Sick building syndrome - A case study in a multistory centrally air-conditioned building in the Delhi City

被引:55
|
作者
Gupta, Sanjeev
Khare, Mukesh [1 ]
Goyal, Radha
机构
[1] CEA, DEN, DANS,DM2S, SFME,LTMF, F-91191 Gif Sur Yvette, France
[2] Univ W Indies, St Augustine, Trinidad Tobago
[3] Indian Inst Technol, Dept Civil Engn, New Delhi 110016, India
关键词
SBS; indoor air pollution; air-conditioned building; SBS score;
D O I
10.1016/j.buildenv.2006.10.013
中图分类号
TU [建筑科学];
学科分类号
0813 ;
摘要
Recently, airtight envelope system has become popular in the design of office buildings to reduce heating and cooling loads. Maintaining allowable indoor air quality (IAQ) for such airtight buildings totally depends on mechanical ventilation systems. Subsequently, poor operation of the ventilation system in such office buildings causes ineffective removal of polluted indoor air, and displays a sign of "sick building syndrome" (SBS). User's perception is an important parameter for evaluating IAQ. A questionnaire study was carried out to investigate the prevalence of the SBS at a multistory centrally air-conditioned Airport Authority of India (AAI) building in the New Delhi city. Quantification of the perceptions of the users regarding IAQ was done by converting their responses to a SBS score. The quantified answers were then subjected to statistical analysis. Qualitative analysis of the questionnaire was carried out to evaluate relationships between SBS score and carbon dioxide (CO,) and other parameters related to building and work environment. Quantitative analysis of IAQ was also conducted by monitoring indoor concentrations of four pollutants, namely, nitrogen dioxide (NO,), sulphur dioxide (SO,), suspended particulate matter (SPM) and carbon monoxide (CO). Concentrations of pollutants were complying with IAQ standards as given by ASHRAE and WHO. The SBS was higher on the third floor as compared to other floors and the control tower. The main symptoms prevailing were headache (51%), lethargy (50%), and dryness in body mucous (33%). The third floor and the control tower were affected by infiltration, mainly from entrance doors. A direct relation between the average SBS score and CO2 concentration was found, i.e., the average SBS score increased with CO2 concentration and vice versa, clearly signifying the usefulness of SBS score in IAQ. (c) 2006 Elsevier Ltd. All rights reserved.
引用
收藏
页码:2797 / 2809
页数:13
相关论文
共 50 条
  • [1] Sick building syndrome in air-conditioned museum
    Ali, Azlan Shah
    Chua, Shirley Jin Lin
    Bin Umar, Mohd Azlan
    [J]. MUSEUM MANAGEMENT AND CURATORSHIP, 2023,
  • [2] HIGH PREVALENCE OF SICK BUILDING SYNDROME IN A NEW AIR-CONDITIONED BUILDING IN ITALY
    ABBRITTI, G
    MUZI, G
    ACCATTOLI, MP
    FIORDI, T
    DELLOMO, M
    COLANGELI, C
    GABRIELLI, AR
    FABBRI, T
    DALESSANDRO, A
    [J]. ARCHIVES OF ENVIRONMENTAL HEALTH, 1992, 47 (01): : 16 - 22
  • [3] Hybrid Ventilation in an Air-Conditioned Office Building with a Multistory Atrium for Thermal Comfort: A Practical Case Study
    Hsu, Hao-Hsiang
    Chiang, Wei-Hwa
    Huang, Jian-Sheng
    [J]. BUILDINGS, 2021, 11 (12)
  • [4] A NATURALLY AIR-CONDITIONED BUILDING
    HAY, HR
    YELLOTT, JI
    [J]. MECHANICAL ENGINEERING, 1970, 92 (01): : 19 - &
  • [5] Relationship of multiple indoor air pollutants and sick building syndrome at air-conditioned office buildings in Taiwan
    Wu, PC
    Li, YY
    Chiang, CM
    Su, HJ
    Lee, CC
    [J]. EPIDEMIOLOGY, 2004, 15 (04) : S16 - S16
  • [6] Ionization of air in an air-conditioned building
    Behounek, F
    Kletschka, J
    [J]. NATURE, 1938, 142 : 956 - 956
  • [7] Indoor air quality in an air-conditioned building in new Delhi and its relationship to ambient air quality
    Prasad, RK
    Uma, R
    Kansal, A
    Gupta, S
    Kumar, P
    Saksena, S
    [J]. INDOOR AND BUILT ENVIRONMENT, 2002, 11 (06) : 334 - 339
  • [8] Field study of performance of solar chimney with air-conditioned building
    Khedari, J
    Rachapradit, N
    Hirunlabh, J
    [J]. ENERGY, 2003, 28 (11) : 1099 - 1114
  • [9] CONSTRUCTION AND OPERATION OF A NATURALLY AIR-CONDITIONED BUILDING
    HAY, HR
    YELLOTT, JI
    [J]. MECHANICAL ENGINEERING, 1969, 91 (03): : 66 - &
  • [10] A case study of energy performance for solar film coating in an air-conditioned commercial building
    Li, Danny Hin Wa
    Wong, Sai Lee
    Mak, Ada Hoi Lam
    [J]. FIRST INTERNATIONAL CONFERENCE ON BUILDING ENERGY AND ENVIRONMENT, PROCEEDINGS VOLS 1-3, 2008, : 176 - 183