Experimental study of a closed loop vertical ground source heat pump system

被引:149
|
作者
Hepbasli, A [1 ]
Akdemir, O
Hancioglu, E
机构
[1] Ege Univ, Dept Mech Engn, Fac Engn, TR-35100 Izmir, Turkey
[2] Ege Univ, Grad Sch Nat & Appl Sci, TR-35100 Izmir, Turkey
关键词
coefficient of performance; energy efficiency; geothermal heat pumps; ground source heat pumps; heat pumps; heating and cooling systems; Izmir (Turkey);
D O I
10.1016/S0196-8904(02)00073-0
中图分类号
O414.1 [热力学];
学科分类号
摘要
Ground source heat pumps (GSHPs), also known as geothermal heat pumps, are a promising new technology that has been used for the last three years in the Turkish market. The main objective of the present study, which was performed for the first time in Turkey at the university level, is to investigate the performance characteristics of a GSHP system with a 50 in vertical 1(1)/(4) in. nominal diameter U-bend ground heat exchanger. This system was installed in a 65 m(2) room in the Solar Energy Institute, Ege University, Izmir (568 degree days cooling, base: 22 degreesC, 1226 degree days heating, base: 18 degreesC), Turkey. The Institute, built in 1986, has a livable floor area of 3000 m(2) and uses passive solar techniques. The heating and cooling loads of the room were 3.8 and 4.2 kW at design conditions, respectively. The system was commissioned in May 2000 and performance tests have been conducted since then. Based upon the measurements made in the heating mode, the heat extraction rate from the soil, with an average thermal diffusivity of 0.00375 m(2)/h, was found to be, on average, 11 W/m of bore depth, while the required borehole length in meter per kW of heating capacity was obtained as 14.7. The entering water temperature to the unit ranged from 5.5 to 13.2 degreesC, with an average value of 8 degreesC. The heating coefficient of performance of the heat pump and the whole system was extremely low when compared to other heat pumps operating under conditions at or near design values. The primary reasons for this were discussed in detail, and the potential for performance improvements was also suggested. (C) 2002 Elsevier Science Ltd. All rights reserved.
引用
收藏
页码:527 / 548
页数:22
相关论文
共 50 条
  • [31] Experimental study of vertical ground-source heat pump performance evaluation for cold climate in Turkey
    Ozyurt, Omer
    Ekinci, Dundar Arif
    [J]. APPLIED ENERGY, 2011, 88 (04) : 1257 - 1265
  • [33] Experimental Study Of Heating-cooling Combined Ground Source Heat Pump System with Horizontal Ground Heat Exchanger
    Hu, Ying-Ning
    Peng, Ban-Jun
    Hu, Shan-Shan
    Lin, Jun
    [J]. SUSTAINABLE DEVELOPMENT OF URBAN ENVIRONMENT AND BUILDING MATERIAL, PTS 1-4, 2012, 374-377 : 398 - 404
  • [34] Numerical and experimental study of a closed loop for ground heat exchanger coupled with heat pump system and a solar collector for heating a glass greenhouse in north of Tunisia
    Awani, S.
    Kooli, S.
    Chargui, R.
    Guizani, A.
    [J]. INTERNATIONAL JOURNAL OF REFRIGERATION-REVUE INTERNATIONALE DU FROID, 2017, 76 : 328 - 341
  • [35] Experimental and Simulant Study on Vertical U-Tube Underground Heat Exchanger in Ground-Source Heat Pump
    Gao, Zhen
    Ma, Jinwei
    Yu, Xiaochun
    Zhang, Yu
    Hu, Ning
    Wang, Yanping
    [J]. PROCEEDINGS OF THE 2015 4TH INTERNATIONAL CONFERENCE ON SUSTAINABLE ENERGY AND ENVIRONMENTAL ENGINEERING, 2016, 53 : 636 - 641
  • [36] Experimental investigation and control optimization of a ground source heat pump system
    Xia, Lei
    Ma, Zhenjun
    McLauchlan, Craig
    Wang, Shugang
    [J]. APPLIED THERMAL ENGINEERING, 2017, 127 : 70 - 80
  • [37] EXPERIMENTAL STUDY OF HEAT TRANSFER OF BOREHOLES IN CLOSED LOOP VERTICAL GROUND HEAT EXCHANGERS IN A COLD WINTER AND HOT SUMMER AREA
    Qian, H.
    Ren, Q.
    Zhang, X.
    Shi, Y.
    [J]. 23RD IIR INTERNATIONAL CONGRESS OF REFRIGERATION, 2011, 23 : 4225 - +
  • [38] Influence of closed loop ground source heat pumps on groundwater: a case study
    Park, Youngyun
    Mok, Jong-Koo
    Jang, Bum-Ju
    Lee, Jin-Yong
    Park, Yu-Chul
    [J]. JOURNAL OF THE GEOLOGICAL SOCIETY OF KOREA, 2015, 51 (02) : 243 - 251
  • [39] Simulation study on the thermal performance of vertical U-tube heat exchangers for ground source heat pump system
    Pu, Liang
    Qi, Di
    Li, Kang
    Tan, Hongbo
    Li, Yanzhong
    [J]. APPLIED THERMAL ENGINEERING, 2015, 79 : 202 - 213
  • [40] Experimental study of refrigeration operating characteristics of ground source heat pump
    Fu, Yunzhun
    Cai, Yingling
    Han, Jianjie
    Yang, Lin
    [J]. Taiyangneng Xuebao/Acta Energiae Solaris Sinica, 2014, 35 (12): : 2508 - 2513