Corrosion Rate Simulation and Influence Factors of a Vertical DC Grounding Electrode

被引:10
|
作者
Tong, Xuefang [1 ,2 ]
Zheng, Zhihui [3 ]
Tan, Bo [1 ,2 ]
Lu, Hailiang [3 ]
Lan, Lei [3 ]
Wen, Xishan [3 ]
机构
[1] State Key Lab Power Grid Environm Protect, Wuhan 430074, Hubei, Peoples R China
[2] China Elect Power Res Inst, Wuhan 430074, Hubei, Peoples R China
[3] Wuhan Univ, Sch Elect Engn, Wuhan 430072, Hubei, Peoples R China
来源
IEEE ACCESS | 2018年 / 6卷
关键词
Grounding electrode; corrosion; soil parameters; ground current; GALVANIC CORROSION; MILD-STEEL; CONCRETE;
D O I
10.1109/ACCESS.2018.2873080
中图分类号
TP [自动化技术、计算机技术];
学科分类号
0812 ;
摘要
Corrosion affects the performance of grounding electrode materials buried in soil and threatens the safe operation of power systems. Natural corrosion of grounding electrode materials occurs over a long time and involves many influencing factors. Simulating the true corrosion environment of grounding electrode materials, exploring the corrosion mechanism, and accurately determining the corrosion condition of these materials are problems that must be solved urgently. In this paper, a corrosion simulation model of a vertical carbon steel grounding electrode was built based on the principle of electrochemical corrosion. The influence of soil parameters (oxygen concentration, pH value, and chloride ion concentration) on the corrosion characteristics of the grounding electrode was calculated. The corrosion rates of the vertical grounding electrode at different burial depths were compared with and without direct current. Simulation results showed that the corrosion rate of the grounding electrode changed linearly with oxygen concentration in the soil, changed negatively and exponentially with pH, and changed logarithmically with chloride ion concentration. Grounding electrode materials should be buried at a depth of 2 m when the time with no current in the grounding electrode is more than that with current. This burial depth can effectively reduce the influence of oxygen concentration on grounding corrosion. Moreover, the local reduction in hydrogen ion content must be considered during the construction of a grounding electrode to ensure that the grounding electrode surface is in a strong alkaline environment, which can passivate the grounding electrode and reduce the corrosion rate.
引用
收藏
页码:57230 / 57238
页数:9
相关论文
共 50 条
  • [41] The Influence of Ultra HVDC Grounding Electrode on the High-speed Railway Bridges Grounding System
    Li, Chenkun
    Zhang, Huazhi
    Huang, Jun
    Zhang, Bo
    Song, Wei
    Journal of Railway Engineering Society, 2021, 38 (10) : 90 - 94
  • [42] Influence of soil temperature characteristic on the grounding electrode temperature rise
    Sima, Wenxia
    Zhu, Bin
    Yuan, Tao
    Yang, Qing
    Luo, Ling
    Wu, Peng
    IET SCIENCE MEASUREMENT & TECHNOLOGY, 2015, 9 (04) : 410 - 417
  • [43] Influence of coke bed on HVDC grounding electrode heat dissipation
    Chen, Fan
    Zhang, Bo
    He, Jinliang
    IEEE TRANSACTIONS ON MAGNETICS, 2008, 44 (06) : 826 - 829
  • [44] Influence of grounding conductor in cable duct on the corrosion diagnosis in the substation
    Liu, Yugen
    Cheng, Wenjie
    Gaodianya Jishu/High Voltage Engineering, 2014, 40 (02): : 505 - 512
  • [45] Influence of Current on Soil Corrosion of Galvanized Steel of Grounding Grids
    Song, Linbo
    Zhang, Cheng
    Zhao, Jing
    Yang, Rui
    Yuan, Yuan
    MICROMACHINES, 2022, 13 (02)
  • [46] FDTD Surge Simulation of a Vertical Grounding Rod Considering Soil Ionization
    Zhang, Fan
    Tanaka, Hiroki
    Baba, Yoshihiro
    Nagaoka, Naoto
    2016 ASIA-PACIFIC INTERNATIONAL SYMPOSIUM ON ELECTROMAGNETIC COMPATIBILITY (APEMC), 2016, : 260 - 262
  • [47] FDTD simulation of a horizontal grounding electrode and modeling of its equivalent circuit
    Tsumura, Masanobu
    Baba, Yoshihiro
    Nagaoka, Naoto
    Ametani, Akihiro
    IEEE TRANSACTIONS ON ELECTROMAGNETIC COMPATIBILITY, 2006, 48 (04) : 817 - 825
  • [48] Influence of humidity on corrosion rate
    White, B.S.
    Corrosion Prevention and Control, 1992, 39 (06): : 154 - 156
  • [49] AN EXPERIMENTAL INVESTIGATION ON CORROSION RATE OF Mg ELECTRODE USING AN EQCN AND IMPROVEMENT IN ANTI CORROSION RATE OF Mg ELECTRODE BY SURFACE COATING
    Lee, D. H.
    Park, C. H.
    Kim, C. C. S.
    DIGEST JOURNAL OF NANOMATERIALS AND BIOSTRUCTURES, 2014, 9 (03) : 1171 - 1178
  • [50] Influence of water quality factors on stability index of water and corrosion rate of steel
    Yuasa, Makoto
    Sakai, Yuusuke
    Sekine, Isao
    Momozawa, Nobuyuki
    Wake, Toshiharu
    Murata, Hiromichi
    Shibata, Yoshiaki
    Someya, Shintarou
    Zairyo to Kankyo/ Corrosion Engineering, 2000, 49 (09): : 568 - 571