Modeling and parametric study for a two-phase loop passive containment cooling system

被引:3
|
作者
Zhang, Keyuan [1 ]
Zhou, Shaofei [2 ]
Wu, Xiaotian [2 ]
Li, Yaru [1 ]
Chi, Xiangyu [1 ]
Nan, Zezhao [1 ]
Wang, Naihua [1 ]
机构
[1] Shandong Univ, Inst Thermal Sci & Technol, Jinan 250061, Peoples R China
[2] China Nucl Power Engn Co Ltd, State Key Lab Nucl Power Safety Monitoring Technol, Shenzhen 518000, Peoples R China
关键词
Passive containment cooling system; Two-phase loop; Filling ratio; Noncondensable gas; Heat transfer characteristic; NON-CONDENSABLE GAS; HEAT-TRANSFER; THERMOSIPHON;
D O I
10.1016/j.applthermaleng.2022.118666
中图分类号
O414.1 [热力学];
学科分类号
摘要
In this study, an optimization method is developed for the structure of the two-phase loop passive containment cooling system. The total heat transfer area of the passive containment cooling system is minimized. At the same time, a new mathematical model is developed with the considerations of the filling ratio and the noncondensable gas inside the loop. On the basis of the mathematical model, the performances of the passive containment cooling system with different filling ratios and noncondensable gas contents are evaluated. Parametric studies are further performed for the key parameters including the operating pressure in the containment, the filling ratio and the noncondensable gas content. The results indicate that the loop heat transfer rate is significantly influenced by these parameters. The effect of the filling ratio on the loop performance is highly related to the optimal filling ratio. The loop heat transfer rate can increase as the filling ratio increases, until the filling ratio reaches the optimal. In addition, the loop heat transfer rate drops by 34% as the noncondensable gas content increases from 0 to 10 kPa, while the corresponding optimal filling ratio increases. As the filling ratio is fixed at 0.56, the difference between the filling ratio and the optimal filling ratio can aggravate the inhibition of noncondensable gas on the loop performance. The reduction of the loop heat transfer rate increases to 37.5% as the noncon-densable gas content reaches 10 kPa.
引用
收藏
页数:16
相关论文
共 50 条
  • [1] Numerical simulation of the evaporator in two-phase thermosyphon loop for passive containment cooling system
    Yin, Xuan
    Wu, Xiaotian
    Zhou, Shaofei
    Zhu, Xixi
    Wang, Naihua
    [J]. ANNALS OF NUCLEAR ENERGY, 2023, 180
  • [2] Experimental investigation of two-phase natural circulation loop as passive containment cooling system
    Lim, Sun Taek
    Kim, Koung Moon
    Kim, Haeseong
    Jerng, Dong-Wook
    Ahn, Ho Seon
    [J]. NUCLEAR ENGINEERING AND TECHNOLOGY, 2021, 53 (12) : 3918 - 3929
  • [3] Experimental investigation of two-phase thermosyphon loop for passive containment cooling
    Yin, Xuan
    Hu, Jian
    Chi, Xiangyu
    Li, Yaru
    Nan, Zezhao
    Wang, Naihua
    [J]. APPLIED THERMAL ENGINEERING, 2021, 184
  • [4] Experimental Investigation of a Two-Phase Closed Thermosyphon Assembly for Passive Containment Cooling System
    Nam, Kyung Ho
    Kim, Sang Nyung
    [J]. ATW-INTERNATIONAL JOURNAL FOR NUCLEAR POWER, 2017, 62 (06): : 413 - +
  • [5] Parametric analyses for the design of a closed-loop passive containment cooling system
    Bang, Jungjin
    Hwang, Ji-Hwan
    Kim, Han Gon
    Jerng, Dong-Wook
    [J]. NUCLEAR ENGINEERING AND TECHNOLOGY, 2021, 53 (04) : 1134 - 1145
  • [6] Study on the performance of an open-loop passive containment cooling system
    Bai, Jinhua
    Zhao, Bo
    Wang, Jianjun
    [J]. JOURNAL OF NUCLEAR SCIENCE AND TECHNOLOGY, 2018, 55 (01) : 113 - 121
  • [7] PASSIVE TWO-PHASE THERMOSYPHON LOOP COOLING SYSTEM FOR HIGH-HEAT-FLUX SERVERS
    Lamaison, N.
    Marcinichen, J. B.
    Szczukiewicz, S.
    Thome, J. R.
    Beucher, P.
    [J]. INTERFACIAL PHENOMENA AND HEAT TRANSFER, 2015, 3 (04) : 369 - 391
  • [8] AN EXPERIMENTAL STUDY OF CLOSED LOOP TWO-PHASE THERMOSYPHON FOR SPENT FUEL POOL PASSIVE COOLING
    Wang, Minglu
    Zheng, Mingguang
    Ye, Cheng
    Qiu, Zhongming
    Xiong, Zhenqin
    [J]. PROCEEDINGS OF THE 24TH INTERNATIONAL CONFERENCE ON NUCLEAR ENGINEERING, 2016, VOL 3, 2016,
  • [9] SIMULATION AND VALIDATION OF A TWO-PHASE PUMPED LOOP COOLING SYSTEM
    Magee, Thomas C.
    Hines, Kristen M.
    Dumesh, Mike A.
    Meekins, Andrew D.
    Bridges, Michael M.
    [J]. PROCEEDINGS OF THE ASME INTERNATIONAL MECHANICAL ENGINEERING CONGRESS AND EXPOSITION, 2019, VOL 8, 2019,
  • [10] Modeling of ESBWR Passive Containment Cooling System with MELCOR
    Sevon, Tuomo
    [J]. 22ND INTERNATIONAL CONFERENCE NUCLEAR ENERGY FOR NEW EUROPE, (NENE 2013), 2013,