Utilizing heat pipe heat exchanger to reduce the energy consumption of airborne infection isolation hospital room HVAC system

被引:33
|
作者
Sukarno, Ragil [1 ]
Putra, Nandy [1 ]
Hakim, Imansyah Ibnu [1 ]
Rachman, Fadhil Fuad [1 ]
Mahlia, Teuku Meurah Indra [2 ]
机构
[1] Univ Indonesia, Appl Heat Transfer Res Grp, Dept Mech Engn, Kampus UI, Depok 16424, Indonesia
[2] Univ Technol Sydney, Sch Informat Syst & Modelling, Fac Engn & Informat Technol, Sydney, NSW 2007, Australia
来源
关键词
Heat-pipe heat exchanger; HVAC; Airborne infection isolation room; Recovery energy; AIR-CONDITIONING SYSTEM; THERMAL PERFORMANCE; RECOVERY;
D O I
10.1016/j.jobe.2020.102116
中图分类号
TU [建筑科学];
学科分类号
0813 ;
摘要
The COVID-19 pandemic in early 2020 became a global issue and received substantial attention worldwide. In a hospital, airborne infection isolation (AII) room is significant to prevent the spread of the virus to patients and medical personnel. This research aims to improve the design of the HVAC system of AII room used for removing contaminated air by making physical changes through the addition of heat pipe heat exchanger (HPHE). Experiments were conducted with varying fresh air inlet temperature between 30 and 45 degrees C and velocity between 1.5 and 2.5 m/s with three configurations of HPHE to investigate the performance of the HVAC system in the AII room. To ensure the HVAC system with HPHE meets the AII room requirements, this study carried out a smoke test as well as pressure and hourly air volume measurement tests between the exhaust and supply air sides. The results showed that the design of ventilation coupled with HPHE could meet the standards for the AII room. The HPHE succeeded in reducing energy consumption through pre-cooling of fresh air before entering the cooling coil device, with the highest temperature difference of 9.4 degrees C. The highest energy recovery was 767 W at 0.080 m(3)/s air volume, which can handle 46% of the total HVAC system load at operating conditions and enhance the combined efficiency of the HVAC system. Based on the results, it can be concluded that the HPHE can be coupled in the HVAC system of the hospital AII room that is safe from cross-contamination which significantly reduces the energy consumption.
引用
收藏
页数:9
相关论文
共 33 条
  • [1] Multi-stage heat-pipe heat exchanger for improving energy efficiency of the HVAC system in a hospital operating room
    Sukarno, Ragil
    Putra, Nandy
    Hakim, Imansyah Ibnu
    Rachman, Fadhil Fuad
    Mahlia, Teuku Meurah Indra
    [J]. INTERNATIONAL JOURNAL OF LOW-CARBON TECHNOLOGIES, 2021, 16 (02) : 259 - 267
  • [2] Non-dimensional analysis for heat pipe characteristics in the heat pipe heat exchanger as energy recovery device in the HVAC systems
    Sukarno, Ragil
    Putra, Nandy
    Hakim, Imansyah Ibnu
    [J]. THERMAL SCIENCE AND ENGINEERING PROGRESS, 2021, 26
  • [3] Energy conservation of HVAC systems in isolation rooms using heat pipe heat exchangers
    Amir, Fazri
    Rizal, Samsul
    Thaib, Razali
    Umar, Hamdani
    Ikramullah, Ikramullah
    Abdullah, Nasruddin A.
    Rizal, Teuku Azuar
    [J]. HELIYON, 2024, 10 (02)
  • [4] Utilization of U-shaped finned heat pipe heat exchanger in energy-efficient HVAC systems
    Hakim, Imansyah Ibnu
    Sukarno, Ragil
    Putra, Nandy
    [J]. THERMAL SCIENCE AND ENGINEERING PROGRESS, 2021, 25
  • [5] THE APPLICATION OF U-SHAPE HEAT PIPE HEAT EXCHANGER TO REDUCE RELATIVE HUMIDITY FOR ENERGY CONSERVATION IN HEATING, VENTILATION, AND AIR CONDITIONING (HVAC) SYSTEMS
    Kusumah, Aliefka Satria
    Hakim, Imansyah Ibnu
    Sukarno, Ragil
    Rachman, Fadhil Fuad
    Putra, Nandy
    [J]. INTERNATIONAL JOURNAL OF TECHNOLOGY, 2019, 10 (06) : 1202 - 1210
  • [6] Application of a heat pipe heat exchanger to dehumidification enhancement in a HVAC system for tropical climates - a baseline performance characteristics study
    Yau, Yat H.
    [J]. INTERNATIONAL JOURNAL OF THERMAL SCIENCES, 2007, 46 (02) : 164 - 171
  • [7] Withering of tea leaves using heat pipe heat exchanger by utilizing low-temperature geothermal energy
    Gunawan, Yohanes
    Putra, Nandy
    Hakim, Imansyah Ibnu
    Agustina, Dinni
    Mahlia, Teuku Meurah Indra
    [J]. INTERNATIONAL JOURNAL OF LOW-CARBON TECHNOLOGIES, 2021, 16 (01) : 146 - 155
  • [8] An investigation into the use of water as a working fluid in wraparound loop heat pipe heat exchanger for applications in energy efficient HVAC systems
    Jouhara, Hussam
    Meskimmon, Richard
    [J]. ENERGY, 2018, 156 : 597 - 605
  • [9] Experimental study on utilization of heat pipe heat exchanger for improving efficiency of clean room air system in hospitals
    Hakim, Imansyah Ibnu
    Putra, Nandy
    Marda, Adam Prihananda
    Alvaro, Muhammad Alvin
    Winarta, Adi
    [J]. 3RD INTERNATIONAL TROPICAL RENEWABLE ENERGY CONFERENCE SUSTAINABLE DEVELOPMENT OF TROPICAL RENEWABLE ENERGY (I-TREC 2018), 2018, 67
  • [10] The application of heat pipe heat exchangers to improve the air quality and reduce the energy consumption of the air conditioning system in a hospital ward-A full year model simulation
    Ahmadzadehtalatapeh, M.
    Yau, Y. H.
    [J]. ENERGY AND BUILDINGS, 2011, 43 (09) : 2344 - 2355