Failure analysis of aluminum cable steel reinforced (ACSR) conductor of the transmission line crossing the Parana River

被引:89
|
作者
Azevedo, CRF [1 ]
Cescon, T [1 ]
机构
[1] Inst Pesquisas Tecnol Estado Sao Paulo SA, Lab Failure Anal, BR-01064970 Sao Paulo, Brazil
关键词
failure analysis; power lines; fretting; wear; rupture;
D O I
10.1016/S1350-6307(02)00021-3
中图分类号
TH [机械、仪表工业];
学科分类号
0802 ;
摘要
The failure of the conductor of the 460 kV overhead transmission line located along the crossing of the Parana River was investigated. As a result of this failure, a blackout took place in the southern states of Brazil in January of 2002, reaching approximately 67 million inhabitants. Investigation of the external aluminium layer of the ACSR conductor near the fracture showed typical static deformation marks and dynamic fretting wear tangential marks, both associated with the presence of Al2O3 debris. Additionally, encrusted silicon particles were observed on the external surface of the strands. The internal Al layer showed elliptical deformation marks also associated with Al2O3 debris. Both Al2O3 and Si particles are efficient abrasive material, which associated with slight relative motion of metallic surfaces (clamp/strand and strand/strand) can promote fretting wear. Two types of fracture surface of the Al strands were identified: 45degrees and quasi-normal surfaces, the former being the predominant type. Delamination and particle detachment were the mechanisms of superficial degradation observed on the Al strands, indicating that the rupture of the strands occurred under a gross slip fretting regime induced by sub-conductor oscillation. Inspection of the internal surface of as-cast Al-10%Si spacer clamps revealed different stages of intense circumferential wear caused by the preferential cracking and particle detachment of the eutectic constituent of the as-cast microstructure. This intense wear reduces the clamping contact pressure, which allows higher displacement amplitude and leads to the critical fretting regime. Finally, a few suggestions are discussed to minimise the occurrence of future failures. (C) 2002 Elsevier Science Ltd. All rights reserved.
引用
收藏
页码:645 / 664
页数:20
相关论文
共 21 条
  • [11] Structural failure analysis of a river-crossing transmission line impacted by the super typhoon Rammasun
    An, Liqiang
    Guan, Yongyu
    Zhu, Zhijian
    Wu, Jiong
    Zhang, Ronglun
    ENGINEERING FAILURE ANALYSIS, 2019, 104 : 911 - 931
  • [12] Numerical Analysis of Fretting Wear Characteristics of Aluminum Cable Steel Reinforced Strands
    Zhu, He
    Han, Zhaobing
    Liu, Cheng
    Zhang, Yue
    Chen, Wenlong
    Pan, Shengnan
    STRUCTURES, 2023, 55 : 1497 - 1506
  • [13] Dynamic analysis due to cable rupture of a transmission line tower for large river crossing in Brazil considering the soil-structure interaction
    Kaminski, Joao, Jr.
    Fadel Miguel, Leandro F.
    Riera, Jorge Daniel
    Ramos de Menezes, Ruy Carlos
    Fadel Miguel, Leticia F.
    EURODYN 2014: IX INTERNATIONAL CONFERENCE ON STRUCTURAL DYNAMICS, 2014, : 3715 - 3722
  • [14] An experimental study of dynamic icing process on an Aluminum-Conductor-Steel-Reinforced power cable with twisted outer strands
    Veerakumar, Ramsankar
    Tian, Linchuan
    Hu, Haiyang
    Liu, Yang
    Hu, Hui
    EXPERIMENTAL THERMAL AND FLUID SCIENCE, 2023, 142
  • [15] A framework for application of dynamic line rating to aluminum conductor steel reinforced cables based on mechanical strength and durability
    Morozovska, Kateryna
    Naim, Wadih
    Viafora, Nicola
    Shayesteh, Ebrahim
    Hilber, Patrik
    INTERNATIONAL JOURNAL OF ELECTRICAL POWER & ENERGY SYSTEMS, 2020, 116 (116)
  • [16] Analysis for the mechanism of transmission conductor breakage induced by externally gapped line arrester failure
    Wang, Qian
    Wang, Jian
    Wang, Rui
    Yan, Yucheng
    Xiao, Qingwei
    Wang, Peifeng
    Guo, Deming
    Liu, Gang
    ELECTRIC POWER SYSTEMS RESEARCH, 2025, 241
  • [17] Failure analysis of wire-breaks in aluminum conductor production and investigation of early failure reasons for transmission lines
    Karabay, Sedat
    Erturk, Alpay Tamer
    Zeren, Muzaffer
    Yamanoglu, Ridvan
    Karakulak, Erdem
    ENGINEERING FAILURE ANALYSIS, 2018, 83 : 47 - 56
  • [18] Structural Analysis of Steel Transmission Towers for Large River Crossing of Overhead Transmission Lines A Case Study in Brazil
    Rechtman, Mariana S.
    Motta, Juliana N. M.
    Menezes, Amauri
    da Silva, Jose Guilherme S.
    Longo, Orlando
    ENGINEERING TECHNOLOGY & APPLIED SCIENCE RESEARCH, 2020, 10 (06) : 6438 - 6444
  • [19] Feasibility study for online assessment on fatigue failure of aluminum cable steel reinforced conductors based on DC resistance measurement method
    Mao, Hanling
    Li, Xiaokang
    Mao, Hanying
    Lan, Shun
    Li, Siyue
    Wang, Bang
    Huang, Zhenfeng
    Li, Xinxin
    Tang, Weili
    FATIGUE & FRACTURE OF ENGINEERING MATERIALS & STRUCTURES, 2021, 44 (07) : 1808 - 1821
  • [20] Economic analysis of aluminium conductor composite core and conventional aluminium conductor steel reinforced conductors in overhead ultra-high voltage transmission lines
    Zhang, Yujiao
    Sun, Hongda
    Zhang, Xuankun
    Chen, Zhiwei
    Zhou, Li
    Huang, Xiongfeng
    IET GENERATION TRANSMISSION & DISTRIBUTION, 2023, 17 (05) : 1098 - 1110