Boost multi-level NPC-fed VS large rated asynchronous pumped storage hydro-generating unit

被引:4
|
作者
Joseph, Anto [1 ]
Kim, Seok-Min [2 ]
Sing Lee, Sze [3 ]
Dominic, Arun [4 ]
Lee, Kyo-Beum [2 ]
机构
[1] Univ Calif Irvine, Dept Elect Engn & Comp Sci, Irvine, CA 92717 USA
[2] Ajou Univ, Power Elect Lab, Suwon, South Korea
[3] Univ Southampton Malaysia, Dept Elect & Comp Sci, Johor Baharu, Malaysia
[4] Natl Inst Technol Warangal, Elect Engn Dept, Warangal, Andhra Pradesh, India
关键词
switching convertors; rotors; voltage control; asynchronous machines; harmonic distortion; machine control; pumped-storage power stations; reactive power control; voltage-source convertors; pumping modes; mode changeover time; output voltage levels; boost NPC converter topology; converter redundancy; asynchronous VS-PSP units; 250 MW DFIM hydro-generating unit; boost multilevel NPC-fed VS large rated asynchronous pumped storage hydro-generating unit; boost multilevel converter; doubly fed induction machine; voltage-source converters; three-level NPC; DC-link voltage; variable-speed pumped storage plants; rotor side; active powers; reactive powers; boost neutral point clamped converter topology; 3L-NPC system; speed variation; switching losses; conduction losses; total harmonic distortion; power; 250; 0; MW; SPEED; POWER; CHALLENGES; CONVERTER; ENERGY; TRENDS;
D O I
10.1049/iet-epa.2018.5851
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
The authors intent using a boost multi-level converter for the doubly fed induction machine (DFIM) used in variable-speed pumped storage plants (VS-PSP). Voltage-source converters connected on the rotor side of the machine control the active and reactive powers of the unit. The proposed boost neutral point clamped (NPC) converter topology provides a voltage output two times larger than a conventional three-level NPC (3L-NPC) with similar DC-link voltage and equal number of switches. Hence, it increases the speed variation of the unit, which improves the efficiency during generation and pumping modes. Moreover, it reduces the starting period of the unit at the pumping mode, which is significant during mode changeover time. Furthermore, it reduces switching and conduction losses in the converter. It also reduces the total harmonic distortion in the output current, as it provides five output voltage levels. These improvements show that the boost NPC converter topology is better among VS-PSP project authorities. In addition, the reliability of the proposed topology is investigated, where converter redundancy is a challenging issue in asynchronous VS-PSP units. The proposed boost NPC was compared with the conventional 3L-NPC system by examining a 250 MW DFIM hydro-generating unit.
引用
收藏
页码:1488 / 1496
页数:9
相关论文
共 9 条
  • [1] Two-Stage Protection for Multi-Channel Power Electronic Converters Fed Large Asynchronous Hydro-Generating Unit
    Semwal, R. R.
    Joseph, Anto
    Chelliah, Thanga Raj
    2018 INTERNATIONAL POWER ELECTRONICS CONFERENCE (IPEC-NIIGATA 2018 -ECCE ASIA), 2018, : 1358 - 1363
  • [2] Fault Tolerant Schemes for Multi-Channel 3L-NPC Bi-directional PWM Power Converter Fed Asynchronous Hydro-Generating Unit
    Selvaraj, Raghu
    Desingu, Karthik
    Chelliah, Thanga Raj
    2021 THIRTY-SIXTH ANNUAL IEEE APPLIED POWER ELECTRONICS CONFERENCE AND EXPOSITION (APEC 2021), 2021, : 2626 - 2631
  • [3] Fault Diagnosis and Tolerant Operation of Multi-Channel 3L-NPC Power Converter Fed Adjustable Speed Hydro-Generating Unit
    Selvaraj, Raghu
    Desingu, Karthik
    Chelliah, Thanga Raj
    2020 IEEE INDUSTRY APPLICATIONS SOCIETY ANNUAL MEETING, 2020,
  • [4] Fault-Tolerant and Reconfiguration Control for Boost Multi-level NPC Converter Fed Doubly Fed Induction Machines
    Joseph, Anto
    Bak, Yeongsu
    Lee, Sze Sing
    Lee, Kyo-Beum
    2019 10TH INTERNATIONAL CONFERENCE ON POWER ELECTRONICS AND ECCE ASIA (ICPE 2019 - ECCE ASIA), 2019, : 2466 - 2472
  • [5] Improved start-up strategy for a doubly fed induction machine fed large rated variable speed pumped storage unit in pumping mode operation
    N. Malathy
    Y. Sukhi
    Electrical Engineering, 2024, 106 : 615 - 629
  • [6] Improved start-up strategy for a doubly fed induction machine fed large rated variable speed pumped storage unit in pumping mode operation
    Malathy, N.
    Sukhi, Y.
    ELECTRICAL ENGINEERING, 2024, 106 (01) : 615 - 629
  • [7] Innovative Energy Sustainable Solutions for Urban Infrastructure: Implementing Micro-Pumped Hydro Storage in Singapore's Multi-Level Carparks
    Kok, Chiang Liang
    Ho, Chee Kit
    Koh, Yit Yan
    Tay, Wan Xuan
    Teo, Tee Hui
    APPLIED SCIENCES-BASEL, 2024, 14 (17):
  • [8] Rotor short-circuited start-up strategy for a doubly fed induction machine-fed large-rated variable-speed pumped storage unit operating in pumping mode
    Narayanasamy, Malathy
    Sukhi, Y.
    JOURNAL OF POWER ELECTRONICS, 2023, 23 (11) : 1733 - 1744
  • [9] Rotor short-circuited start-up strategy for a doubly fed induction machine-fed large-rated variable-speed pumped storage unit operating in pumping mode
    Malathy Narayanasamy
    Y. Sukhi
    Journal of Power Electronics, 2023, 23 : 1733 - 1744