Buoyancy Driven Natural Ventilation through Horizontal Openings

被引:0
|
作者
Heiselberg, Per [1 ]
Li, Zhigang [2 ]
机构
[1] Univ Aalborg, Dept Civil Engn, Div Architectural Engn, Aalborg, Denmark
[2] Danfoss AS, Nordborg, Denmark
关键词
natural ventilation; airflow rate; buoyancy; horizontal opening; tracer gas; LES; EXCHANGE FLOW;
D O I
暂无
中图分类号
TU [建筑科学];
学科分类号
0813 ;
摘要
An experimental study of the phenomenon of buoyancy driven natural ventilation through single-sided horizontal openings was performed in a full-scale laboratory test rig. The measurements were made for opening ratios L/D ranging from 0.027 to 4.455, where L and D are the length of the opening and the diameter of the opening, respectively. The basic nature of airflow through single-sided openings, including airflow rate, air velocity, temperature difference between the rooms and the dimensions of the horizontal openings, were measured. A bi-directional airflow rate was measured using the constant injection tracer gas technique. Smoke visualizations showed that the airflow patterns are highly transient and unstable, and that the airflow rate oscillates with time. Correlations between the Froude (Archimedes) number Fr (Ar) and the L/D ratio are presented. In some cases the measured airflow rates fit quite well with the Epstein's formula but in other cases the measured data show clear deviations from the Epstein's formula. Thus, revised formulas for natural ventilation are proposed.
引用
收藏
页码:219 / 231
页数:13
相关论文
共 50 条
  • [1] Characteristics of buoyancy driven single-sided natural ventilation through horizontal openings
    Li, ZG
    Heiselberg, P
    Nielsen, PV
    BUILT ENVIRONMENT AND PUBLIC HEALTH, PROCEEDINGS, 2004, : 288 - 294
  • [2] Buoyancy-driven natural ventilation of a room with large openings
    Li, Rong
    Pitts, Adrian
    Li, Yuguo
    BUILDING SIMULATION 2007, VOLS 1-3, PROCEEDINGS, 2007, : 984 - +
  • [3] Influence of Horizontal Openings on Buoyancy-driven Natural Ventilation of an Atrium in High-rise Residential Buildings
    Li, Jing
    Li, Nianping
    Li, Chuawang
    Zhang, Minhui
    Hou, Sujuan
    He, Dongyue
    6TH INTERNATIONAL SYMPOSIUM ON HEATING, VENTILATING AND AIR CONDITIONING, VOLS I-III, PROCEEDINGS, 2009, : 1224 - 1231
  • [4] Analytical solutions for buoyancy-driven natural ventilation in buildings with three openings
    Leung, H
    Li, YG
    PROCEEDINGS OF THE 4TH INTERNATIONAL CONFERENCE ON INDOOR AIR QUALITY, VENTILATION AND ENERGY CONSERVATION IN BUILDINGS, VOLS I-III, 2001, : 857 - 864
  • [5] BUOYANCY-DRIVEN EXCHANGE FLOW THROUGH SMALL OPENINGS IN HORIZONTAL PARTITIONS
    EPSTEIN, M
    JOURNAL OF HEAT TRANSFER-TRANSACTIONS OF THE ASME, 1988, 110 (4A): : 885 - 893
  • [6] Buoyancy-driven exchange flow through small openings in horizontal partitions
    Epstein, M.
    Journal of Heat Transfer, 1988, 110 (04): : 885 - 893
  • [7] Buoyancy-driven single-sided natural ventilation in buildings with large openings
    Jiang, Y
    Chen, QY
    INTERNATIONAL JOURNAL OF HEAT AND MASS TRANSFER, 2003, 46 (06) : 973 - 988
  • [8] Characteristics of buoyancy-driven interzonal airflow via horizontal openings
    Riffat, S.B.
    Shao, L.
    Building Services Engineering Research and Technology, 1995, 16 (03): : 149 - 152
  • [9] Buoyancy-driven displacement natural ventilation in a single-zone building with three-level openings
    Chen, ZD
    Li, YG
    BUILDING AND ENVIRONMENT, 2002, 37 (03) : 295 - 303
  • [10] Survey of buildings with natural ventilation and basic analysis of buoyancy driven ventilation
    Shimonosono K.