Energy conservation of HVAC systems in isolation rooms using heat pipe heat exchangers

被引:1
|
作者
Amir, Fazri [1 ,3 ]
Rizal, Samsul [2 ]
Thaib, Razali [2 ]
Umar, Hamdani [2 ]
Ikramullah, Ikramullah [2 ]
Abdullah, Nasruddin A. [3 ]
Rizal, Teuku Azuar [3 ]
机构
[1] Univ Syiah Kuala, Sch Engn, Doctoral Program, Banda Aceh 23111, Indonesia
[2] Univ Syiah Kuala, Dept Mech & Ind Engn, Banda Aceh 23111, Indonesia
[3] Univ Samudra, Dept Mech Engn, Langsa 24416, Indonesia
关键词
Energy conservation; Heating; Ventilation; And air conditioning; Isolation room; Heat pipe heat exchanger; RECOVERY;
D O I
10.1016/j.heliyon.2024.e24288
中图分类号
O [数理科学和化学]; P [天文学、地球科学]; Q [生物科学]; N [自然科学总论];
学科分类号
07 ; 0710 ; 09 ;
摘要
Isolation rooms are crucial in healthcare facilities to prevent the spread of infectious diseases. Infectious diseases can be transmitted to humans from humans or through animals known as zoonoses. With the increase in the number of COVID-19 cases, isolation rooms have become one of the most critical facilities in hospitals. Maintaining the correct temperature and humidity in these isolation rooms is a challenge, considering the heating, ventilation, and air conditioning (HVAC) systems that continuously consume large amounts of energy. With the application of energy conservation methods, the total energy consumption of HVAC systems can be reduced. Many studies have shown that the heat pipe heat exchanger (HPHE) technology can contribute significantly to energy savings using HVAC systems. In this study, the effectiveness of an HPHE on an HVAC system in an isolation room was examined, and the total energy reduction was quantified. The HPHE consisted of two rows with ten heat pipes in each row, arranged in a staggered configuration with fresh air temperature and mass flow variations. The inlet fresh air temperatures varied at 32, 35, 37, and 40 C and fresh air velocities at 1.2, 1.6, 2.2, and 2.6 m/s. Using a chiller, the inlet fresh air was cooled to a comfortable temperature zone, approximately 24.4-25.2 C-degrees, in the isolation room. Notably, higher velocities decreased the effectiveness of the HPHE. An increase in the flow rate enhanced the system, thereby improving the heat recovery value. The increase in the inlet fresh air temperature from 32 C-degrees, that yielded an energy saving of 1.23 W, to 40 C-degrees, resulted in a further energy saving of 1.85 W. The application of the HPHE in the HVAC system in isolation rooms represents a significant innovation that contributes to a reduction in total energy consumption.
引用
收藏
页数:10
相关论文
共 50 条
  • [1] HEAT PIPE EXCHANGERS AND ENERGY CONSERVATION.
    Wang Lijian
    [J]. Hunan Keji Daxue Xuebao/Journal of Hunan Science and Technology University, 1985, 1 (1-2): : 169 - 176
  • [2] Heat recovery and dehumidification enhancement in HVAC systems using heat pipe
    Saidi, M. H.
    Talaee, M. R.
    Babaie, H. Ali
    [J]. PROCEEDINGS OF THE 3RD ASIAN CONFERENCE ON REFRIGERATION AND AIR-CONDITIONING VOLS I AND II, 2006, : 749 - +
  • [3] Heat pipe heat exchangers in energy technology
    Groll, M
    [J]. ENERGY AND ENVIRONMENT, 1998, : 235 - 244
  • [4] A testing and HVAC design methodology for air-to-air heat pipe heat exchangers
    Guo, PB
    Ciepliski, DL
    Besant, RW
    [J]. HVAC&R RESEARCH, 1998, 4 (01): : 3 - 26
  • [5] Non-dimensional analysis for heat pipe characteristics in the heat pipe heat exchanger as energy recovery device in the HVAC systems
    Sukarno, Ragil
    Putra, Nandy
    Hakim, Imansyah Ibnu
    [J]. THERMAL SCIENCE AND ENGINEERING PROGRESS, 2021, 26
  • [6] HEAT PIPE HEAT-EXCHANGERS IN HEAT-RECOVERY SYSTEMS
    STULC, P
    VASILIEV, LL
    KISELJEV, VG
    MATVEJEV, JN
    [J]. JOURNAL OF HEAT RECOVERY SYSTEMS, 1985, 5 (05): : 415 - 418
  • [7] HEAT PIPES AND HEAT PIPE EXCHANGERS FOR HEAT-RECOVERY SYSTEMS
    VASILIEV, LL
    GRAKOVICH, LP
    KISELEV, VG
    MATVEEV, Y
    KHRUSTALEV, DK
    [J]. JOURNAL OF HEAT RECOVERY SYSTEMS, 1984, 4 (04): : 227 - 233
  • [8] Energy conservation by waste heat recovery in industry using thermosyphon heat exchangers
    Noie, SH
    Lotfi, M
    Saghatoleslami, N
    [J]. IRANIAN JOURNAL OF SCIENCE AND TECHNOLOGY, 2004, 28 (B6): : 707 - 712
  • [9] Using Approach to Assess the Condition of HVAC Heat Exchangers
    Gallagher, Mike
    [J]. ASHRAE Journal, 2024, 66 (01) : 20 - 22
  • [10] Utilizing heat pipe heat exchanger to reduce the energy consumption of airborne infection isolation hospital room HVAC system
    Sukarno, Ragil
    Putra, Nandy
    Hakim, Imansyah Ibnu
    Rachman, Fadhil Fuad
    Mahlia, Teuku Meurah Indra
    [J]. JOURNAL OF BUILDING ENGINEERING, 2021, 35