in situ tests. (C) 2010 Elsevier Ltd. All rights reserved.
引用
收藏
页码:187 / 200
页数:14
相关论文
共 50 条
  • [1] The importance of axial effects for borehole design of geothermal heat-pump systems
    Marcotte, D.
    Pasquier, P.
    Sheriff, F.
    Bernier, M.
    RENEWABLE ENERGY, 2010, 35 (04) : 763 - 770
  • [2] Modelling of Thermal Behavior of Borehole Heat Exchangers of Geothermal Heat Pump Heating Systems
    Gornov, V. F.
    Peskov, N. V.
    Vasilyev, G. P.
    Kolesova, M. V.
    2016 3RD INTERNATIONAL CONFERENCE ON MECHANICS AND MECHATRONICS RESEARCH (ICMMR 2016), 2016, 77
  • [3] Computer simulation of borehole ground heat exchangers for geothermal heat pump systems
    Lee, C. K.
    Lam, H. N.
    RENEWABLE ENERGY, 2008, 33 (06) : 1286 - 1296
  • [4] Heat transfer in a geothermal heat-pump system - an analytical assessment
    Yang, Y.
    Datcheva, M.
    Koenig, D.
    Schanz, T.
    GEOTECHNIQUE LETTERS, 2014, 4 : 139 - 144
  • [5] HEAT-PUMP AND HEAT PIPE SYSTEMS
    VOGELSANG, H
    METALL, 1982, 36 (01): : 85 - 88
  • [6] Effect of borehole array geometry and thermal interferences on geothermal heat pump system
    Kurevija, Tomislav
    Vulin, Domagoj
    Krapec, Vedrana
    ENERGY CONVERSION AND MANAGEMENT, 2012, 60 : 134 - 142
  • [8] HEAT-PUMP DESIGN WITH THERMAL STORAGE
    HAVELSKY, V
    MECARIK, K
    HEAT RECOVERY SYSTEMS & CHP, 1989, 9 (05): : 447 - 450
  • [9] TRANSIENT ANALYSIS OF HEAT-PUMP ASSISTED DISTILLATION SYSTEMS .1. THE HEAT-PUMP
    SALIM, MA
    SADASIVAM, M
    BALAKRISHNAN, AR
    INTERNATIONAL JOURNAL OF ENERGY RESEARCH, 1991, 15 (02) : 123 - 135
  • [10] Multipole method to calculate borehole thermal resistances in a borehole heat exchanger
    Claesson, Johan