An Unsynchronized Measurements Correction Method for Two-Terminal Fault-Location Problems

被引:24
|
作者
Yu, Chi-Shan [1 ]
机构
[1] Natl Taipei Univ Technol, Dept Elect Engn, Taipei, Taiwan
关键词
Fault location; synchronization angle; synchronization index; unsynchronized measurements; TRANSMISSION-LINES; COMPENSATION; VOLTAGE;
D O I
10.1109/TPWRD.2009.2037631
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
This paper presents a method to correct the unsynchronized measurements for two-terminal fault-location problems. First, a synchronization index is defined to check whether the measurements are synchronized. A modified secant method-based algorithm is then developed to obtain a synchronization angle and correct the unsynchronized measurements. When the unsynchronized measurements are corrected, the fault location can be simultaneously obtained from the intermediate result of the proposed computation. Thus, although the proposed method is developed to correct the unsynchronized measurements, the fault-location problem can also be solved. Compared with the previous works, the proposed iteration equation is simpler. The MATLAB/SIMULINK simulator is used to evaluate the effectiveness of the proposed method.
引用
收藏
页码:1325 / 1333
页数:9
相关论文
共 50 条
  • [1] An iterative two-terminal fault-location method based on unsynchronized phasors
    Dalcastagne, Andre Luis
    Noceti Filho, Sidnei
    Zuern, Hans Helmut
    Seara, Rui
    [J]. IEEE TRANSACTIONS ON POWER DELIVERY, 2008, 23 (04) : 2318 - 2329
  • [2] New Fault Impedance Computations for Unsynchronized Two-Terminal Fault-Location Computations
    Yu, Chi-Shan
    Chang, Li-Ren
    Cho, Jr-Ru
    [J]. IEEE TRANSACTIONS ON POWER DELIVERY, 2011, 26 (04) : 2879 - 2881
  • [3] Unsynchronized two-terminal fault location estimation
    Novosel, D
    Hart, DG
    Udren, E
    Garitty, J
    [J]. IEEE TRANSACTIONS ON POWER DELIVERY, 1996, 11 (01) : 130 - 138
  • [4] A novel method for fault location based on two-terminal unsynchronized data
    Li, Xun
    Gong, Qingwu
    Ming, Ruiqing
    [J]. 2010 ASIA-PACIFIC POWER AND ENERGY ENGINEERING CONFERENCE (APPEEC), 2010,
  • [5] A two-terminal fault location approach based on unsynchronized phasors
    Dalcastagne, Andre Luis
    Noceti Filho, Sidnei
    Zurn, Hans Helmut
    Seara, Rui
    [J]. 2006 INTERNATIONAL CONFERENCE ON POWER SYSTEMS TECHNOLOGY: POWERCON, VOLS 1- 6, 2006, : 2624 - 2630
  • [6] Unsynchronized fault-location technique for two- and three-terminal transmission lines
    Elsadd, Mahmoud A.
    Abdelaziz, Almoataz Y.
    [J]. ELECTRIC POWER SYSTEMS RESEARCH, 2018, 158 : 228 - 239
  • [7] Accurate Noniterative Fault-Location Algorithm Utilizing Two-End Unsynchronized Measurements
    Izykowski, Jan
    Rosolowski, Eugeniusz
    Balcerek, Przemyslaw
    Fulczyk, Marek
    Saha, Murari Mohan
    [J]. IEEE TRANSACTIONS ON POWER DELIVERY, 2011, 26 (02) : 547 - 555
  • [8] A Novel Fault-location Method for HVDC Transmission Lines Based on the Ratio of Two-terminal Traveling Wave Frequency Difference
    Shu H.
    Yang J.
    Zhang G.
    [J]. Zhongguo Dianji Gongcheng Xuebao/Proceedings of the Chinese Society of Electrical Engineering, 2022, 42 (18): : 6715 - 6726
  • [9] Unsynchronised two-terminal transmission-line fault-location without using line parameters
    Liao, Y.
    Elangovan, S.
    [J]. IEE PROCEEDINGS-GENERATION TRANSMISSION AND DISTRIBUTION, 2006, 153 (06) : 639 - 643
  • [10] Unsynchronized Fault-Location Scheme for Nonlinear HIF in Transmission Lines
    Ibrahim, Doaa Khalil
    Eldin, El Sayed Tag
    Abou El-Zahab, Essam El-Din
    Saleh, Saber Mohamed
    [J]. IEEE TRANSACTIONS ON POWER DELIVERY, 2010, 25 (02) : 631 - 637