Multivariate diagnosis analysis for chiller system for improving energy performance

被引:8
|
作者
Yu, F. W. [1 ]
Ho, W. T. [1 ]
机构
[1] Hong Kong Polytech Univ, Hong Kong Community Coll, 8 Hung Lok Rd, Hong Kong, Hong Kong, Peoples R China
关键词
Coefficient of performance; Cooling tower; Operating status diagnosis; Survival analysis; Water-cooled chiller; STRATEGY; MODELS;
D O I
10.1016/j.jobe.2018.07.012
中图分类号
TU [建筑科学];
学科分类号
0813 ;
摘要
The operating status of a large chiller system in buildings with central air-conditioning could vary at a given cooling demand and ambient condition. This study investigates the potential change of operating statuses and its influence on the system coefficient of performance (COP)-cooling energy output divided by the total electric power input. The system studied comprised four large and one small chillers. A set of primary chilled water pumps operated in different numbers to deliver the required flow rate of chilled water to the operating chillers. The actual flow rate to meet the building cooling demand was regulated by the secondary chilled water pumps. A set of evaporative cooling towers was installed to match the heat rejection required for the chillers. Comprehensive operating data were collected at 15-min intervals in 8 months. 18.46% of the total operating conditions were transitional statuses and unconventional operating statuses by switching on or off one extra cooling tower. This led to a 33.9-64.9% drop in individual system COPs. An examination of the variation of system load ratios and ambient wet bulb temperatures showed that the system COP was higher at the pair-up operation of system components even at higher wet bulb temperatures. A survival analysis indicated that the transitional statuses depended mainly on the temperature of chilled water returning to the evaporators and the temperatures of cooling water entering and leaving the condensers. Minimizing unnecessary transitional statuses and restoring the pair-up operation of system components could save electricity by 2.72%.
引用
收藏
页码:317 / 326
页数:10
相关论文
共 50 条
  • [41] Dynamic performance analysis of a solar driving absorption chiller integrated with absorption thermal energy storage
    Liu, Meng
    Cheng, Youliang
    Cheng, Weiliang
    Zhan, Chenglin
    ENERGY CONVERSION AND MANAGEMENT, 2021, 247
  • [42] Performance Augmentation of a Water Chiller System Using Nanofluids
    Liu, M. S.
    Hu, R.
    Lin, M. C. C.
    Wang, C. C.
    Liaw, J. S.
    ASHRAE TRANSACTIONS 2009, VOL 115, PT 1, 2009, 115 : 581 - 586
  • [43] Quick design analysis for improving building energy performance
    Brown, N.
    Ubbelohde, M. S.
    Loisos, G.
    Philip, S.
    2013 ISES SOLAR WORLD CONGRESS, 2014, 57 : 3041 - 3050
  • [44] Quick design analysis for improving building energy performance
    Brown, N.
    Ubbelohde, M. S.
    Loisos, G.
    Philip, S.
    2013 ISES SOLAR WORLD CONGRESS, 2014, 57 : 1868 - 1877
  • [45] Algorithmically Generated Chiller Performance Curves for Building Energy Simulation
    Lerond, Jeremy
    ASHRAE TRANSACTIONS 2019, VOL 125, PT 2, 2019, 125 : 93 - 95
  • [46] Feasibility energy performance simulation of DHC system with gas engine driven chiller by using lcem tool
    Chubu University, Kasugai-City, Aichi Pref, Japan
    不详
    Proc. Build. Simu. 2011: 12 conf. Inter. Build. Perf. Simu. Assoc., (2186-2193):
  • [47] Energy and, exergy analysis of a CCHP-ORC system based on MGT - ORC and absorption chiller
    Lei, Huan
    Yang, Jinfu
    Tang, Changliang
    Han, Dongjiang
    ENVIRONMENTAL PROGRESS & SUSTAINABLE ENERGY, 2018, 37 (04) : 1513 - 1522
  • [48] Exergy and energy analysis of a double evaporating temperature chiller
    Zhang, Kai
    Zhu, Yutong
    Liu, Jinxiang
    Niu, Xiaofeng
    Yuan, Xiaolei
    ENERGY AND BUILDINGS, 2018, 165 : 464 - 471
  • [49] Energy management of chiller systems by data envelopment analysis
    Yu, Fu Wing
    Chan, Kwok Tai
    FACILITIES, 2013, 31 (3-4) : 106 - 118
  • [50] Energy and exergy analysis of solar heat driven chiller under wide system boundary conditions
    Petela, Karolina
    Szlek, Andrzej
    ENERGY, 2019, 168 : 440 - 449