Corrosion Rate Simulation and Influence Factors of a Vertical DC Grounding Electrode

被引:10
|
作者
Tong, Xuefang [1 ,2 ]
Zheng, Zhihui [3 ]
Tan, Bo [1 ,2 ]
Lu, Hailiang [3 ]
Lan, Lei [3 ]
Wen, Xishan [3 ]
机构
[1] State Key Lab Power Grid Environm Protect, Wuhan 430074, Hubei, Peoples R China
[2] China Elect Power Res Inst, Wuhan 430074, Hubei, Peoples R China
[3] Wuhan Univ, Sch Elect Engn, Wuhan 430072, Hubei, Peoples R China
来源
IEEE ACCESS | 2018年 / 6卷
关键词
Grounding electrode; corrosion; soil parameters; ground current; GALVANIC CORROSION; MILD-STEEL; CONCRETE;
D O I
10.1109/ACCESS.2018.2873080
中图分类号
TP [自动化技术、计算机技术];
学科分类号
0812 ;
摘要
Corrosion affects the performance of grounding electrode materials buried in soil and threatens the safe operation of power systems. Natural corrosion of grounding electrode materials occurs over a long time and involves many influencing factors. Simulating the true corrosion environment of grounding electrode materials, exploring the corrosion mechanism, and accurately determining the corrosion condition of these materials are problems that must be solved urgently. In this paper, a corrosion simulation model of a vertical carbon steel grounding electrode was built based on the principle of electrochemical corrosion. The influence of soil parameters (oxygen concentration, pH value, and chloride ion concentration) on the corrosion characteristics of the grounding electrode was calculated. The corrosion rates of the vertical grounding electrode at different burial depths were compared with and without direct current. Simulation results showed that the corrosion rate of the grounding electrode changed linearly with oxygen concentration in the soil, changed negatively and exponentially with pH, and changed logarithmically with chloride ion concentration. Grounding electrode materials should be buried at a depth of 2 m when the time with no current in the grounding electrode is more than that with current. This burial depth can effectively reduce the influence of oxygen concentration on grounding corrosion. Moreover, the local reduction in hydrogen ion content must be considered during the construction of a grounding electrode to ensure that the grounding electrode surface is in a strong alkaline environment, which can passivate the grounding electrode and reduce the corrosion rate.
引用
收藏
页码:57230 / 57238
页数:9
相关论文
共 50 条
  • [1] Research on the Influence of DC Current Overflowing on Grounding Electrode Corrosion
    Liu, Guohua
    Jiang, Ganzhi
    Zhang, Zhanlong
    Mei, Daojun
    Zheng, Yan
    2017 IEEE 3RD INFORMATION TECHNOLOGY AND MECHATRONICS ENGINEERING CONFERENCE (ITOEC), 2017, : 291 - 295
  • [2] Simulation of Impact of Vertical Grounding Electrode on Impulse Grounding Resistance of Substation Grounding Network
    Zhou, Lijun
    He, Jian
    Xu, Han
    Wang, Pengcheng
    Chen, Ying
    Chen, Sixiang
    2017 2ND IEEE INTERNATIONAL CONFERENCE ON INTEGRATED CIRCUITS AND MICROSYSTEMS (ICICM), 2017, : 18 - 22
  • [3] Research on the influence of ac current overflowing on grounding electrode corrosion
    Liu, Guohua
    Wu, Zhen
    Li, Wei
    Zhang, Zhanlong
    Mei, Daojun
    2017 2ND INTERNATIONAL SEMINAR ON ADVANCES IN MATERIALS SCIENCE AND ENGINEERING, 2017, 231
  • [4] Effect of DC grounding electrode currents on the corrosion interference behavior of cathodic protection of nearby pipelines
    Chen, Xiao
    Li, Lin
    Zhang, Boyang
    Li, Hengfeng
    Zhao, Lunuo
    Zhou, Yixi
    Wu, Weiting
    MEASUREMENT SCIENCE AND TECHNOLOGY, 2024, 35 (02)
  • [5] A method for grounding resistance calculation of vertical electrode
    Kwon, Hyeyong
    Kil, Yongmin
    Kim, Sunghyok
    ELECTRIC POWER SYSTEMS RESEARCH, 2023, 224
  • [6] Research on Scope of Environmental Influence of DC Grounding Electrode Rated ±800kV
    Cui, Mingde
    Chu, Youqun
    Liu, Lianguang
    2010 ASIA-PACIFIC POWER AND ENERGY ENGINEERING CONFERENCE (APPEEC), 2010,
  • [7] Potential numerical simulation and analysis of influencing factors of toroidal HVDC grounding electrode
    Fu Z.
    Tan H.
    Liu H.
    Guo C.
    Zhu Z.
    1909, Power System Technology Press (40): : 1909 - 1915
  • [8] A Simulation Study of the Direct Current Corrosion Characteristics of Carbon Steel Grounding Electrode With Ground Lead
    Zhang, Zhanlong
    Gao, Pan
    Dan, Yihua
    Liu, Guohua
    Xiang, Rui
    Zou, Jing
    INTERNATIONAL JOURNAL OF ELECTROCHEMICAL SCIENCE, 2018, 13 (12): : 11974 - 11985
  • [9] ELECTRICAL AND THERMAL MEASUREMENTS FOR DC GROUNDING ELECTRODE DESIGN
    ZURFLUEH, EG
    BASKIN, DA
    GEOPHYSICS, 1979, 44 (03) : 362 - 363
  • [10] Analysis the influence of corrosion layer on the grounding performance of grounding electrodes
    Zhang, Zhanlong
    Zou, Jing
    Dan, Yihua
    Ye, Huarui
    Li, Yiqiao
    Deng, Jun
    IET GENERATION TRANSMISSION & DISTRIBUTION, 2020, 14 (13) : 2602 - 2609