Failure analysis of aluminum cable steel reinforced (ACSR) conductor of the transmission line crossing the Parana River

被引:89
|
作者
Azevedo, CRF [1 ]
Cescon, T [1 ]
机构
[1] Inst Pesquisas Tecnol Estado Sao Paulo SA, Lab Failure Anal, BR-01064970 Sao Paulo, Brazil
关键词
failure analysis; power lines; fretting; wear; rupture;
D O I
10.1016/S1350-6307(02)00021-3
中图分类号
TH [机械、仪表工业];
学科分类号
0802 ;
摘要
The failure of the conductor of the 460 kV overhead transmission line located along the crossing of the Parana River was investigated. As a result of this failure, a blackout took place in the southern states of Brazil in January of 2002, reaching approximately 67 million inhabitants. Investigation of the external aluminium layer of the ACSR conductor near the fracture showed typical static deformation marks and dynamic fretting wear tangential marks, both associated with the presence of Al2O3 debris. Additionally, encrusted silicon particles were observed on the external surface of the strands. The internal Al layer showed elliptical deformation marks also associated with Al2O3 debris. Both Al2O3 and Si particles are efficient abrasive material, which associated with slight relative motion of metallic surfaces (clamp/strand and strand/strand) can promote fretting wear. Two types of fracture surface of the Al strands were identified: 45degrees and quasi-normal surfaces, the former being the predominant type. Delamination and particle detachment were the mechanisms of superficial degradation observed on the Al strands, indicating that the rupture of the strands occurred under a gross slip fretting regime induced by sub-conductor oscillation. Inspection of the internal surface of as-cast Al-10%Si spacer clamps revealed different stages of intense circumferential wear caused by the preferential cracking and particle detachment of the eutectic constituent of the as-cast microstructure. This intense wear reduces the clamping contact pressure, which allows higher displacement amplitude and leads to the critical fretting regime. Finally, a few suggestions are discussed to minimise the occurrence of future failures. (C) 2002 Elsevier Science Ltd. All rights reserved.
引用
收藏
页码:645 / 664
页数:20
相关论文
共 21 条
  • [1] Fretting Wear Behaviors of Aluminum Cable Steel Reinforced (ACSR) Conductors in High-Voltage Transmission Line
    Ma, Xingchi
    Gao, Lei
    Zhang, Junxi
    Zhang, Lai-Chang
    METALS, 2017, 7 (09)
  • [2] A Study on the Lifetime Estimates of Aluminum Cable, Steel Reinforced (ACSR) Transmission Lines Under Flame Exposure
    Kim, Young-Dal
    Shim, Jae-Myung
    Lee, Dae-Dong
    TECHNOLOGICAL DEVELOPMENTS IN EDUCATION AND AUTOMATION, 2010, : 513 - +
  • [3] Characterization of an aluminum conductor steel reinforced (ACSR) after 60 years of operation
    Lequien, F.
    Auzoux, Q.
    Moine, G.
    Rousseau, M.
    Pasquier-Tilliette, S.
    Holande, A.
    Ammi, S.
    Heurtault, S.
    Prieur, P.
    ENGINEERING FAILURE ANALYSIS, 2021, 120
  • [4] Effects of Dynamic Line Rating on the Durability and Mechanical Strength of Aluminum Cable Steel Reinforced (ACSR) Conductors
    Naim, Wadih
    Morozovska, Kateryna
    Hilber, Patrik
    INNOVATIVE SOLUTIONS FOR ENERGY TRANSITIONS, 2019, 158 : 3164 - 3169
  • [5] On mechanical waves along aluminum conductor steel reinforced (ACSR) power lines
    Martin, PA
    Berger, JR
    JOURNAL OF APPLIED MECHANICS-TRANSACTIONS OF THE ASME, 2002, 69 (06): : 740 - 748
  • [6] Damage investigation of the aged aluminium cable steel reinforced (ACSR) conductors in a high-voltage transmission line
    Chen, Guohong
    Wang, Xu
    Wang, Jiaqing
    Liu, Junjian
    Zhang, Tao
    Tang, Wenming
    ENGINEERING FAILURE ANALYSIS, 2012, 19 : 13 - 21
  • [7] Conductor Corrosion Inspection of Aluminum Conductor Steel Reinforced Transmission Lines
    Murray, Neal
    Besnard, Fabien
    McGuire, Drew B.
    Scissum, Kuni J.
    2016 IEEE/PES TRANSMISSION AND DISTRIBUTION CONFERENCE AND EXPOSITION (T&D), 2016,
  • [8] HIGH STRENGTH AND HIGH FATIGUE LIMIT ZINC GALVANIZED STEEL CORE WIRE FOR ALUMINUM CONDUCTOR STEEL REINFORCED (ACSR).
    Sudo, Chuzo
    Aihara, Kenji
    Tsukamoto, Takashi
    Nishimura, Shoji
    Sumitomo Metals, 1983, 35 (04): : 63 - 72
  • [9] Sensitivity analysis of Aluminum Conductor Steel Reinforced (ACSR) using historical permeability data from a single wire versus stranded steel core permeability data
    Findlay, RD
    Brocilo, D
    Morgan, VT
    UNIVERSITY AND INDUSTRY - PARTNERS IN SUCCESS, CONFERENCE PROCEEDINGS VOLS 1-2, 1998, : 906 - 909
  • [10] Fretting fatigue in overhead conductors: Rig design and failure analysis of a Grosbeak aluminium cable steel reinforced conductor
    Azevedo, C. R. F.
    Henriques, A. M. D.
    Pulino Filho, A. R.
    Ferreira, J. L. A.
    Araujo, J. A.
    ENGINEERING FAILURE ANALYSIS, 2009, 16 (01) : 136 - 151