An investigation of ventilation control strategies for louver windows in different climate zones

被引:5
|
作者
Scheuring, Leonie [1 ]
Weller, Bernhard [1 ]
机构
[1] Tech Univ Dresden, Inst Bldg Construct, August Bebel Str 30, D-01219 Dresden, Germany
关键词
Indoor air quality; natural ventilation; control strategies; louver window; energy performance; NATURAL VENTILATION; COOLING STRATEGIES;
D O I
10.1080/14733315.2020.1777018
中图分类号
TU [建筑科学];
学科分类号
0813 ;
摘要
Guaranteeing high indoor air quality and high degree of usersatisfaction at the same time is one of the challenges when improving the energy efficiency, namely the energy consumption, of a building. Current non-residential buildings mainly use mechanical ventilation systems to ensure high air quality. Natural ventilation can be an alternative regarding to lower maintenance costs and the psychological feeling of fresh air. Present natural ventilated buildings pose the risk of higher energy demand and less indoor air quality due to user's behaviour. Controlled natural ventilation based on indoor CO2 concentration and room air temperature is needed. However, the energy efficiency of a control strategy highly depends on climate zone and control parameters. This paper aims to explore the impact of different control strategies on the energy efficiency of an operable louver window. The analyses are done for yearly results and then for each month individual to clarify the effect of monthly varying control strategies. For the analysis EnergyPlus as a building energy simulation tool and for the natural ventilation in specific the EnergyPlus Design Flow Rate method is used. In the simulation four window opening strategies based on CO2 concentration and one simple intake/exhaust mechanical ventilation system were tested in Mediterranean, subtropical and moderate climate zone. The highest impact on energy efficiency and thermal comfort was seen at the cold months in the moderate climate. Long window opening strategies cannot be implemented because of a high thermal discomfort. In the hot months in the Mediterranean and subtropical climate an impact of ventilation strategies are seen as well. Only at moderate conditions no major differences in the natural ventilation strategies were observed. When comparing the natural ventilation conditions to mechanical ventilation major differences were found. In almost all climate conditions natural ventilation outperformed the mechanical ventilation. Only in winter months in the moderate climate mechanical ventilation outperforms natural ventilation.
引用
收藏
页码:226 / 235
页数:10
相关论文
共 50 条
  • [31] Thermal comfort investigation of stratified indoor environment in displacement ventilation: Climate-adaptive building with smart windows
    Khalesi, Javad
    Goudarzi, Navid
    [J]. SUSTAINABLE CITIES AND SOCIETY, 2019, 46
  • [32] Exploring the natural ventilation potential of urban climate for high-rise buildings across different climatic zones
    Mao, Rui
    Ma, Zhipeng
    Ning, Haoran
    Cao, Junliang
    [J]. JOURNAL OF CLEANER PRODUCTION, 2024, 475
  • [33] Emission effects of three different ventilation control strategies - A scale model study
    Zhang, G.
    Bjerg, B.
    Strom, J. S.
    Morsing, S.
    Kai, P.
    Tong, G.
    Ravn, P.
    [J]. BIOSYSTEMS ENGINEERING, 2008, 100 (01) : 96 - 104
  • [34] Experimental research on the cross-infection control performance of different ventilation strategies
    Li, Han
    Lan, Yuer
    Liu, Musong
    Kong, Xiangfei
    Fan, Man
    [J]. BUILDING AND ENVIRONMENT, 2023, 243
  • [35] Investigation of annual performance of a building shaded by rooftop PV panels in different climate zones of India
    Bhuvad, Sushant Suresh
    Udayraj
    [J]. RENEWABLE ENERGY, 2022, 189 : 1337 - 1357
  • [36] Assessment of different ventilation strategies on ventilation performance in immersed tunnels
    Linjie Li
    Qiaozhi Qiu
    Xuefu Zhang
    Pai Xu
    Jialiang Liu
    Yilin Li
    Chuangang Fan
    [J]. Environmental Science and Pollution Research, 2021, 28 : 31838 - 31849
  • [37] Assessment of different ventilation strategies on ventilation performance in immersed tunnels
    Li, Linjie
    Qiu, Qiaozhi
    Zhang, Xuefu
    Xu, Pai
    Liu, Jialiang
    Li, Yilin
    Fan, Chuangang
    [J]. ENVIRONMENTAL SCIENCE AND POLLUTION RESEARCH, 2021, 28 (24) : 31838 - 31849
  • [38] Relevant indoor ventilation by windows and apertures in tropical climate: a review study
    Aflaki, Ardalan
    Mahyuddin, Norhayati
    Awad, Zakaria Al-Cheikh Mahmoud
    Baharum, Mohamad Rizal
    [J]. EMERGING TECHNOLOGY FOR SUSTAINABLE DEVELOPMENT CONGRESS (ETSDC 2014), 2014, 3
  • [39] Investigation of varying louver angles and positions on cross ventilation in a generic isolated building using CFD simulation
    Tai, Vin Cent
    Kai-Seun, Joseph Wu
    Mathew, Prasath Reuben
    Moey, Lip Kean
    Cheng, Xinwei
    Baglee, David
    [J]. JOURNAL OF WIND ENGINEERING AND INDUSTRIAL AERODYNAMICS, 2022, 229
  • [40] The Simulation of Natural Ventilation of Buildings with Different Location of Windows/Openings
    Idris, A.
    Huynh, B. P.
    Abdullah, Z.
    [J]. PROCEEDINGS OF THE ASME INTERNATIONAL MECHANICAL ENGINEERING CONGRESS AND EXPOSITION, 2015, VOL 6B, 2016,