Comparison of control strategies for shunt active power filters in three-phase four-wire systems

被引:389
|
作者
Milanes Montero, Maria Isabel [1 ]
Romero Cadaval, Enrique [1 ]
Barrero Gonzalez, Fermin [1 ]
机构
[1] Univ Extremadura, Dept Elect & Electromech Engn, Badajoz 639798, Spain
关键词
active filtering; i(d) - i(q) method; perfect harmonic cancellation method; p-q theory; reference current extraction; unity power factor method (UPF);
D O I
10.1109/TPEL.2006.886616
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
Strategies for extracting the three-phase reference currents for shunt active power filters are compared, evaluating their performance under different source and load conditions with the new IEEE Standard 1459 power definitions. The study was applied to a three-phase four-wire system in order to include imbalance. Under balanced and sinusoidal voltages, harmonic cancellation and reactive power compensation can be attained in all the methods. However, when the voltages are distorted and/or unbalanced, the compensation capabilities are not equivalent, with some strategies unable to yield an adequate solution when the mains voltages are not ideal. Simulation and experimental results are included.
引用
收藏
页码:229 / 236
页数:8
相关论文
共 50 条
  • [1] Comparison of Control Strategies for Active Power Filter in Three-phase Four-Wire Systems
    Ma, Hao
    Cai, Zheng
    IECON 2004: 30TH ANNUAL CONFERENCE OF IEEE INDUSTRIAL ELECTRONICS SOCIETY, VOL 2, 2004, : 1429 - 1434
  • [2] Three-phase four-wire shunt active filter control strategies
    Aredes, M
    Hafner, J
    Heumann, K
    IEEE TRANSACTIONS ON POWER ELECTRONICS, 1997, 12 (02) : 311 - 318
  • [3] Power quality improvement in three-phase four-wire systems using shunt active filters
    Esfandiari, A
    Parniani, M
    Mokhtari, H
    2004 IEEE 9th International Power Electronics Congress, Technical Proceedings, 2004, : 193 - 197
  • [4] Field Results on Developed Three-Phase Four-Wire Shunt Active Power Filters
    Pinto, J. G.
    Neves, Pedro
    Goncalves, D.
    Afonso, Joao L.
    IECON: 2009 35TH ANNUAL CONFERENCE OF IEEE INDUSTRIAL ELECTRONICS, VOLS 1-6, 2009, : 440 - +
  • [5] Current control schemes for three-phase four-wire shunt active power filters: a comparative study
    Petit Suarez, Johann
    Amaris, Hortensia
    Robles, Guillermo
    REVISTA FACULTAD DE INGENIERIA-UNIVERSIDAD DE ANTIOQUIA, 2010, (52): : 206 - 214
  • [6] Energy control of three-phase four-wire shunt active power filter
    Rodríguez, P
    Pindado, R
    Pou, J
    IECON'03: THE 29TH ANNUAL CONFERENCE OF THE IEEE INDUSTRIAL ELECTRONICS SOCIETY, VOLS 1 - 3, PROCEEDINGS, 2003, : 1061 - 1066
  • [7] Adaptive Backstepping Control of Three-Phase Four-Wire Shunt Active Power Filters for Energy Quality improvement
    Ait Chihab A.
    Ouadi H.
    Giri F.
    El Majdoub K.
    Journal of Control, Automation and Electrical Systems, 2016, 27 (2) : 144 - 156
  • [8] The Study of Three-Phase Four-Wire Shunt Active Power Filter
    Huang, Hai-hong
    Xu, Ruo-bing
    Wang, Hai-xin
    PROCEEDINGS 2013 INTERNATIONAL CONFERENCE ON MECHATRONIC SCIENCES, ELECTRIC ENGINEERING AND COMPUTER (MEC), 2013, : 3496 - 3499
  • [9] Simulation of three-phase four-wire shunt active power filter
    Wang, Ji-Dong
    Tianjin Daxue Xuebao (Ziran Kexue yu Gongcheng Jishu Ban)/Journal of Tianjin University Science and Technology, 2007, 40 (SUPPL.): : 95 - 99
  • [10] Simulation of Three-phase Four-wire Shunt Active Power Filter
    Wang, Jidong
    2009 ASIA-PACIFIC POWER AND ENERGY ENGINEERING CONFERENCE (APPEEC), VOLS 1-7, 2009, : 1702 - 1705